HVAC Sizing Analysis for Bengaluru Project

The document provides cooling and heating load calculations for a project in Bangaluru, India. It summarizes the coincident peak cooling and heating loads for the entire building. It also provides details on the proposed chilled water plant, including the electric water-cooled chiller and cooling tower capacities and pump powers. Finally, it lists the peak cooling and heating loads for one air handling unit serving different zones in the building.

Uploaded by

U DEEPAK
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
129 views10 pages

HVAC Sizing Analysis for Bengaluru Project

The document provides cooling and heating load calculations for a project in Bangaluru, India. It summarizes the coincident peak cooling and heating loads for the entire building. It also provides details on the proposed chilled water plant, including the electric water-cooled chiller and cooling tower capacities and pump powers. Finally, it lists the peak cooling and heating loads for one air handling unit serving different zones in the building.

Uploaded by

U DEEPAK
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

HVAC Sizing IES VIRTUAL ENVIRONMENT

Project and Climate


VE 2019
Model Data Cooling Calculation Data
Project file HVAC [Link] Results file Load [Link]
Source HVAC file [Link] Calculated 2020/04/11 11:57
HVAC file snapshot Vista\Load [Link] Profile Month Jan - Dec
Model floor area 13,782.1 m² Max outdoor temp. dry bulb 35.2 °C
Building conditioned floor area 13,782.1 m² Max outdoor temp. wet bulb 22.4 °C
Building conditioned volume 48,237.3 m³
Heating Calculation Data
Number of conditioned rooms 4
Results file Load [Link]
Load analysis methodology ASHRAE Heat Balance Method
Calculated 2020/04/11 11:57
Calculated 2020/04/11 11:58
Profile Month Jan
Version No. 2019.1.0.0
Outdoor winter design temp 15.3 °C

Location Data Project Loads Summary


Location Bangaluru , India Cooling loads: kW W/m²
Latitude 12.97 N Coincident peak space load 759.11 55.08
Longitude 77.58 E Coincident peak plant & equipment load 1,188.92 86.27
Altitude 921.0 m Heating loads:
Time Zone 5.5 hours ahead of GMT Coincident peak space load 8.23 0.60
Coincident peak plant & equipment load 0.00 0.00
Design Weather Data
Source ASHRAE design weather database
Monthly percentile:
For heating loads design weather 99.60 %
For cooling loads design weather 0.40 %
Barometric pressure 90,757.6 Pa
Air density 1.200 kg/m³
Air specific heat 1.019 kJ/kg·K
Density-specific heat product 1.223 kJ/m³·K
Summer ground reflectance 0.2
Winter ground reflectance 0.2
Carbon dioxide (ambient) 400.00 ppm

Project Cooling and Heating loads are coincident peak value for all conditioned spaces without oversizing. Load run | 2020/04/11 11:58 | Project and climate - Page 1 of 1
HVAC Sizing IES VIRTUAL ENVIRONMENT
Plant Loops and Equipment
VE 2019
Chilled Water Loop (1 of 1)
One Electric Water-Cooled Chiller with VSD pump on
Name Secondary CHW Loop
Cooling capacity 1,367.26 kW
Primary design flow rate 49.04 l/s
Primary pump power 3,420 W
Secondary design flow rate 50.09 l/s
Secondary pump power 13,974 W
Condenser loop design capacity 1,608.47 kW
Condenser loop design flow rate 68.43 l/s
Condenser loop pump power 20,608 W
Pre-cooling loop capacity -
Equimpment Capacity:
EWC Chiller with default values and VSD sec'd
pump, 2-sp clg tower fan 1,367.26 kW
CWL Cooling Tower 1,608.47 kW

