Transformer Protection Settings
Transformer Protection Settings
2. Calculate ICT multipliers & vectors – These are used to match errors due to
CT ratio mismatch of HV and LV side .
2. Establish Required protection Settings
a)87BD
b)87HS
Sample Graph for Differential relay As X axis is restraining current and Y axis is
differential current.
Slope2- It is used for stable operation for through faults of high magnitudes.
87HS- High set setting which is used to clear high faults within the transformer
and it is based on through fault
7XIn is choosen.
REF is more sensitive than overall biased differential protection (87BD) to earth
faults it can protect against faults for a greater portion of the transformer
windings or where the impedance in the earth fault path is relatively high.
For a solidly earthed star winding, the REF function is roughly twice as sensitive
in detecting a winding earth fault, than biased differential protection.
Calculations –
CT Ratio-HV 150 1 A
CT Ratio-LV 550 1 A
131.2198
HV Side Full load Current Pri 2 A
HV Side Full load Current 0.874798
Sec 8 A
524.8792
LV Side Full load Current Pri 8 A
LV Side Full load Current
Sec 0.954326 A
2. Ict Multiplier Setting and interposed ct connection
1
0.87
Ict at 1.14942
HV side 5
1
0.95
Ict at LV 1.05263
side 2
W1 phase input: 1A
W1 CT ratio : 150/1A
W2 phase input : 1A
W2 CT ratio : 550/1A
Overfluxing Function-
Why overflux produced
1. Switching effect
2. Tap changing
3. High loading of transformers
Effects
1.Harmonics is produced
2. Over heat is produced
3. Non sinusoidal Output is produced
Equation
Eb=4.4fNⱷ
Where
Eb= Voltage & 4.4 is constant
N= no. of turns
f= Frequency
ⱷ= Flux produced
so V/f is produce
Alarm – 110%
Alarm time- 4 sec
Trip - 120%
Trip time -8sec
As Vrn= 63.5
f= 50
V/f = 63.5/50=1.27
V/f= 110%
V/f= 1.27*1.1=1.397
V= 1.397*50=69.85V
Trip = 120%
V/f=63.5/50=1.27
V/f=1.27*1.2
V/f= 1.524
V=50*1.524=76.2V
BACK UP PROTECTION
1. Non directional overcurrent –
Stage 1 – 110% of FLC
Delay – 50 ms(may change if coordination is to be carried out)
Stage 2 – Short ckt. Current of transformer
Delay – 0ms
2. Non directional earthfault-
Stage1- 10% of FLC (may change if coordination is to be carried out)
Delay- 30ms
Stage2 – 20 % of FLC
Delay – 0ms
These setting are general and are load dependent and may vary as
transformer rating is changed.