1017 Series Controllers 1017 Series Controllers
Ordering Details
Description Part # Weight (LB)
The O’Brien 1017 series controllers are compact, full
1017 Controller in a FRP enclosure with window. 10170-002 20 featured, microprocessor based single and dual point
2-pole 30 A 277 V Solid-State Relay. Controls a single circuit with a 2-pole heat trace controllers. They provide control and
Solid-State Relay. (Approved for Class I, Div. 2 areas) monitoring of Tracepak and Stackpak tubing bundles
designed for freeze protection and temperature
1017 Controller with RS-485 communications in a FRP enclosure with window. 10170-016 20
maintenance. The controllers can be set to monitor
2-pole 30 A 277 V Solid-State Relay. Controls a single circuit with a 2-pole
Solid-State Relay. RS-485 communications interface. (Approved for Class I, Div. 2 areas)
and alarm high and low temperature, high and low
current, ground fault trip and voltage.
1017 Controller in an 8” x 10” stainless steel enclosure with window. 10170-004 25
2-pole 30 A 277 V Solid-State Relay. Controls a single circuit with a 2-pole The 1017 series controllers are supplied with a
Solid-State Relay. (Approved for Class I, Div. 2 areas) solid-state relay (SSR) for use in nonhazardous and
Class I Div. 2 / Zone 2 hazardous areas. An optional
1017 Controller with RS-485 communications in an 8” x 10” stainless steel 10170-018 25 RS-485 communications interface is available on all
enclosure with window. 2-pole 30 A 277 V Solid-State Relay. units.
Controls a single circuit with a 2-pole Solid-State Relay.
RS-485 communications interface. (Approved for Class I, Div. 2 areas)
Control
1017 Dual Controller in a FRP enclosure with window. 10171-005 45 The 1017 series controllers will accept one or two
Dual 2-pole 30A 277 V Solid-State Relays. Controls two independent circuits. 3-wire 100-ohm RTDs for each control point. Each
(Approved for Class I, Div. 2 areas) control point can provide soft start, line sensing,
ambient sensing, proportional ambient sensing, and
1017 Dual Controller with RS-485 communications in a FRP enclosure with window. 10171-020 45 power limiting functions.
Dual 2-pole 30A 277 V Solid-State Relays. Controls two independent circuits.
RS-485 communications interface. (Approved for Class I, Div. 2 areas) Monitoring
The system can be set to periodically perform auto
1017 Dual Controller in a stainless steel 10171-006 55
enclosure with window. Dual 2-pole 30A 277 V Solid-State Relays.
cycled maintenance checks even when heat is not
Controls two independent circuits. (Approved for Class I, Div. 2 areas) required.
1017 Dual Controller with RS-485 communications in a stainless steel 10171-019 55 Integrated Ground-Fault Protection National
enclosure with window. Dual 2-pole 30A 277 V Solid-State Relays. electric codes require ground-fault protection on all
Controls two independent circuits. RS-485 communications interface. heat tracing circuits. The 1017 series controllers
(Approved for Class I, Div. 2 areas) satisfy this requirement without the need to purchase
and install additional equipment.
Installation
The 1017 series controllers are factory installed in
standard NEMA 4X FRP enclosures with a full view
front panel. As an option, stainless steel enclosures
may be ordered. Wiring is made using common field
installed connectors.
© 2016, by AMETEK, Inc. All rights reserved • QLT-1017 • 22 JULY 2016
BELGIUM • BRAZIL • CHINA • RUSSIA • SINGAPORE • SOUTH KOREA • USA
[email protected] • www.obcorp.com
1017 Series Controllers
General Monitoring
Area of use Nonhazardous and Division 2 hazardous locations Temperature Low alarm range -76ºF to 1058ºF (-60ºC to 570ºC) or OFF
Approvals 8.93 16.55
13.93 High alarm range -76ºF to 1058ºF (-60ºC to 570ºC) or OFF
Hazardous locations Ground fault Alarm range 20 mA to 250 mA or OFF
Class I, Div. 2, Groups A, B, C, D Trip range 20 mA to 250 mA or OFF
Ex nA IIA, IIB, IIC Current Low alarm range 0.3 Amps to 100 Amps or OFF
T-code: T4 14.55 15.00 High alarm range 0.3 Amps to 100 Amps or OFF
C US
Power limit 3 W to 33 kW
Supply voltage 100 Vac to 277 Vac, +5/–10 %, 50/60 Hz Voltage Low alarm range 10 V to 330 V or OFF
Common supply for controller and heat-tracing circuit High alarm range 10 V to 330 V or OFF
Resistance Low resistance range 1% to 100% of deviation from nominal
Enclosure High resistance range 1% to 250% of deviation from nominal
Protection NEMA 4X Autocycle Diagnostic test interval adjustable from 1 to 240 minutes or 1 to 240 hours
Materials FRP or stainless steel
Ambient operating temperature range –40°F to 140°F (–40°C to 60°C) Temperature Sensor Inputs
Ambient storage temperature range –40°F to 185°F (–40°C to 85°C) Quantity Two inputs per control point
Relative humidity 0% to 90%, noncondensing
Types 100 W platinum RTD, 3-wire, a = 0.00385 ohms/ohm/ºC
Can be extended with a 3-conductor shielded cable of 20 W maximum per conductor
100 W Ni-Fe RTD, 2-wire
Control
Relay type Double-pole, solid-state, normally open Alarm Outputs
Voltage, maximum 277 Vac nominal, 50/60 Hz AC relay Isolated solid-state triac, SPST, 0.75 A maximum, 100 Vac to 277 Vac nominal
Current, maximum 30 A @ 104°F (40°C) derated to 15 A @ 140°F (60°C) Dry contact relay Pilot duty only, 48 Vac/dc, 500 mA maximum, 10 VA maximum resistive switching
Control algorithms Line sensing on/off, proportional, proportional ambient, power limiting, soft start Note: Outputs are configurable as “open on alarm” or “close on alarm”
Control range –76°F to 1058°F (–60°C to 570°C)
Programming and Setting
Method Programmable keypad
Typical Enclosure Dimensions & Connections
Units ºF or ºC
Digital display Actual temperature, control temperature, heater current, voltage, resistance, ground fault,
programming parameter values, alarm values
LEDs Current mode, heater on, alarm condition, receive/transmit data
Memory Nonvolatile, restored after power loss, checksum data checking
8.50
.65 6.25 0.41 6.0 0 Stored parameters (measured) Minimum and maximum process temperature, maximum ground-fault current, maximum
heater current, power accumulator, contactor cycle count, time in use
Alarm conditions Low/high temperature, low/high current, low/high voltage, low/high resistance
Ground-fault alarm, trip
RTD failure, loss of programmed values, or SSR failure
10.00 10.50 11.00
Other Multi-language support
Password protection
Connection Terminals
Power supply input Screw terminals, 22-8 AWG
Heating cable output Screw terminals, 22-8 AWG
Ground Two box lugs, 14-6 AWG
RTD/alarm/communications 28-12 AWG spring clamp terminals
Communications (Optional)
8.93 16.55
13.93
Protocol Modbus RTU or ASCII / HTCBus
Interface RS-485
14.55 15.00