Equipment and loop capacities include oversizing. Load run | 2020/04/11 11:58 | Plant loops & equipment - Page 1 of 1
HVAC Sizing IES VIRTUAL ENVIRONMENT
System Loads Report
03 c AHU GF - Layer 1 VE 2019
ZONE COOLING COIL PEAK SYSTEM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 16:30 5 / 16:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 31.7 / 22.2 / 44.8 34.1 / 20.7 / 30.5 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Zones RA Plenum Net Percent Zones Percent Zones RA Plenum Net Percent Roof 0.0 0.0 -
Value of Total (Sensible) of Total Value of Total External Floor 3,445.5 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 5,632 - 5,632 1.8 6,258 3.0 External Walls - - - - Partition/Door 0.0 - -
Roofs 0 - 0 0.0 0 0.0 Roofs - - - - Internal Ceiling 3,445.5 - -
Ground/Exposed Floors 27,918 - 27,918 9.1 40,321 19.5 Ground/Exposed Floors - - - - Internal Floor 0.0 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 7,758 - 7,758 2.5 9,387 4.5 Windows Conduction - - - - TEMPERATURES
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 12,924 - 12,924 4.2 12,031 5.8 Solar - - - -
Supply Air (design) 12.8
Infiltration 5,263 - 5,263 1.7 6,899 3.3 Infiltration - - - -
Supply Air (actual) 14.3 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Return Air (actual) 24.3 -
Internal Building Gains/Losses Internal Building Gains/Losses Plenum (actual) - -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Mixed Air (actual) 26.0 -
Internal Floors/Air/Furn. -37 - -37 0.0 -36 0.0 Internal Floors/Air/Furn. - - - - Fan Blade Temperature Rise (dT) 0.3 0.3
Ceilings 2,326 - 2,326 0.8 3,362 1.6 Ceilings - - - - Fan Motor Temperature Rise (dT) 0.0 0.0
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Configuration Blow-through Undetermined
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - -
Non-Principal Spaces - - - - - - Non-Principal Spaces - - - - AIRFLOW
Cooling Heating
Sub Total 61,785 0 61,785 78,222 Sub Total 0 0 0 l/s l/s
Supply (design) 15,504 15,504
Internal Gains Internal Gains Supply (actual) 15,504 4,651
Lights 40,796 - 40,796 13.3 40,796 19.7 Lights - - - - Reheat Minimum (design) 4,651 4,651
People 50,489 - 50,489 16.5 50,489 24.4 People - - - - Leakage at Design Flow 0 0
Misc, Computers, Equip 37,087 - 37,087 12.1 37,087 18.0 Misc, Computers, Equip - - - - Return (actual) 15,504 -
Exhaust and Relief (actual) 3,446 -
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
Ventilation (requirement) 3,446 3,446
Mechanical Gains/Losses Mechanical Gains/Losses Ventilation (actual) 3,446 -
Ventilation (sensible) 32,402 - 32,402 10.6 - - Ventilation (sensible) - - - - Infiltration 559 -
Transfer Air † - - - - - - Transfer Air † - - - -
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - CHECKS
Fans 6,130 - 6,130 2.0 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - - Number of People 689.10
m²/Person 5.00
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
W/m² - Cooling 88.80
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
W/m² - Heating 0.00
Latent Cooling 77,288 - 77,288 25.3 - -
m²/kW - Cooling 11.26
Dehumid Oversizing † - - - - - - m²/kW - Heating -
Sub Total 115,820 0 115,820 0 Sub Total 0 0 0 l/s/m² - Cooling 4.50
l/s/m² - Heating 1.35
TOTAL 305,977 0 305,977 100 206,594 100 TOTAL 0 0 0 0 % Outside Air - Cooling 22.22
% Outside Air - Heating 74.08
COOLING COILS HEATING COILS Outdoor Air l/s/m² 1.00
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH Total Capacity Airflow Enter Leave
Outdoor Air l/s/person 5.00
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
Peak Latent Load (W) 89,232.12
System Cooling ‡ - - - - - - - - - - System Heating - - - - Sensible Heat Ratio 0.75
Ventilation - - - - - - - - - - Ventilation - - - -
Indirect Evap - - - - - - - - - - Pre-Heat - - - -
Direct Evap - - - - - - - - - -

TOTAL 0.0 0.0 0.0 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | System loads - Page 1 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration
HVAC Sizing IES VIRTUAL ENVIRONMENT
System Loads Report
03 c AHU FF - Layer 1 VE 2019
ZONE COOLING COIL PEAK SYSTEM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 8:30 5 / 8:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 27.0 / 20.9 / 58.8 28.2 / 19.0 / 42.7 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Zones RA Plenum Net Percent Zones Percent Zones RA Plenum Net Percent Roof 0.0 0.0 -
Value of Total (Sensible) of Total Value of Total External Floor 0.0 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 1,906 - 1,906 0.6 2,124 1.1 External Walls - - - - Partition/Door 0.0 - -
Roofs 0 - 0 0.0 0 0.0 Roofs - - - - Internal Ceiling 3,445.5 - -
Ground/Exposed Floors 0 - 0 0.0 0 0.0 Ground/Exposed Floors - - - - Internal Floor 3,445.5 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 2,881 - 2,881 1.0 3,372 1.8 Windows Conduction - - - - TEMPERATURES
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 13,240 - 13,240 4.4 12,789 6.9 Solar - - - -
Supply Air (design) 12.8
Infiltration 1,278 - 1,278 0.4 1,876 1.0 Infiltration - - - -
Supply Air (actual) 13.3 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Return Air (actual) 24.7 -
Internal Building Gains/Losses Internal Building Gains/Losses Plenum (actual) - -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Mixed Air (actual) 25.4 -
Internal Floors/Air/Furn. 27,080 - 27,080 9.1 32,749 17.6 Internal Floors/Air/Furn. - - - - Fan Blade Temperature Rise (dT) 0.3 0.3
Ceilings 4,167 - 4,167 1.4 5,301 2.8 Ceilings - - - - Fan Motor Temperature Rise (dT) 0.0 0.0
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Configuration Blow-through Undetermined
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - -
Non-Principal Spaces - - - - - - Non-Principal Spaces - - - - AIRFLOW
Cooling Heating
Sub Total 50,551 0 50,551 58,211 Sub Total 0 0 0 l/s l/s
Supply (design) 12,930 12,930
Internal Gains Internal Gains Supply (actual) 12,930 3,879
Lights 40,796 - 40,796 13.7 40,796 21.9 Lights - - - - Reheat Minimum (design) 3,879 3,879
People 50,489 - 50,489 16.9 50,489 27.1 People - - - - Leakage at Design Flow 0 0
Misc, Computers, Equip 37,087 - 37,087 12.4 37,087 19.9 Misc, Computers, Equip - - - - Return (actual) 12,930 -
Exhaust and Relief (actual) 3,446 -
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
Ventilation (requirement) 3,446 3,446
Mechanical Gains/Losses Mechanical Gains/Losses Ventilation (actual) 3,446 -
Ventilation (sensible) 10,927 - 10,927 3.7 - - Ventilation (sensible) - - - - Infiltration 559 -
Transfer Air † - - - - - - Transfer Air † - - - -
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - CHECKS
Fans 5,112 - 5,112 1.7 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - - Number of People 689.10
m²/Person 5.00
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
W/m² - Cooling 86.67
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
W/m² - Heating 0.00
Latent Cooling 103,655 - 103,655 34.7 - -
m²/kW - Cooling 11.54
Dehumid Oversizing † - - - - - - m²/kW - Heating -
Sub Total 119,694 0 119,694 0 Sub Total 0 0 0 l/s/m² - Cooling 3.75
l/s/m² - Heating 1.13
TOTAL 298,618 0 298,618 100 186,584 100 TOTAL 0 0 0 0 % Outside Air - Cooling 26.65
% Outside Air - Heating 88.83
COOLING COILS HEATING COILS Outdoor Air l/s/m² 1.00
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH Total Capacity Airflow Enter Leave
Outdoor Air l/s/person 5.00
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
Peak Latent Load (W) 103,654.89
System Cooling ‡ - - - - - - - - - - System Heating - - - - Sensible Heat Ratio 0.65
Ventilation - - - - - - - - - - Ventilation - - - -
Indirect Evap - - - - - - - - - - Pre-Heat - - - -
Direct Evap - - - - - - - - - -

