Ademco Lynx - Installation and Setup Guide
Ademco Lynx - Installation and Setup Guide
Security Systems
ARMED READY
OFF 1 2 3
ESCAPE RECORD VOLUME PLAY
AWAY 4 5 6
ADD LIGHTS ON TEST BYPASS
STAY 7 8 9
DELETE LIGHTS OFF CODE CHIME
AUX 0 #
SELECT STATUS NO DELAY FUNCTION
KITCHEN
BEDROOM BEDROOM KITCHEN DINING BEDROOM
DINING TV ROOM
BEDROOM
LIVING ROOM
BEDROOM BEDROOM
LIVING KTCHN
GARAGE
ROOM . CLOSED
DOOR
TO
BEDROOM
BASEMENT
01000-002-V0
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be
sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally
sent over the phone lines, if connected to an alarm monitoring station).
–2–
Table of Contents
–3–
System Features
LYNXR and LYNXR-EN are not intended for UL985 Household Fire applications unless a 24-hour backup
battery (P/N LYNXRCHKIT-HC) is installed.
UL
Powerline Carrier Devices are not UL Listed for fire or burglary functions and are intended for home
automation.
The LYNXR-Series controls are self-contained, rechargeable wireless control/communicators that feature easy
installation and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of
each zone (LYNXR-EN if programmed). The following illustration highlights the main features of this system.
FEATURES
ZONES and DEVICES SYSTEM POWER
• Real-time Clock display and Fixed-Word display
• 1 hardwire zone • Primary Power: Ademco
• Message Center (for user recorded messages)
• Up to 24 wireless zones 1332/1332X10 Plug-in Transformer,
• Voice announcement of system and zone status 110VAC to 9VAC, 15VA output
(5800 Series Transmitters)
• Voice chime (1332CN in Canada)
• Up to 16 wireless button zones
• Alarm Clock • Backup battery: Six 1.2V
• Up to 8 Powerline Carrier Devices
• Reminder rechargeable nickel-metal hydride
• Supports wireless keypads
• X-10 Scheduling batteries.
• Latch Key Reports
• Automatic Stay Arming
• Remote Phone Control
• “Follow Me” Reminder and System Announcements
8 USER CODES
• Installer code
• Master code
• 5 Secondary codes
• Duress code
• 3 Panic functions
ARMED READY
OFF 1 2 3
ESCAPE RECORD VOLUME PLAY
AWAY 4 5 6
ADD LIGHTS ON TEST BYPASS
COMMUNICATION STAY 7 8 9
• Ademco Low Speed DELETE LIGHTS OFF CODE CHIME
• Sescoa/Radionics
AUX
SELECT STATUS
0
NO DELAY
#
FUNCTION
ALARM OUTPUT
• Ademco Express • Built-in sounder
• Ademco Contact ID • Piezo output
• Paging feature (30mA max.)
• Bell output
(120mA max.)
• Steady output for
burglary/panic
• Temporal pulse
output for fire alarms
• Long Range
Radio/Alarm audio
verification
–4–
Mounting the Control
Wall Mounting
The illustration below shows the front assembly separated from the back plate.
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the
!
front assembly board.
Certain features differ between the LYNXR/LYNXR24 and the LYNXR-EN models. Verify the specific model
being installed prior to programming the system.
K51 X
16
08
X
PART NUMBER
MXX
1
making wiring connections. LOCATION
Desktop Mounting
If desired, an optional mounting base (model LYNX-DM, purchased separately) allows the LYNXR-Series controls to be
used on a desktop.
panel.
AUX
SELECT
–5–
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of
Connections diagram on the inside back cover when making connections.
PHONE LINES
Use either the plug-in jacks or
the screw terminals.
K51 X
08
X
MXX
AC TRANSFORMER
Use the supplied
ADEMCO 1332X10
9VAC, 15VA Plug-in
Transformer (1332CN in
Canada).
01009-005-V0
EARTH GROUND
See Earth Ground paragraph.
SOUNDERS
The system includes a built-in sounder in the master keypad. If
LOCAL SOUNDER DISABLE JUMPER desired, an external bell or piezo sounder can be connected.
Remove the shorting jumper (shunt) to disable local Bell: Use a 6-14V bell with maximum current drain of 120mA.
sounder, leaving only the external sounder active. Piezo: Use a 6-14V piezo sounder with maximum current drain of
30mA.
UL NOTE: Do not remove the shorting jumper (the shunt) This control complies with NFPA requirements for temporal pulse
for UL installations. sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
Wiring Connections
1. Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth
grounds available at most installations:
Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically
connected and secured to which the ground lead.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or
equivalent, available at most electrical supply stores.
a. Connect terminal 1 to a good earth ground.
–6–
Wiring Connections
Wiring Connections
INCOMING
PHONE LINE
2. Make Phone Line Connections - For local or full line RING
seizure proceed to the appropriate steps below. TIP
BROWN
GREEN
GREY
RED
them to RJ31X terminals 4 (red) and 5 (green).
b. Connect the premises end of the cut RING and TIP
wires to RJ31X terminals 1 (grey) and 8 (brown)
8-POSITION
JACK
TIP RING TIP RING
respectively.
}
}
INCOMING TO
c. Wire the flying leads of a Direct Connect Cord to the PHONE LINE PREMISES
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly
supervised, and the system may not respond to an open circuit on the zone.
3. Make Hardwired Zone Connections - Zone 1 is an EOLR supervised zone that supports both open circuit and closed
circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a. Connect sensors/contacts to the hardwired zone terminals 6 (+) and 7 (–). Refer to the Summary of Connections
diagram.
b. Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in
series with the devices, following the last device.
c. Connect open circuit devices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop
at the last device.
4. Make External Sounder Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) or
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX).
a. Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by
removing the shorting jumper (shunt) on the terminal board. If disabled, however, no sounding
will occur upon AC loss, since the external sounder does not operate when AC power is lost.
5. Disable Local Sounder Option - If required the Master Keypad’s built-in piezo sounder can be disabled.
a. Remove the shorting jumper (shunt) on the terminal board.
6. Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using
these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the SUMMARY OF
CONNECTIONS diagram.
a. Connect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.
Note: If not using the supplied Ademco connection cable, you may need to reverse the black and yellow wire connections. Refer to the
✻80 Device Programming Menu Mode section for details on programming Powerline Carrier Devices.
–7–
Wiring Connections
8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
RJ11 POS
JACK
TIP RING TIP RING (+) ( ) ( ) (+) ( ) (+) DATA SYNC
OUT IN
HARD
CARRIER DEVICES
WIRED
TO INCOMING ZONE
HANDSET PHONE
POWERLINE
PHONE LINE
LINE
LOCAL SOUNDER
DISABLE SHUNT
REMOVE TO
DISABLE
TRIGGER
INCOMING SIGNAL
(NEG) 1332/
TELEPHONE 1332X10/
LINE 1332CN
PLUG-IN
EARTH PREMISES PIEZO TRANSFORMER
GROUND TELEPHONE 9VAC, 15VA
BELL
2k OHMS 6-14VDC AC
EOLR 30mA max.