TOTAL 0.0 0.0 0.0 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | System loads - Page 2 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration
HVAC Sizing IES VIRTUAL ENVIRONMENT
System Loads Report
03 c AHU SF - Layer 1 VE 2019
ZONE COOLING COIL PEAK SYSTEM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 8:30 5 / 8:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 27.0 / 20.9 / 58.8 28.2 / 19.0 / 42.7 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Zones RA Plenum Net Percent Zones Percent Zones RA Plenum Net Percent Roof 0.0 0.0 -
Value of Total (Sensible) of Total Value of Total External Floor 0.0 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 1,772 - 1,772 0.6 1,953 1.1 External Walls - - - - Partition/Door 0.0 - -
Roofs 0 - 0 0.0 0 0.0 Roofs - - - - Internal Ceiling 3,445.5 - -
Ground/Exposed Floors 0 - 0 0.0 0 0.0 Ground/Exposed Floors - - - - Internal Floor 3,445.5 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 2,912 - 2,912 1.0 3,450 1.9 Windows Conduction - - - - TEMPERATURES
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 13,240 - 13,240 4.5 12,789 7.1 Solar - - - -
Supply Air (design) 12.8
Infiltration 1,292 - 1,292 0.4 1,923 1.1 Infiltration - - - -
Supply Air (actual) 13.3 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Return Air (actual) 24.6 -
Internal Building Gains/Losses Internal Building Gains/Losses Plenum (actual) - -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Mixed Air (actual) 25.3 -
Internal Floors/Air/Furn. 22,199 - 22,199 7.6 25,847 14.3 Internal Floors/Air/Furn. - - - - Fan Blade Temperature Rise (dT) 0.3 0.3
Ceilings 4,588 - 4,588 1.6 5,824 3.2 Ceilings - - - - Fan Motor Temperature Rise (dT) 0.0 0.0
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Configuration Blow-through Undetermined
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - -
Non-Principal Spaces - - - - - - Non-Principal Spaces - - - - AIRFLOW
Cooling Heating
Sub Total 46,003 0 46,003 51,785 Sub Total 0 0 0 l/s l/s
Supply (design) 12,600 12,600
Internal Gains Internal Gains Supply (actual) 12,600 3,780
Lights 40,796 - 40,796 13.9 40,796 22.6 Lights - - - - Reheat Minimum (design) 3,780 3,780
People 50,489 - 50,489 17.2 50,489 28.0 People - - - - Leakage at Design Flow 0 0
Misc, Computers, Equip 37,087 - 37,087 12.7 37,087 20.6 Misc, Computers, Equip - - - - Return (actual) 12,600 -
Exhaust and Relief (actual) 3,446 -
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
Ventilation (requirement) 3,446 3,446
Mechanical Gains/Losses Mechanical Gains/Losses Ventilation (actual) 3,446 -
Ventilation (sensible) 10,693 - 10,693 3.6 - - Ventilation (sensible) - - - - Infiltration 559 -
Transfer Air † - - - - - - Transfer Air † - - - -
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - CHECKS
Fans 4,982 - 4,982 1.7 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - - Number of People 689.10
m²/Person 5.00
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
W/m² - Cooling 85.08
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
W/m² - Heating 0.00
Latent Cooling 103,080 - 103,080 35.2 - -
m²/kW - Cooling 11.75
Dehumid Oversizing † - - - - - - m²/kW - Heating -
Sub Total 118,755 0 118,755 0 Sub Total 0 0 0 l/s/m² - Cooling 3.66
l/s/m² - Heating 1.10
TOTAL 293,130 0 293,130 100 180,158 100 TOTAL 0 0 0 0 % Outside Air - Cooling 27.34
% Outside Air - Heating 91.15
COOLING COILS HEATING COILS Outdoor Air l/s/m² 1.00
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH Total Capacity Airflow Enter Leave
Outdoor Air l/s/person 5.00
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
Peak Latent Load (W) 103,080.27
System Cooling ‡ - - - - - - - - - - System Heating - - - - Sensible Heat Ratio 0.65
Ventilation - - - - - - - - - - Ventilation - - - -
Indirect Evap - - - - - - - - - - Pre-Heat - - - -
Direct Evap - - - - - - - - - -

TOTAL 0.0 0.0 0.0 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | System loads - Page 3 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration
HVAC Sizing IES VIRTUAL ENVIRONMENT
System Loads Report
03 c AHU TF - Layer 1 VE 2019
ZONE COOLING COIL PEAK SYSTEM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 14:30 5 / 14:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 32.5 / 22.4 / 42.9 35.1 / 21.0 / 28.9 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Zones RA Plenum Net Percent Zones Percent Zones RA Plenum Net Percent Roof 3,445.5 0.0 0.0
Value of Total (Sensible) of Total Value of Total External Floor 0.0 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 4,970 - 4,970 1.6 5,634 2.8 External Walls - - - - Partition/Door 0.0 - -
Roofs 36,481 - 36,481 11.5 38,237 19.0 Roofs - - - - Internal Ceiling 0.0 - -
Ground/Exposed Floors 0 - 0 0.0 0 0.0 Ground/Exposed Floors - - - - Internal Floor 3,445.5 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 9,540 - 9,540 3.0 11,506 5.7 Windows Conduction - - - - TEMPERATURES
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 11,640 - 11,640 3.7 11,730 5.8 Solar - - - -
Supply Air (design) 12.8
Infiltration 5,487 - 5,487 1.7 7,221 3.6 Infiltration - - - -
Supply Air (actual) 13.7 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Return Air (actual) 24.4 -
Internal Building Gains/Losses Internal Building Gains/Losses Plenum (actual) - -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Mixed Air (actual) 26.2 -
Internal Floors/Air/Furn. -1,801 - -1,801 -0.6 -937 -0.5 Internal Floors/Air/Furn. - - - - Fan Blade Temperature Rise (dT) 0.3 0.3
Ceilings 0 - 0 0.0 0 0.0 Ceilings - - - - Fan Motor Temperature Rise (dT) 0.0 0.0
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Configuration Blow-through Undetermined
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - -
Non-Principal Spaces - - - - - - Non-Principal Spaces - - - - AIRFLOW
Cooling Heating
Sub Total 66,318 0 66,318 73,391 Sub Total 0 0 0 l/s l/s
Supply (design) 14,934 14,934
Internal Gains Internal Gains Supply (actual) 14,934 4,480
Lights 40,796 - 40,796 12.9 40,796 20.2 Lights - - - - Reheat Minimum (design) 4,480 4,480
People 50,489 - 50,489 16.0 50,489 25.0 People - - - - Leakage at Design Flow 0 0
Misc, Computers, Equip 37,087 - 37,087 11.7 37,087 18.4 Misc, Computers, Equip - - - - Return (actual) 14,934 -
Exhaust and Relief (actual) 3,446 -
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
Ventilation (requirement) 3,446 3,446
Mechanical Gains/Losses Mechanical Gains/Losses Ventilation (actual) 3,446 -
Ventilation (sensible) 33,770 - 33,770 10.7 - - Ventilation (sensible) - - - - Infiltration 559 -
Transfer Air † - - - - - - Transfer Air † - - - -
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - CHECKS
Fans 5,905 - 5,905 1.9 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - - Number of People 689.10
m²/Person 5.00
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
W/m² - Cooling 91.79
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
W/m² - Heating 0.00
Latent Cooling 81,901 - 81,901 25.9 - -
m²/kW - Cooling 10.89
Dehumid Oversizing † - - - - - - m²/kW - Heating -
Sub Total 121,576 0 121,576 0 Sub Total 0 0 0 l/s/m² - Cooling 4.33
l/s/m² - Heating 1.30
TOTAL 316,266 0 316,266 100 201,763 100 TOTAL 0 0 0 0 % Outside Air - Cooling 23.07
% Outside Air - Heating 76.90
COOLING COILS HEATING COILS Outdoor Air l/s/m² 1.00
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH Total Capacity Airflow Enter Leave
Outdoor Air l/s/person 5.00
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
Peak Latent Load (W) 94,466.27
System Cooling ‡ - - - - - - - - - - System Heating - - - - Sensible Heat Ratio 0.74
Ventilation - - - - - - - - - - Ventilation - - - -
Indirect Evap - - - - - - - - - - Pre-Heat - - - -
Direct Evap - - - - - - - - - -