6-14VDC AC
120mA max.
THE LYNX SERIES CONTROLS ARE (e.g. WAVE2EX) SYNC
EQUIPPED WITH AN INTEGRAL WEEKLY TESTING IS
RECHARGEABLE BATTERY PACK. REQUIRED TO ENSURE COM
LYNXR: P/N LYNXRCHKIT-SC PROPER OPERATION
LYNXR24: P/N LYNXRCHKIT-HC OF THIS SYSTEM DATA
LYNXR-EN: P/N LYNXRCHKIT-SC
OR NOTE
P/N LYNXRCHKIT-HC 1332X10
USE ONLY 1332/1332X10 OR 1332CN ONLY
REPLACE EVERY FOUR YEARS TRANSFORMERS PROVIDED CONNECTIONS
01009-009-V0
–8–
AC Power and Backup Battery
The system is powered by a 9VAC, 15VA Plug-in Transformer, ADEMCO 1332/1332X10 (1332CN in
Canada). Refer to the wiring table below for wire gauge and length.
Use only the provided ADEMCO Distance from Transformer Wire Gauge
1332/1332X10 or 1332CN Transformer to Control
Up to 75 feet #20
75 to 150 feet #18
150 to 300 feet #16
Wiring to the AC Transformer must not exceed 300 feet using 16-gauge wire. The voltage reading between
terminals 15 and 16 of the control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery. In the event of an AC power loss, the system is supported by a long life backup battery that
is supervised for connection and for low voltage conditions. If the battery is missing, or a low battery condition
is detected, a “low battery” message is displayed and a report is sent to the central station. In addition, the
system will beep once every 45 seconds to audibly indicate a low battery condition (press any key to stop the
beeping).
BATTERY WIRING
RECEPTACLE TERMINALS
01009-007-V0
–9–
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The LYNXR Series is equipped with an integral, replaceable, rechargeable battery pack composed of six (6)
rechargeable 1.2-volt nickel-metal hydride batteries. Select the appropriate battery pack, based on the
installation’s requirement, and install the battery pack.
back plate.
6. Install the battery retainer.
7. Connect the battery connector to the
K51 X
08
X
MXX
receptacle on the terminal block PC board.
8. After the wiring connection has been made,
snap the front assembly to the back plate. BATTERY
RECEPTACLE
9. Plug the transformer into a 24-hour, 110VAC
unswitched outlet. 01009-006-V0
Ensure the control panel assembly is snapped closed prior to applying AC power.
–10–
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16
wireless buttons.
Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal
range of 200 feet.
Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the
system using the ✻56 or ✻83 interactive mode, or input to the control via the downloader. 5800
Series transmitters (except the 5800RL and 5827, described separately) do not have DIP switches.
Each transmitter's zone number is programmed into the system in ✻56 mode. Some transmitters,
such as the 5816 and 5817, can support more than one "zone" (referred to as loops or inputs). On the
5816, for example, the wire connection terminal block is loop 1,the reed contact is loop 2. Each loop
must be assigned a different zone number.
The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring. Therefore, for
UL Household Burglary installations, the loop wiring may not exceed 3 feet.
UL
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP,
5819, 5819S(WHS & BRS), and 5850(GBD) transmitters are not intended for any UL installations.
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone
number to each individual button used on the transmitter. Each button on the transmitter also has
a pre-designated loop or input number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV, or 5827 Wireless Keypad with 1
the system, you must program a House ID Code (01–31) in field ✻24
2
4 3
5
7 6
8
to establish proper communication, and the keypad must be set to *
0
9
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-
premises (5804, 5804BD, 5804BDV, 5804E, 5804WATCH, and
5827), each transmitter is supervised by a check-in signal that is
sent to the receiver at 70–90 minute intervals. If at least one check-
in is not received from each supervised transmitter within a 12-
hour period, the "missing" transmitter number(s) and "FAULT" will 5816 5806/5807/5808 5890 / 5890PI
be displayed. The supervision for a particular transmitter in the 01009-010-V1
system that may also be carried off the premises (5801, 5802MN)
may be turned off by entering it as a "UR" (unsupervised RF) type,
as described in the ✻56 Enhanced Zone Programming Mode section.
5800 Series transmitters have built-in tamper protection and will
annunciate as a fault condition if covers are removed.
Transmitter Input Types
Each of the following transmitters has one or more unique factory-assigned input (loop) ID codes.
Each of the inputs requires a programming zone (e.g., a 5804's four inputs require four button zones).
Transmitters can be entered as one of the following types (see transmitter’s instructions for appropriate
input type):
Type Description
"RF" (Supervised RF) Sends periodic check-in signals, as well as fault, restore, and low battery signals. The
transmitter must remain within the receiver's range.
"UR" (Unsupervised RF) Sends all the signals that the "RF" type does, but the control does not supervise the
check-in signals. The transmitter may therefore be carried off-premises.
"BR" (Unsupervised Button RF) These only send fault signals. They do not send low battery signals until they are
activated. The transmitter may be carried off-premises.
–11–
Installing Wireless Zones
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years,
depending on the environment, usage, and the specific wireless device
being used. Factors such as humidity, high or low temperatures, as well
as large swings in temperature may all reduce the actual battery life in a
given installation. The wireless system can identify a true low battery
situation, thus allowing the dealer or user of the system time to arrange
a change of battery and maintain protection for that point within the 5801 5802MN
system.
• Button-type transmitters should be periodically tested for battery life. ON
OF
Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode.
If so, wait a few minutes and try again.
2. The keypad will display all zone numbers, which have a non-zero Zone Type (even if serial
numbers were not learned yet). Fault each transmitter in turn, causing each one to send a
signal. As the system receives a signal from each of the transmitters, the zone number of that
transmitter will disappear from the display. The transmitters may be checked upon
installation, or in an installed system.
3. When all transmitters have been checked, exit Sniffer mode. Enter Installer Code (4112) +
OFF.
Notes: (1) Sniffer mode does not automatically expire. You must manually exit (Installer Code + OFF) Sniffer mode to return to normal
operation.
(2) All BR-type units must physically be activated to clear the display, since they do not automatically send check-in signals.
(3) When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are
cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
(4) Any transmitter that is not “entered” will not turn off its zone number.
Go/No Go Test Mode
Note: Encrypted (high-security) devices must be activated while the system is in Go/No Go Test Mode. Refer to the transmitter’s
installation instructions for complete details.
The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location,
and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters
permanently.
This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced.
This will enable you to make sure that the RF signal from each transmitter is received with
sufficient signal amplitude when the system is in the normal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitters in their desired locations and the approximate length of wire
to be run to sensors is connected to the transmitter's screw terminals (if used), fault each
transmitter.
Conducting this test with your hand wrapped around the transmitter will cause inaccurate results.