TOTAL 0.0 0.0 0.0 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | System loads - Page 4 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration
Room Conditioning Loads Report HVAC Sizing IES VIRTUAL ENVIRONMENT
Zone: None Ground Floor
System: 03 c AHU GF VE 2019
ZONE COOLING COIL PEAK ROOM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 16:30 5 / 16:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 31.7 / 22.2 / 44.8 34.1 / 20.7 / 30.5 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Room RA Plenum Net Percent Room Percent Room RA Plenum Net Percent Roof 0.0 0.0 -
Value of Total (Sensible) of Total Value of Total External Floor 3,445.5 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 5,632 - 5,632 1.8 6,258 3.0 External Walls - - - - Partition/Door 0.0 - -
Roofs 0 - 0 0.0 0 0.0 Roofs - - - - Internal Ceiling 3,445.5 - -
Ground/Exposed Floors 27,918 - 27,918 9.1 40,321 19.5 Ground/Exposed Floors - - - - Internal Floor 0.0 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 7,758 - 7,758 2.5 9,387 4.5 Windows Conduction - - - - TEMPERATURES & SETPOINTS
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 12,924 - 12,924 4.2 12,031 5.8 Solar - - - -
Supply Air (design) 12.8 32.2
Infiltration 5,263 - 5,263 1.7 6,899 3.3 Infiltration - - - -
Supply Air (actual) 14.3 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Room Setpoint (design) 23.9 21.1
Internal Building Gains/Losses Internal Building Gains/Losses Room (actual) 24.3 -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Return Air (actual) 24.3 -
Internal Floors/Air/Furn. -37 - -37 0.0 -36 0.0 Internal Floors/Air/Furn. - - - - Plenum (actual) - -
Ceilings 2,326 - 2,326 0.8 3,362 1.6 Ceilings - - - - Mixed Air (actual) 26.0 -
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Temperature Rise (dT) - -
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - - RH (Design Max Setpoint) (%) 70.0 70.0
RH (actual) (%) 55.0 0.0
Non-Principal Spaces - - - - 0 0.0 Non-Principal Spaces - - - -
Sub Total 61,785 0 61,785 78,222 Sub Total 0 0 0 AIRFLOW
Cooling Heating
Internal Gains Internal Gains l/s l/s
Lights 40,796 - 40,796 13.3 40,796 19.7 Lights - - - - Supply (design) 15,504 4,651
People 50,489 - 50,489 16.5 50,489 24.4 People - - - - Supply (actual) 15,504 -
Misc, Computers, Equip 37,087 - 37,087 12.1 37,087 18.0 Misc, Computers, Equip - - - - Reheat Minimum (design) 4,651 4,651
Leakage at Design Flow 0 0
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
SA Plenum Leakage to Room - -
Mechanical Gains/Losses Mechanical Gains/Losses Return (actual) 15,504 -
Ventilation (sensible) 32,402 - 32,402 10.6 - - Ventilation (sensible) - - - - Exhaust (actual) - -
Transfer Air † - - - - - - Transfer Air † - - - - Ventilation (requirement) 3,446 3,446
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - Ventilation (actual) 3,446 -
Infiltration 559 -
Fans 6,130 - 6,130 2.0 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - -
CHECKS
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
Number of People 689.10
Latent Cooling 77,288 - 77,288 25.3 - -
m²/Person 5.00
Dehumid Oversizing † - - - - - - W/m² - Cooling 88.80
Sub Total 115,820 0 115,820 0 Sub Total 0 0 0 W/m² - Heating 0.00
m²/kW - Cooling 11.26
TOTAL 305,977 0 305,977 100 206,594 100 TOTAL 0 0 0 0 m²/kW - Heating -
l/s/m² - Cooling 4.50
COOLING COILS AND ROOM UNITS HEATING COILS AND ROOM UNITS l/s/m² - Heating 1.35
Total Capacity* Sensible Cap* Airflow* Enter DB / WB / RH Leave DB / WB / RH Total Capacity* Airflow* Enter Leave
% Outside Air - Cooling 22.22
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
% Outside Air - Heating 74.08
System Cooling ‡ 100.2 352.2 263.3 15,504 26.3 19.1 51.5 14.3 13.7 94.0 System Heating - - - - Outdoor Air l/s/m² 1.00
Ventilation - - - - - - - - - - Ventilation - - - - Outdoor Air l/s/person 5.00
Indirect Evap - - - - - - - - - - Pre-Heat - - - - Peak Latent Load (W) 89,232.12
Direct Evap - - - - - - - - - - Re-Heat - - - - Sensible Heat Ratio 0.75
FCU, FPB, Act Bm - - - - - - - - - - FCU, FPB, Act Bm - - - -
Room Units - - - - - - - - - - Room Units - - - -
* For system coils, this is the fraction attributed to this room * For system coils, this is the fraction attributed to this room
TOTAL 100.2 352.2 263.3 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | Room conditioning loads - Page 1 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration
Room Conditioning Loads Report HVAC Sizing IES VIRTUAL ENVIRONMENT
Zone: None First Floor
System: 03 c AHU FF VE 2019
ZONE COOLING COIL PEAK ROOM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 8:30 5 / 8:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 27.0 / 20.9 / 58.8 28.2 / 19.0 / 42.7 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Room RA Plenum Net Percent Room Percent Room RA Plenum Net Percent Roof 0.0 0.0 -
Value of Total (Sensible) of Total Value of Total External Floor 0.0 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 1,906 - 1,906 0.6 2,124 1.1 External Walls - - - - Partition/Door 0.0 - -
Roofs 0 - 0 0.0 0 0.0 Roofs - - - - Internal Ceiling 3,445.5 - -
Ground/Exposed Floors 0 - 0 0.0 0 0.0 Ground/Exposed Floors - - - - Internal Floor 3,445.5 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 2,881 - 2,881 1.0 3,372 1.8 Windows Conduction - - - - TEMPERATURES & SETPOINTS
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 13,240 - 13,240 4.4 12,789 6.9 Solar - - - -
Supply Air (design) 12.8 32.2
Infiltration 1,278 - 1,278 0.4 1,876 1.0 Infiltration - - - -
Supply Air (actual) 13.3 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Room Setpoint (design) 23.9 21.1
Internal Building Gains/Losses Internal Building Gains/Losses Room (actual) 24.7 -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Return Air (actual) 24.7 -
Internal Floors/Air/Furn. 27,080 - 27,080 9.1 32,749 17.6 Internal Floors/Air/Furn. - - - - Plenum (actual) - -
Ceilings 4,167 - 4,167 1.4 5,301 2.8 Ceilings - - - - Mixed Air (actual) 25.4 -
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Temperature Rise (dT) - -
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - - RH (Design Max Setpoint) (%) 70.0 70.0
RH (actual) (%) 54.9 0.0
Non-Principal Spaces - - - - 0 0.0 Non-Principal Spaces - - - -
Sub Total 50,551 0 50,551 58,211 Sub Total 0 0 0 AIRFLOW
Cooling Heating
Internal Gains Internal Gains l/s l/s
Lights 40,796 - 40,796 13.7 40,796 21.9 Lights - - - - Supply (design) 12,930 3,879
People 50,489 - 50,489 16.9 50,489 27.1 People - - - - Supply (actual) 12,930 -
Misc, Computers, Equip 37,087 - 37,087 12.4 37,087 19.9 Misc, Computers, Equip - - - - Reheat Minimum (design) 3,879 3,879
Leakage at Design Flow 0 0
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
SA Plenum Leakage to Room - -
Mechanical Gains/Losses Mechanical Gains/Losses Return (actual) 12,930 -
Ventilation (sensible) 10,927 - 10,927 3.7 - - Ventilation (sensible) - - - - Exhaust (actual) - -
Transfer Air † - - - - - - Transfer Air † - - - - Ventilation (requirement) 3,446 3,446
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - Ventilation (actual) 3,446 -
Infiltration 559 -
Fans 5,112 - 5,112 1.7 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - -
CHECKS
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
Number of People 689.10
Latent Cooling 103,655 - 103,655 34.7 - -
m²/Person 5.00
Dehumid Oversizing † - - - - - - W/m² - Cooling 86.67
Sub Total 119,694 0 119,694 0 Sub Total 0 0 0 W/m² - Heating 0.00
m²/kW - Cooling 11.54
TOTAL 298,618 0 298,618 100 186,584 100 TOTAL 0 0 0 0 m²/kW - Heating -
l/s/m² - Cooling 3.75
COOLING COILS AND ROOM UNITS HEATING COILS AND ROOM UNITS l/s/m² - Heating 1.13
Total Capacity* Sensible Cap* Airflow* Enter DB / WB / RH Leave DB / WB / RH Total Capacity* Airflow* Enter Leave
% Outside Air - Cooling 26.65
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
% Outside Air - Heating 88.83
System Cooling ‡ 97.8 344.0 224.6 12,930 25.7 19.2 55.6 13.3 12.8 94.8 System Heating - - - - Outdoor Air l/s/m² 1.00
Ventilation - - - - - - - - - - Ventilation - - - - Outdoor Air l/s/person 5.00
Indirect Evap - - - - - - - - - - Pre-Heat - - - - Peak Latent Load (W) 103,654.89
Direct Evap - - - - - - - - - - Re-Heat - - - - Sensible Heat Ratio 0.65
FCU, FPB, Act Bm - - - - - - - - - - FCU, FPB, Act Bm - - - -
Room Units - - - - - - - - - - Room Units - - - -
* For system coils, this is the fraction attributed to this room * For system coils, this is the fraction attributed to this room
TOTAL 97.8 344.0 224.6 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | Room conditioning loads - Page 2 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration
Room Conditioning Loads Report HVAC Sizing IES VIRTUAL ENVIRONMENT