Note: On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, pressing a button will take the
system out of the Go/No Go Test mode and cause the programmed action.
a. The keypad will beep three times indicating signal reception and will display the appropriate
zone number.
b. If the keypad does not beep, reorient or move the transmitter to another location. Usually a
few inches in either direction is all that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then
permanently mount each of the transmitters according to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: Installer Code (4112) + OFF.
–12–
Installing Wireless Zones
5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop
designations.
LOOP 3 LOOP 3 LOOP 4
LOOP 2 YOU MUST
LOOP 4 LOOP 4 LOOP 4 ENROLL
YOU MUST YOU MUST
ON
OFF
LOOP 2 YOU MUST THIS
ENROLL LOOP 2 ENROLL BUTTON
ENROLL
THIS LOOP LOOP THIS LOOP 1 THIS BUTTON 1 :15 LOOP 1
LOOP 1 :0
1 :13 0
BUTTON 1 1 LOOP 3
BUTTON
: 16
••
•
LOOP 1
•• •
•
••• ••••
••
LOOP 3
• ••
LOOP 2
LOOP 1
LOOP 2 (PRIMARY)
(REED)
LOOP 2
(REED) LOOP 2
LOOP 1 LOOP 1 LOOP 1 (AUX.
LOOP 1 LOOP 1 CENTER)
(TERMINALS) LOOP 1
(TERMINALS)
(TEMP
ALTERNATE SENSOR) LOOP 3 LOOP 1
POSITION (AUX.
FOR LOOP 2 RIGHT)
LOOP 2 LOOP 2 34
2
AR
ME
D
5
(REED) (REED) 67 RE
AD
8 Y
9* MIC
0
LOOP 3 #
MESS
AGE LOOP 1 LOOP 1
(TERMINALS) LOOP 1 1
2
3
(SOUND) (MOTION)
4
(INTERNAL 7
5
6
8
SHOCK * 9
(G
LOOP 1 SENSOR
0
#
ree
(R n)
ed
(Ye
)
LOOP 3 (TERMINALS)
llow)
(TERMINALS)
5819 5819S (WHS & BRS) 5827 5827BD 5828V 5849 5850 (GBD) 5890/5890PI
ENROLL AS "RF" ENROLL AS "RF" PROGRAM PROGRAM PROGRAM ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF"
HOUSE ID HOUSE ID HOUSE ID 01009-012-V3
Note: Loop 4 must be enrolled on the 5801, 5804, 5804BD, 5804BDV, 5804E and 5804WATCH transmitters, whether or not the loop is used.
UL The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(WHS
& BRS), and 5850(GBD) wireless transmitters are not intended for any UL installations.
–13–
Mechanics of Programming
General Programming Information
Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The
system can be programmed at any time, even at the installer's premises prior to the actual installation.
Simply apply power temporarily to the Control and then program the unit as desired. There are two
programming modes:
• Data field programming (used for setting various system options)
• Interactive menu mode programming (used for programming zone information, programming Powerline Carrier
Devices, and for entering transmitter serial numbers)
The system can also be programmed remotely, using an IBM Personal Computer, a modem, and Compass Downloader
for Windows. See the Remote Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear the
feedback announcements or system beeps in the Programming Mode, of the system’s built-in speaker. To adjust the volume, press
FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the system will reset the volume to the default value (mid level).
! Certain features differ between the LYNXR/LYNXR24 and the LYNXR-EN models. Verify the specific model being
installed prior to the system programming.
Entering Program Mode - Use one of the following methods to enter Programming Mode:
1. Press both the [✻] and [#] keys at the same time, within 50 seconds after power is applied to the Control or from
exiting Programming mode, OR
2. After power-up, enter the Installer Code (4112) + 800 (This method disabled if Program mode is exited using ✻98.)
to enter Expert Programming mode or Installer Code (4112) + 888 to enter Voice Prompt Programming
mode.
Notes: 1. If a different Installer Code has been programmed, use that code to enter the Programming mode. Once you have entered the
Program mode, data field ✻20 (the first data field in the system) will be displayed and both keypad LEDs will flash.
2. Entering Programming mode may take up to 18 seconds if the 5842 Wireless Dialer has been enabled. The system will display
“ - - “ until the Lynx enters Programming mode.
Programming a Data Field
1. Press [✻] + Field No. (for example, ✻21), followed by the required entry.
2. When you have completely programmed a data field, the keypad will “beep” three times and then automatically
display the next data field in sequence. To go to a different field, press [✻] plus the desired field number.
3. If the number of digits that will be entered in a data field is less than the maximum number of digits available (e.g.
phone number field), enter the desired data, then press [✻] to advance to the next data field.
4. If a nonexistent field has been entered, the keypad will display “EE”. Simply re-enter [✻] plus a valid field number.
To view a data field without making changes: Enter [#] + Field No. Data will be displayed for that field.
To delete an entry in a field: Enter [✻] + Field No. + [✻]. (Applies only to fields ✻40–✻44, ✻88 and ✻94).
Interactive Mode Programming (✻56, ✻80, ✻81, ✻83, ✻84, ✻85)
Press [✻] + interactive mode No. (for example, ✻56). The keypad will display the first of a series of prompts.
A detailed procedure (with displays of prompts) is provided in later sections of this manual.
Interactive Mode Used to Program
✻56 Enhanced Zone Programming Mode Zone characteristics, report codes, and serial numbers
✻80 Device Programming Menu Mode Powerline Carrier Devices
✻81 Zone List Menu Mode Zone Lists for powerline carrier activation
✻83 Enhanced Sequential Mode 5800 Series transmitter serial numbers
✻84 Assign Zone Voice Descriptors Voice descriptors for each zone
✻85 Record Custom Voice Descriptors Up to 5 custom voice descriptors for zones
Loading Factory Defaults
To load the factory defaults, enter the Programming mode, press ✻97, then press number 1, 2, 3, or 4 to select from
default tables 1-4 at the back of this manual, or press “0” if you are not selecting a default table.
! If a default table is loaded, any data that has already been programmed into the system will be changed according to
the default table selected!
✻96 resets all subscriber account numbers and CSID in preparation for an initial download.
Exiting Program Mode
✻98 inhibits re-entry into the Expert or Voice Prompt Programming modes using the Installer Code.
✻99 allows re-entry into the Expert Program mode using Installer Code (4112) + 800 or into the Voice Prompt
Programming mode using Installer Code (4112) + 888.
Note: After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset delay, press [#] + [0].
–14–
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.
Type 00 Zone type 00 is used to program a zone that is not used.
Zone Not Used
Type 01 Zone type 01 is usually assigned to sensors or contacts on primary entry and exit
Entry/Exit Burglary #1 doors.
Zone Characteristics:
• Entry delay #1 is programmable from 0-99 seconds (field ✻35).
• Exit delay is independently programmable from 0-99 seconds (field ✻34).
• Exit and entry delays when armed in AWAY or STAY mode.
• No entry delay when armed in STAY NO DELAY or AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
01000-017-V0
Type 02 Zone type 02 is usually assigned to sensors or contacts on which secondary entry and
Entry/Exit Burglary #2 exit doors that might be further from the keypad (typically used for a garage, loading
dock, or basement door).
Zone Characteristics:
• Entry delay #2 is programmable from 0-99 seconds (field ✻36).
• Exit delay is independently programmable from 0-99 seconds (field ✻34).
• Secondary entry delay, if armed in the AWAY or STAY mode.
• No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.
01000-017-V0
• Exit delay begins regardless of the arming mode selected.
Type 03 Zone type 03 is usually assigned to all sensors or contacts on exterior doors and
Perimeter windows. Zone Characteristics:
Burglary • Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO
DELAY mode.
01000-018-V0
Type 04 Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or
Interior, Follower hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach
the keypad. It provides an instant alarm if the entry/exit zone is not violated first,
and protects an area in the event an intruder has hidden on the premises before the
system is armed, or gains access to the premises through an unprotected area.
Zone Characteristics:
• Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or
5890 / 5890PI
02) or interior-with-delay (type 10) zone is faulted first.
01000-019-V1
• Instant alarm in all other situations.
• Active when armed in AWAY or AWAY NO DELAY mode.
• Bypassed automatically when armed in STAY or STAY NO DELAY mode.
Type 05 Zone type 05 is usually assigned to a zone that contains foil-protected doors or
Trouble by Day/ windows or covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also
be used on a sensor or contact in an area where immediate notification of an entry is
Alarm by Night
desired.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO
DELAY (night) mode.
• Provides a latched trouble sounding from the keypad and, if desired, a central
station report during the disarmed state (day).
–15–
Zone Response Type Definitions
Type 07
Zone type 07 is usually assigned to a zone containing an Emergency
24-hour button (audible emergency).
Audible Zone Characteristics:
Alarm • Sends a report to the central station, and provides alarm sounds
externally and at the keypad.
Type 08 Zone type 08 is usually assigned to a zone containing a button for use
24-hour in personal emergencies or to a zone containing monitoring devices
(i.e.: water or temperature sensors, etc.).
Auxiliary Alarm
Zone Characteristics:
• Sends a report to the central station and provides an alarm sound at
the keypad. (No bell output is provided and there is no keypad
timeout.)
Type 10 Zone type 10 is bypassed when the panel is armed in the STAY or STAY
Interior w/Delay NO DELAY mode.
Zone Characteristics:
• Entry delay #1 (with programmed entry time) when armed in the
AWAY mode.
• Entry delay begins whenever sensors in this zone are violated,
regardless of whether an entry/exit delay zone was tripped first.
• No entry delay when armed in the AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
Type 20 Zone type 20 is a special-purpose zone type used with 5800 Series
Arm–Stay wireless pushbutton units.
Zone Characteristics:
• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when
arming or disarming.
Type 21 Zone type 21 is a special-purpose zone type used with 5800 Series
Arm–Away wireless pushbutton units.
Zone Characteristics:
• System is armed in the AWAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when
arming or disarming.
Type 22 Zone type 22 is a special-purpose zone type used with 5800 series
Disarm wireless pushbutton.
Zone Characteristics:
• Disarms the system when the zone is activated.
Type 23 Zone type 23 can be used on a zone when a Powerline Carrier Device
No Alarm Response (e.g., X-10) action is desired, but with no accompanying alarm (e.g.,
front door light).
–16–
Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form
to record the data for this installation. Note that both keypad LEDs flash while in Programming mode.
Note: Entering a number other than the one specified will give unpredictable results.
Installer Code The Installer Code is used to enter the 4-digit Master Security Code. See
✻20 Enter 4 digits, 0-9 "Master Code" in the System Operation section for procedure.
Quick Arm Enable If enabled, security code is not required to arm the system. The user
✻21 0 = do not allow quick arm simply presses and holds down the AWAY or STAY key to arm.
1 = allow quick arm
Keypad Backlight Timeout This option allows the choice of either always backlighting the keypad or
✻22 0 = no timeout; always backlight keys turning the backlighting off after 10 seconds of keypad inactivity.
1 = turn backlighting off after inactivity
Forced Bypass All zones bypassed by this function will be displayed after the bypass is
✻23 0 = no forced bypass initiated.
1 = provide automatic bypass of all open (faulted)
Note: UL installations: must be 0 (no forced bypass)
zones
RF House ID Code The House ID identifies receivers and wireless keypads.
✻24 00 = disable all wireless keypad usage If a 5827 Wireless Keypad or 5804BD/5804BDV Transmitter is to be
used, a House ID Code MUST be entered, and the keypad should be set
01-31 = House ID to the same ID.
Powerline Carrier Device (X-10) House ID Powerline Carrier Devices require a House ID. This field identifies this
✻25 0=A 4=E 8=I # + 12 = M House ID to the Control. The Powerline Carrier Devices are
programmed in field ✻80.
1=B 5=F 9=J # + 13 = N
2=C 6=G # + 10 = K # + 14 = O
3=D 7=H # + 11 = L # + 15 = P
Chime by Zone This option allows the installer to define the specific zones intended to
✻26 0 = no (chimes on fault of any entry/exit or perimeter chime when faulted while the system is in Chime mode. If enabled, these
zones are defined in zone list 3 (see ✻81 Zone List Menu Mode).
zone when Chime mode is activated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime mode on)
Real Time Clock Display Refer to the User’s Manual for setting the clock time and date.
✻27 0 = do not display the time
1 = display the time
Daylight Savings Time Start/End Month Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
✻29 0, 0 = no daylight saving time used
1-12 = start month and end month
Daylight Savings Time Start/End Week Enter the appropriate start and end weekend of the month.
✻30 0 = disable 4 = fourth weekend
1 = first weekend of month 5 = last weekend
2 = second weekend 6 = next to last
3 = third weekend 7 = 3rd from last
Single Alarm Sounding Per Zone UL installations: must be 0 (no limit)
✻31 (per armed period) This field applies only to burglary zones (zone response types 1-5, 10),
and affects long range radio reporting but does not affect central station
0 = no limit on alarm sounding per zone
reporting.
1 = limit alarm sounding to once per arming period for
a given zone Note: This field applies only to the bell and does not affect keypad
LYNXR/LYNXR24 - Applies to Long Range Radio Output if “0” sounds.
is selected in field ✻91
LYNXR-EN - Applies to Long Range Radio Output if Long Range
Radio is connected to the Trigger Single (Neg.) terminal #8.
Fire Sounder Timeout This Control complies with NFPA requirements for temporal pulse
✻32 0 = yes, fire sounder timeout after time programmed in sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
field ✻33
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
1 = no fire sounder timeout; continue sounding until
manually turned off
Alarm Bell Timeout This field determines whether the external sounder will shut off after
✻33 0 = No timeout 2 = 8 min 4 = 16 min time allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
1 = 4 min 3 = 12 min
Exit Delay The system will wait the time entered before sounding an alarm if the
✻34 00-99 = exit delay time in seconds exit door is left open after the system has been armed.