Zone: None Second Floor
System: 03 c AHU SF VE 2019
ZONE COOLING COIL PEAK ROOM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 8:30 5 / 8:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 27.0 / 20.9 / 58.8 28.2 / 19.0 / 42.7 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Room RA Plenum Net Percent Room Percent Room RA Plenum Net Percent Roof 0.0 0.0 -
Value of Total (Sensible) of Total Value of Total External Floor 0.0 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 1,772 - 1,772 0.6 1,953 1.1 External Walls - - - - Partition/Door 0.0 - -
Roofs 0 - 0 0.0 0 0.0 Roofs - - - - Internal Ceiling 3,445.5 - -
Ground/Exposed Floors 0 - 0 0.0 0 0.0 Ground/Exposed Floors - - - - Internal Floor 3,445.5 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 2,912 - 2,912 1.0 3,450 1.9 Windows Conduction - - - - TEMPERATURES & SETPOINTS
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 13,240 - 13,240 4.5 12,789 7.1 Solar - - - -
Supply Air (design) 12.8 32.2
Infiltration 1,292 - 1,292 0.4 1,923 1.1 Infiltration - - - -
Supply Air (actual) 13.3 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Room Setpoint (design) 23.9 21.1
Internal Building Gains/Losses Internal Building Gains/Losses Room (actual) 24.6 -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Return Air (actual) 24.6 -
Internal Floors/Air/Furn. 22,199 - 22,199 7.6 25,847 14.3 Internal Floors/Air/Furn. - - - - Plenum (actual) - -
Ceilings 4,588 - 4,588 1.6 5,824 3.2 Ceilings - - - - Mixed Air (actual) 25.3 -
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Temperature Rise (dT) - -
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - - RH (Design Max Setpoint) (%) 70.0 70.0
RH (actual) (%) 55.1 0.0
Non-Principal Spaces - - - - 0 0.0 Non-Principal Spaces - - - -
Sub Total 46,003 0 46,003 51,785 Sub Total 0 0 0 AIRFLOW
Cooling Heating
Internal Gains Internal Gains l/s l/s
Lights 40,796 - 40,796 13.9 40,796 22.6 Lights - - - - Supply (design) 12,600 3,780
People 50,489 - 50,489 17.2 50,489 28.0 People - - - - Supply (actual) 12,600 -
Misc, Computers, Equip 37,087 - 37,087 12.7 37,087 20.6 Misc, Computers, Equip - - - - Reheat Minimum (design) 3,780 3,780
Leakage at Design Flow 0 0
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
SA Plenum Leakage to Room - -
Mechanical Gains/Losses Mechanical Gains/Losses Return (actual) 12,600 -
Ventilation (sensible) 10,693 - 10,693 3.6 - - Ventilation (sensible) - - - - Exhaust (actual) - -
Transfer Air † - - - - - - Transfer Air † - - - - Ventilation (requirement) 3,446 3,446
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - Ventilation (actual) 3,446 -
Infiltration 559 -
Fans 4,982 - 4,982 1.7 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - -
CHECKS
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
Number of People 689.10
Latent Cooling 103,080 - 103,080 35.2 - -
m²/Person 5.00
Dehumid Oversizing † - - - - - - W/m² - Cooling 85.08
Sub Total 118,755 0 118,755 0 Sub Total 0 0 0 W/m² - Heating 0.00
m²/kW - Cooling 11.75
TOTAL 293,130 0 293,130 100 180,158 100 TOTAL 0 0 0 0 m²/kW - Heating -
l/s/m² - Cooling 3.66
COOLING COILS AND ROOM UNITS HEATING COILS AND ROOM UNITS l/s/m² - Heating 1.10
Total Capacity* Sensible Cap* Airflow* Enter DB / WB / RH Leave DB / WB / RH Total Capacity* Airflow* Enter Leave
% Outside Air - Cooling 27.34
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
% Outside Air - Heating 91.15
System Cooling ‡ 96.0 337.6 218.9 12,600 25.7 19.2 55.8 13.3 12.8 94.9 System Heating - - - - Outdoor Air l/s/m² 1.00
Ventilation - - - - - - - - - - Ventilation - - - - Outdoor Air l/s/person 5.00
Indirect Evap - - - - - - - - - - Pre-Heat - - - - Peak Latent Load (W) 103,080.27
Direct Evap - - - - - - - - - - Re-Heat - - - - Sensible Heat Ratio 0.65
FCU, FPB, Act Bm - - - - - - - - - - FCU, FPB, Act Bm - - - -
Room Units - - - - - - - - - - Room Units - - - -
* For system coils, this is the fraction attributed to this room * For system coils, this is the fraction attributed to this room
TOTAL 96.0 337.6 218.9 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | Room conditioning loads - Page 3 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration
Room Conditioning Loads Report HVAC Sizing IES VIRTUAL ENVIRONMENT
Zone: None Third Floor
System: 03 c AHU TF VE 2019
ZONE COOLING COIL PEAK ROOM PEAK HEATING COIL PEAK AREAS