UL installations: must be set for a maximum of 60 seconds
–17–
Data Field Descriptions
Entry Delay 01 The system will wait the time entered before sounding alarm upon entering
✻35 00-99 = entry delay time in seconds. if system is not disarmed. UL installations: must be set for a maximum of
45 seconds
Entry Delay 02 The system will wait the time entered before sounding alarm upon
✻36 00-99 = entry delay time in seconds. entering. UL installations: must be set for a maximum of 45 seconds
Audible Exit Warning/Quick Exit Exit Warning: Sound consists of slow continuous beeps until last 5 seconds,
✻37 when it changes to fast beeps. The warning sound will end at the
Exit Warning Quick Exit termination of exit delay.
0 = no exit warning 0 = no quick
Quick Exit: If enabled, user can restart the exit delay time after arming in
sound exit
STAY mode by entering the user code and pressing the STAY key, or by
1 = provide exit 1 = allow quick pressing the STAY key if Quick Arm is enabled. This avoids having the
warning sound exit user disarm then re-arm the system after allowing someone to enter or exit
when armed AWAY
Confirmation of Arming Ding Confirmation of arming is provided by a 1/2 second external sounder “ding”
✻38 0 = no ding that sounds when closing report is sent, or at the end of exit delay.
1 = confirmation ding after arming system If Option 2 is selected the external sounder “ding” occurs immediately after
2 = confirmation ding after arming from RF button or the system receives the RF transmission.
RF keypad only
Power Up In Previous State When the system powers up armed, an alarm will occur 1 minute after
✻39 0 = always power up in a disarmed state arming if a zone is faulted, and any bypassed zones will be unbypassed.
Note: If the previous state was armed AWAY or STAY, the system will not
1 = assume the system status prior to power-down respond to sensor changes for 1 minute, which allows time for sensors such
as PIRs to stabilize. UL installations: must be 1 (power up in previous
state)
If fewer than 24 digits entered, exit by pressing [✻]. To clear entries from
✻42 Secondary Phone No.
Enter up to 24 digits. field, press ✻42✻. See backup reporting note for field ✻41. If using the
paging feature, enter the pager phone number here.
! All four digits of the Subscriber Account number must be entered in Fields ✻43 and ✻44. If ten digit format is
selected in ✻48 (option 5), all ten digits of the Subscriber Account number must be entered.
–18–
Data Field Descriptions
Field 46: Enter up to 24 digits. Do not fill unused spaces. Enter 0-9, #+11 for ‘*’; #+12 for’#’; #+13 for a pause (2 seconds).
“Follow Me Reminder” Phone Number This option allows the user to schedule a time driven message. When
✻46 Enter up to 24 digits.
activated the system will dial the phone number programmed and deliver a
voice message (custom words 72, 73 and 74). This option is only supported
when the pager or follow me feature is enabled in field ✻49 (option 6-9 or
10-13).
If using the Follow Me Reminder feature, enter the phone number here. If
fewer than 24 digits are entered, exit by pressing [✻]. To clear entries from
the field press ✻46✻.
The telephone message can be terminated (acknowledged) by pressing any
key on the telephone keypad. Pressing any key on the local LYNXR keypad
will terminate (acknowledge) both the follow me and the local reminder
announcements.
Note: The follow me reminder announcement will be terminated if any
other event requires the system to dial out or if and audible alarm
has occurred.
Phone System Select This option is used to enter the correct type of phone dialing (pulse or tone),
✻47 Note: For LYNXR/LYNXR24 only options 0, 1, 2, and 3 and to select the correct WATS line option for the Central Station. For
LYNXR-EN this option is used to activate the speaker phone option.
are applicable. For LYNXR-EN all options apply.
Central Dialing Mode Note: If using pulse dialing, you must enter the numbers slowly in order to
Station Pulse Tone Pulse Tone allow the pulse dialer time to operate.
No WATS 0 = No 1 = No 4 = With 5 = With
Speaker Speaker Speaker Speaker
Phone Phone Phone Phone
WATS 2 = No 3 = No 6 = With 7 = With
Speaker Speaker Speaker Speaker
Phone Phone Phone Phone
Report Format for Primary/Secondary Enter ✻ as the 4th digit of ✻43 through ✻44, if 3+1 dialer reporting is to be
✻48 used. (For an explanation of these formats, see the System Communication
Primary Secondary section of this manual.)
See choices below See choices below Notes: (1) The maximum number of alarm and alarm restore reports
0 = 3+1; 4+1 ADEMCO Low Speed Standard during one armed period is determined by field ✻92.
1 = 3+1; 4+1 Radionics Standard (2) If Option 5 is selected a 10-digit account number must be
2 = 4+2 ADEMCO Low Speed Standard entered in Fields ✻43 or ✻44.
3 = 4+2 Radionics Standard (3) Option 5 or 7 (ADEMCO Contact ID® Reporting) must be
selected for AVM.
5 = ADEMCO Contact ID® Reporting with 10-digit
(4) Option 5 or 7 (ADEMCO Contact ID® Reporting) must be
subscriber account number
selected if installing the 5842 Wireless Dialer.
6 = 4+2 ADEMCO Express
7 = ADEMCO Contact ID® Reporting with 7-digit
subscriber account number
8 = 3+1; 4+1 ADEMCO Low Speed Expanded
9 = 3+1; 4+1 Radionics Expanded
Split/Dual Reporting This field is used to select a reporting option as follows:
✻49 Enter: 0 - 5 when reporting to telephone receivers.
To Primary To Secondary 6 - 9 when reporting to a pager is desired.
0 = All reports None, unless primary 10 - 13 when reporting to an auxiliary telephone receiver.
fails, then all
Pager Report Format
1 = Alarms, Restore, Cancel Others
Options 6-9 send reports to the primary phone number, in a format defined
2 = All except Open/Close, Test Open/Close, Test
in Field ✻48, and send reports to a pager, which has its phone number
3 = Alarms, Restore, Cancel All
entered as the secondary phone number in Field ✻42. The pager report is a
4 = All except Open/Close, Test All
7-digit code, with optional 16-digit prefix, in the following format:
5 = All reports All
AAAAAAAAAAAAAAAA-EEE–00NN where:
To Primary To Paging Number AAA = Optional 16 digits for PIN number, etc. See Field ✻88 for full
6 = All reports except Open/Close Alarms, Open/Close ‡, description of these characters.
Troubles EEE = 3-digit Event Code as follows:
7 = All reports Alarms, Troubles 911 = Alarm (NN = zone number)
8 = All reports Alarms, Open/Close ‡, 101 = Open, system disarmed (NN = user no.)
Troubles 102 = Close, system armed (NN = user no.)
Open/Close ‡
811 = Trouble (NN = zone no.)
9 = All reports except Open/Close
00 = Always displayed before 2-digit user/zone no.
NN = 2-digit user number or zone number, depending on the type of
To Primary To Follow Me System event (EEE) that occurred. NN=00 indicates AC loss, system low
Phone Number battery, or low battery in 5827.
10=All reports except Open/Close Alarms, Open/Close ‡, Follow Me System Report Format
Troubles Options 10-13 send reports to the primary phone number, in a format
11 = All reports Alarms, Troubles defined in Field ✻48, and sends voice message to the secondary phone
12=All reports Alarms, Open/Close ‡, number entered in Field ✻42.
Troubles The message is a repeatable system status announcement. If the manual
13=All reports except Open/Close Open/Close ‡ paging option has been programmed in Field ✻87, the message will repeat
“system, system…..”.
‡ Will report Users 0, 5-8, and, if using wireless button-type
The message can be terminated by pressing any key on the telephone
devices, will report the zone number of the arm or disarm
keypad.
button 26-33. All other zones and users are not reported.
–19–
Data Field Descriptions
15-Second Dialer Delay (Burglary) If enabled, provides communication delay to the central station and allows
✻50 0 = no dialer delay the subscriber time to avoid a false alarm transmission. Delay does not
apply to zone type 6, 7, 8, and 9 alarms, which are always sent as soon as
1 = provide 15-second delay of burglary alarm report they occur. UL installations: must be 0 (no delay)
when armed away
Periodic Test Report Test report code entered in field ✻64 is sent.
✻51 0 = no test report 2 = weekly
1 = once every 24 hrs 3 = once every 30 days
First test Report Offset This is the time to first report from programming or downloading.
✻52 0 = 24 hrs after exit program mode or download
1 = 6 hours after exit program mode or download
2 = 12 hrs after exit program mode or download
3 = 18 hrs after exit program mode or download
Sescoa/Radionics Select Select 0 for all other formats.
✻53 0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
Lack of Usage Notification If enabled, notifies the central station if an end user is not operating their
✻54 0 = Disabled 4 = 90 days security system by sending a System Inactivity report 654. The report will
be sent only to the Primary phone number and only if Contact ID® format
1 = 1 day 5 = 180 days was selected.
2 = 7 days 6 = 365 days Note: The report will follow the ✻49 = 0 rules, no matter which selection
3 = 27 days was made in ✻49.
Note: There will be no local annunciation indicating that
this report has been sent to the Central Station.
RF Jam Detection For Event Logging, Option 2 must be selected.
✻58 0 = no jam detection If the control detects an RF jam condition, a “FAULT” message appears for
1 = RF jam detection with event logging, but no zone 90. The Contact ID® code for RF Jam is 344.
central station report Note: This feature cannot be used in conjunction with the 5827 wireless
2 = RF jam detection with event logging and with keypad.
central station report (if trouble/restore report is
enabled in fields ✻60, ✻71)
SYSTEM STATUS AND RESTORE REPORT CODES PROGRAMMING (✻59 – ✻76, & ✻89)
Program Report Codes using the interactive ✻56 Enhanced Zone Programming Mode, or codes can be entered in data
fields ✻59-✻76, ✻89. The following is a set of guidelines when programming report codes. The actual report code digits
that you enter depend upon the particular installation, and should be in agreement with you and the central station
office receiving the signals.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter "#+10" for A
(reports a “0” on some receivers), "#+11" for B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F. Entering "0" in the
first box will disable a report. Entering "0" in the second box results in automatic advance to the next field.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, or A–F, as described above.
Entering "0" in the first box will disable a report. Entering "0" in the second box will eliminate the expanded message for
that report.
With ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different
digit for each zone until you have used up available digits. If the number of zones exceeds the number of available
digits, begin with digit 1 again. This is an "enabling" code only and is not the actual code sent to the central station
office. Entries in the second boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the first box for all
the system conditions you want to send to the central station. A "0" in the first box disables the report.
–20–
Data Field Descriptions
SYSTEM STATUS REPORT CODES (✻59–✻68)
Exit Error Report Code If the system is armed and an entry/exit or interior zone is still open
✻59 (See notes above) after the exit delay time has expired, an alarm will sound at the
keypad and external sounder. If the system is disarmed before the
end of the entry delay that immediately follows, the alarm sounding
will stop and no message will be sent to the central station. The
keypad will display “CA (CANCELED ALARM).”
If the system is not disarmed before the end of the entry delay
mentioned above, and an entry/exit or interior zone is still open, an
“exit alarm” message will be sent to the central station if an Exit
Error report code is selected in this field. The keypad will display
“EA (EXIT ALARM),” and the alarm sounding will continue until
the system is disarmed (or timeout occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or
interior zone within 2 minutes following the end of the exit delay,
and an “Exit Alarm” message will be sent to the central station.
If Contact ID® format has been programmed, the message will
contain the zone number and error code 374 (Trouble–Exit Error). If
4+2 format is used, the digit entered in this field will be sent
followed by the second digit of the programmed alarm code for that
zone. If 3+1 or 4+1 format is used, only the digit entered in this field
will be sent. This message will go to the primary phone no. Under
any of these conditions, no restore message will be sent.
If “0” is entered in this field, no special message will be sent, only
the regular alarm and alarm restore code for the zone.
Trouble Report Code This will be sent if a zone goes into trouble.
✻60 (See notes above)
Bypass Report Code This will be sent when a zone is manually bypassed.
✻61 (See notes above)
AC Loss Report Code Timing of this report is random with up to a 4-hour delay. If AC
✻62 (See notes above)
restores before the report goes out, there is no AC restore report.
Low Battery Report Code This will be sent when a low battery condition exists in the system’s
✻63 (See notes above)
standby battery.
Test Report Code This is sent periodically to test that the communicator and phone
✻64 (See notes above)
lines are operational (frequency of report is selected in field ✻51).
RF transmitter Low Batt. Report Code This is sent in the event that a wireless transmitter low battery
✻67 (See notes above) condition exists.
Cancel Report Code This is sent upon disarming of the system after an alarm condition
✻68 (See notes above)
was reported.
–21–
Data Field Descriptions
RESTORE REPORT CODES (✻70–✻76) Continued
RF Transmitter Low Batt. Restore Code Sent when a transmitter that previously sent in a “low battery” message
✻75 (See notes above)
has sent a message indicating it no longer has a low battery condition.
Test Restore Report Code Sent when the test mode is exited. A restore code entered here will cause
✻76 (See notes above)
a restore message to be sent when Test mode is exited.
AUX Function/1-Button Paging If “0” is entered, user can define a macro function for the AUX key. See
✻87 0 = Aux key performs defined function (macro) user manual for description of the use of this key.
If “1” is entered, you must also select an option in field ✻49. The options
1 = Aux key sends predefined message to pager or a
are 6-9 for the pager or 10-13 for the follow me system announcement.
voice message to Follow Me system phone The actual pager message is 999-9999. Note that the hyphen may not be
number displayed, depending on the pager service. The manual follow me system
announcement is a repeatable “System, System…..”.
Note: A macro cannot be run from the Test mode.