Time of Peak (Mo/Hr:Mn) 6 / 14:30 5 / 14:30 Time of Peak (Mo/Hr:Mn) -/- Gross Glass Glass
Outside Air (DB/WB/RH) 32.5 / 22.4 / 42.9 35.1 / 21.0 / 28.9 Outside Air (DB/WB/RH) -/-/- m² m² %
Wall 822.5 297.0 36.1
Room RA Plenum Net Percent Room Percent Room RA Plenum Net Percent Roof 3,445.5 0.0 0.0
Value of Total (Sensible) of Total Value of Total External Floor 0.0 - -
Envelope Gains/Losses W W W % W % Envelope Gains/Losses W W W % Door 0.0 - -
External Walls 4,970 - 4,970 1.6 5,634 2.8 External Walls - - - - Partition/Door 0.0 - -
Roofs 36,481 - 36,481 11.5 38,237 19.0 Roofs - - - - Internal Ceiling 0.0 - -
Ground/Exposed Floors 0 - 0 0.0 0 0.0 Ground/Exposed Floors - - - - Internal Floor 3,445.5 - -
External Doors 0 - 0 0.0 0 0.0 External Doors - - - -
Windows Conduction 9,540 - 9,540 3.0 11,506 5.7 Windows Conduction - - - - TEMPERATURES & SETPOINTS
Cooling Heating
Skylights Conduction 0 - 0 0.0 0 0.0 Skylights Conduction - - - -
°C °C
Solar 11,640 - 11,640 3.7 11,730 5.8 Solar - - - -
Supply Air (design) 12.8 32.2
Infiltration 5,487 - 5,487 1.7 7,221 3.6 Infiltration - - - -
Supply Air (actual) 13.7 -
Nat/Aux Vent 0 - 0 0.0 0 0.0 Nat/Aux Vent - - - - Room Setpoint (design) 23.9 21.1
Internal Building Gains/Losses Internal Building Gains/Losses Room (actual) 24.4 -
Internal Walls/Openings 0 - 0 0.0 0 0.0 Internal Walls/Openings - - - - Return Air (actual) 24.4 -
Internal Floors/Air/Furn. -1,801 - -1,801 -0.6 -937 -0.5 Internal Floors/Air/Furn. - - - - Plenum (actual) - -
Ceilings 0 - 0 0.0 0 0.0 Ceilings - - - - Mixed Air (actual) 26.2 -
Duct Conduction 0 - 0 0.0 0 0.0 Duct Conduction - - - - Fan Temperature Rise (dT) - -
Duct Leakage † 0 - - - 0 0.0 Duct Leakage † - - - - RH (Design Max Setpoint) (%) 70.0 70.0
RH (actual) (%) 53.1 0.0
Non-Principal Spaces - - - - 0 0.0 Non-Principal Spaces - - - -
Sub Total 66,318 0 66,318 73,391 Sub Total 0 0 0 AIRFLOW
Cooling Heating
Internal Gains Internal Gains l/s l/s
Lights 40,796 - 40,796 12.9 40,796 20.2 Lights - - - - Supply (design) 14,934 4,480
People 50,489 - 50,489 16.0 50,489 25.0 People - - - - Supply (actual) 14,934 -
Misc, Computers, Equip 37,087 - 37,087 11.7 37,087 18.4 Misc, Computers, Equip - - - - Reheat Minimum (design) 4,480 4,480
Leakage at Design Flow 0 0
Sub Total 128,373 0 128,373 128,373 Sub Total 0 0 0
SA Plenum Leakage to Room - -
Mechanical Gains/Losses Mechanical Gains/Losses Return (actual) 14,934 -
Ventilation (sensible) 33,770 - 33,770 10.7 - - Ventilation (sensible) - - - - Exhaust (actual) - -
Transfer Air † - - - - - - Transfer Air † - - - - Ventilation (requirement) 3,446 3,446
SA Duct Leakage † - - - - - - SA Duct Leakage † - - - - Ventilation (actual) 3,446 -
Infiltration 559 -
Fans 5,905 - 5,905 1.9 - - Fans - - - -
SA Duct (conduction) 0 - 0 0.0 - - SA Duct (conduction) - - - -
CHECKS
Supply Air Plenum - - - - - - Supply Air Plenum - - - -
Room Units, Coils, etc. 0 - 0 0.0 - - Room Units, Coils, etc. - - - -
Number of People 689.10
Latent Cooling 81,901 - 81,901 25.9 - -
m²/Person 5.00
Dehumid Oversizing † - - - - - - W/m² - Cooling 91.79
Sub Total 121,576 0 121,576 0 Sub Total 0 0 0 W/m² - Heating 0.00
m²/kW - Cooling 10.89
TOTAL 316,266 0 316,266 100 201,763 100 TOTAL 0 0 0 0 m²/kW - Heating -
l/s/m² - Cooling 4.33
COOLING COILS AND ROOM UNITS HEATING COILS AND ROOM UNITS l/s/m² - Heating 1.30
Total Capacity* Sensible Cap* Airflow* Enter DB / WB / RH Leave DB / WB / RH Total Capacity* Airflow* Enter Leave
% Outside Air - Cooling 23.07
ton kW kW l/s °C °C % °C °C % kW l/s °C °C
% Outside Air - Heating 76.90
System Cooling ‡ 103.5 364.1 269.8 14,934 26.5 18.9 49.9 13.7 13.1 93.7 System Heating - - - - Outdoor Air l/s/m² 1.00
Ventilation - - - - - - - - - - Ventilation - - - - Outdoor Air l/s/person 5.00
Indirect Evap - - - - - - - - - - Pre-Heat - - - - Peak Latent Load (W) 94,466.27
Direct Evap - - - - - - - - - - Re-Heat - - - - Sensible Heat Ratio 0.74
FCU, FPB, Act Bm - - - - - - - - - - FCU, FPB, Act Bm - - - -
Room Units - - - - - - - - - - Room Units - - - -
* For system coils, this is the fraction attributed to this room * For system coils, this is the fraction attributed to this room
TOTAL 103.5 364.1 269.8 TOTAL 0.0

Coil and room unit capacities include oversizing Load run | 2020/04/11 11:58 | Room conditioning loads - Page 4 of 4
† Not carried across to the Net Value column
‡ Blow-through fan configuration