Pager Characters If entered, these digits will appear in front of the 7-digit pager message
✻88 Enter up to 16 digits that will appear in front of the 7- sent by the control (either upon a system event or upon pressing the AUX
key [if programmed for paging]), and during latch key report (if enabled
digit pager message. during scheduling). These digits can consist of a PIN number, account
Enter [#] + [11] for “*” number, pauses or special digits needed by the pager (these types of
Enter [#] + [12] for “#” characters are not displayed), or any other characters the user chooses
Enter [#] + [13] for 2-second pause that will be displayed (eg., using a character code to distinguish between
control panel messages and other pager messages).
NOTES: Verify that the pager supports [*] and [#]
characters before using them. Some pagers You do not need to fill all 16 digits. Press [✻] + next field number to exit
require an additional delay [pause] in order to the field. To clear the field, press ✻88✻.
receive the entire message.
See field ✻87 to select the AUX key Paging feature. See field ✻49, which
must have an option 6-9 selected to enable paging messages, for
description of the pager message.
Event Log 80% Full Report Code If an Event Logging selection is made in field ✻90, a message can be sent
✻89 (See notes above) to the central station receiver when the log is 80% full. If the log becomes
full, a new message will overwrite the oldest message in the log.
Note: All control and readout from the log, aside from the selection made
by the installer in field ✻90, is accomplished via the downloader.
Event Logging Options Example: To select “Alarm/Alarm Restore” and “Open/Close,” enter 9 (1 +
✻90 0 = No event logging 8); to select all events, enter #15.
Default “3” = alarm/alarm restore (1) plus trouble/trouble restore (2).
1 = log Alarm/Alarm Restore The system has the ability to record various events in a history log (84-
2 = log Trouble/Trouble Restore event capacity). The types of events to be logged can be selected as
4 = log Bypass/Bypass Restore indicated. At any time, the downloader operator can then upload the log
8 = log Open/Close and view or print out all or selected categories of the log. The log can also
x = log combination of events (add value of entries) be cleared by the download operator.
The display/printout at the central station will show the date, time, event,
and description of the occurrences.
Note: System messages are logged when any non-zero selection is made.
–22–
Data Field Descriptions
! The features programmed in Field ✻91 differ between LYNXR models. Ensure you use the correct option
for the model you are installing!
LYNXR/LYNXR24 For LYNXR/LYNXR24, this option is used to enable the Long Range
✻91 Radio, Alarm Audio Verification and/or Remote Phone Control options.
Long Range Radio/Alarm Audio If Long Range Radio (0) is selected, trigger output (terminal screw #8)
Verification (AAV) Trigger/Remote Phone will generate a steady signal for burglary alarm (a single 3 to 4-second
Control pulse for all types of silent alarms) or a temporal signal for fire alarm.
0 = long range radio trigger only (Refer to Long Range Radio Installation Instructions for appropriate
wiring.) Alarm Audio Verification requires the installation of the
1 = AAV and remote phone control
LYNX-AVM. (Refer to LYNX-AVM Installation Instructions)
2 = long range radio trigger and remote phone control Notes: (1) If Long Range Radio is being connected, Alarm Audio
4 = AAV only Verification cannot be used.
(2) In order to activate the remote phone control feature and
Notes: For UL installations Alarm Audio Verification defeat an answering machine, ensure that the correct ring
cannot be used. Alarm Audio Verification will only detection count (“15”) has been programmed in field ✻95.
function when Contact ID® is selected. (3) Remote phone session will be terminated if a report must
be sent.
(4) A Long Range Radio cannot be connected f AAV is selected.
(5) Alarm Audio Verification will only function when Contact
ID® is selected and cannot be used for UL installations.
(6) If an alarm will be reported to primary and secondary
phone numbers, AAV can only function via the secondary
number.
(7) If an alarm will be reported to a pager (6-8 in field ✻49), or
to follow me phone number (10-12 in field ✻49) AAV
cannot be used.
LYNXR-EN For LYNXR-EN, this option is used to enable the Audio Alarm
Verification and/or the Remote Phone Control features.
Alarm Audio Verification (AAV)/Remote Notes: (1) In order to activate the Remote Phone Control feature and
Phone Control defeat an answering machine, ensure that the correct ring
0 = none detection count (“15”) has been programmed in field ✻95.
1 = AAV and remote phone control (2) Remote phone session will be terminated if a report must
be sent.
2 = remote phone control only
(3) Alarm Audio Verification will only function when Contact
4 = AAV only ID® is selected. AAV cannot be used for UL installations.
Notes: (1) For UL installations alarm audio verification cannot (4) If an alarm will be reported to primary and secondary
be used. Alarm Audio Verification will only function phone numbers, AAV can only function via the secondary
when Contact ID® is selected. number.
(2) AAV and Remote Phone Control features can only (5) If an alarm will be reported to a pager (6-8 in field ✻49), or
be used if the central station or remote phone to follow me phone number (10-12 in field ✻49) AAV
supports DTMF commands. cannot be used.
(3) No programming is required if connecting an
ALARMNET 7845C device because the option is
always enabled.
Number of Reports In Armed Period This option can be used to limit the number of messages (alarm &
✻92 0 = reports limited to a total of 10 alarm restore reports) sent to the central station in an armed period.
UL installations: must be 1 (unlimited reports)
1 = unlimited number of reports
Flexible Callback If enabled, the control will ignore the last 1, 2, or 3 digits of the
✻93 0 = no flexible callback programmed callback number (field ✻94) during a single download
session. This allows the download operator to temporarily change the
1 = last digit flexible callback phone number by the number of digits selected, which allows
2 = last 2 digits flexible the control to call back similar, but different numbers during a single
3 = last 3 digits flexible session. For example, if downloading to a large number of controls, the
operator can command the controls to call back phone numbers 555-
1111, 555-1112, 555-1113, etc., thus spreading the communications
among several computers.
–23–
Data Field Descriptions
Other Programming Commands
–24–
✻55 Enabling the 5842 Wireless Dialer
This is an interactive menu mode that is used to enable and program the 5842 Wireless Dialer. When
enabled, the 5842 will interface with the Lynx Control and serve as the system’s primary dialer. The 5842
receives and acknowledges RF messages from the control’s transceiver and, in response, sends reports to the
central station via the dialer. It also sends acknowledgements, supervisory and tamper RF transmissions to
the control. If the wireless dialer has tried unsuccessfully to send a report, the Lynx will attempt to report to
the Central Station via the on-board dialer (if it has been programmed for back-up reporting). The Back-up
reporting option must be selected for Follow-me, Pager and AAV operation (refer to field *49).
LYNX must be connected to the telephone line, if using the Back-up reporting option.
Note: 1. It takes about 95 seconds for Lynx to transmit the setup information after power has been applied to the
control.
2. Entering Programming mode may take up to 18 seconds if the 5842 Wireless Dialer has been enabled. The
system will display “ - - “ until the Lynx enters Programming mode.
You must refer to these instructions or to the Programming Guide while programming the system because the keypad display
does not show prompt titles. Instead, prompts are indicated by a number/letter combination.
Ln Response to Phone Line Failure ......... for defining console sounder response (trouble/alarm) to a
phone line cut.
Eb Enable Back-up Reporting .................. for enabling the Lynx as a backup dialer.
*The Contact ID® Event Codes for the reports associated with the 5842 wireless dialer include the following:
145 Wireless Dialer Tamper (Alarm)
338 Wireless Dialer Low Battery
341 Wireless Dialer Tamper (Trouble)
342 Wireless Dialer AC Loss (if supported by the 5842 Wireless Dialer being installed)
351 Wireless Dialer Phone Line Cut (if supported by the 5842 Wireless Dialer being installed)
355 (Zone 93) Wireless Dialer Loss of RF Supervision
355 (Zone 000) Interruption of RF Link reported by the 5842 Wireless Dialer
For additional information refer to the Contact ID® Event Codes table.
–25–
✻55 Enabling the 5842 Wireless Dialer
While in Program mode, press ✻55 to enter Wireless Dialer Programming Feature.
The following explains the ✻55 prompts in detail. The left two columns identify the prompts and list the
available entries for each. The right-most column provides a further explanation of the entries.
Note: You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to clearly
hear feedback announcements or system beeps.
Enable the wireless dialer Enter [1] to enable the 5842 Wireless dialer. Press [✻] to advance to next
field.
Ed [✻] = continue
0 = disable Enter [0] to exit mode. The prompt “55” blinks, indicating the mode is
1 = enable inactive. Press [✻] + any field number to go to that field.
Enable trouble reports If selected, the following 5842 trouble reports will be enabled:
• Loss of RF link with 5842 Wireless Dialer
Er [✻] = continue
[#] = return to previous prompt
• Tamper at 5842
• Low Battery at 5842
0 = disable • AC loss at 5842 (if supported by the specific wireless dialer being
1 = enable installed)
• Line Cut at 5842 (if supported by the specific wireless dialer being
installed)
Enter [1] to enable 5842 Wireless Dialer trouble reports. Press [✻] to
advance to next field or [#} to return to the previous prompt.
Response to phone line tamper Select the Lynx response to detection of a line cut at the 5842 Wireless
Dialer.
Ln [✻] = continue
[#] = return to previous prompt
If the trouble sounder is enabled the system will sound a trouble event any
time the 5842 phone line is cut.
0 = enable trouble sounder If the alarm sounder is enabled the system will a trouble by day or an
1 = enable alarm sounder alarm at night in the event that the 5842 phone line is cut.
Enter [1] to select alarm or [0] to select trouble in the event of a 5842 line
cut. Press [✻] to advance to next field or [#} to return to the previous
prompt.
Enable back-up reporting Allows Lynx to do back-up reporting for the 5842 wireless dialer. Enter [1]
to enable back-up reporting. Refer to the 5842 Wireless Dialer Installation
Eb [✻] = continue
[#] = return to previous prompt
guide for additional information.
0 = disable Enter [0] to disable back-up reporting. Enter [#} to return to the previous
1 = enable prompt.
Note: Lynx must be connected to the premises phone line via the 5842
Wireless Dialer.
–26–
✻56 Enhanced Zone Programming Mode
This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes,
and to identify the type of loop input device. This mode can also be used for entering 5800 Series transmitter
serial numbers.
Note: There are two methods for entering transmitter serial numbers. The first method is by using ✻56 Enhanced Zone Programming mode
(described below). The second method is by using ✻83 Enhanced Sequential Mode. Note that the ✻83 Enhanced Sequential Mode
requires that all zone information first be entered using ✻56 Enhanced Zone Programming mode.
You must refer to these instructions or to the Program Form while programming the system because the
keypad display does not show prompt titles. Instead, prompts are indicated by a number/letter combination.
The prompts for ✻56 are as follows:
–27–
✻56 Enhanced Zone Programming Mode
While in Program mode, press ✻56 to enter Zone Programming Menu Mode.
Refer to the zone assignment table for ✻56 on the separate programming form.
The following explains the ✻56 prompts in detail. The left two columns identify the prompts and list the
available entries for each. The right-most column provides a further explanation of the entries.
Note: You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to clearly hear
feedback announcements or system beeps.
Zone number Enter the 2-digit zone number to be programmed and the Voice Descriptor
for the selected zone number will be announced, if it is programmed. Press
01-41, 95, 96, 99 = Zone number
A 0I [✻] = continue
[✻] to advance.
• Zone 01 = hardwire
00 = exit Zone Programming mode
• Zones 02-25 = RF zones (only)
• Zones 26-41 = Button zones (only)
• Zone 92 = Duress
• Zones 95, 96, 99 = Panic zones
Pressing 00 exits mode, upon which the prompt “56” blinks, indicating the
mode is inactive. Press [✻] + any field number to go to that field.
Zone type Each zone must be assigned to a zone type, which defines the way in
b
which the system responds to faults in that zone. Enter the 2-digit zone
00-24 = zone type
zt [✻] = continue
type for this zone as follows:
00 = Not Used 08 = 24 Hr Aux
[#] = return to previous prompt 01 = Entry/Exit #1 09 = Fire without verify
02 = Entry/Exit #2 10 = Interior w/Delay
Note: If 00 is accepted as a zone type, save the 00 03 = Perimeter 20 = Arm–Stay
zone type and advance to the confirm delete 04 = Interior Follower 21 = Arm–Away
prompt (F). 05 = Trouble Day/Alarm Night 22 = Disarm
06 = 24 Hr Silent 23 = No Alarm Response
07 = 24 Hr Audible 24 = Silent Burglary
Report code The report code consists of 2 hexadecimal digits, each in turn consisting of
2 numerical digits. For example, for a report code of "3C", enter [0][3] for
Enter the report code for this zone.
C rc [✻] = continue
"3" and [1][2] for "C".
If this is Zone 1, 95, 96 or 99, the system skips to the VOICE
[#] = return to previous prompt DESCRIPTOR prompt (1C).
Input type Enter the input type for the transmitter assigned to this zone. Refer to the
d
transmitter’s instructions for input types of each transmitter.
3 =RF (supervised RF) – sends periodic
i check-in signals, faults, restore and low
Note: Zones 2-25 should be assigned Input Type 3 or 4 . Zones 26-41
battery signals should be assigned Input Type 5 only.
Note: RF type transmitters must remain within
range of the receiver, otherwise a
supervision failure signal will occur.
4 = UR (unsupervised RF) – sends same as
“RF” type, but control does not supervise
the check-in signals
5 = BR (button type) – sends only fault and low
battery signals; does not send restores or
check-in signals
Note UR and BR type transmitters may be carried
off premises (out of range without causing a
supervision failure.
[✻] = continue
[#] = return to previous prompt
Loop number or Loop and Serial This prompt can be used to enroll loop number and serial number via RF
l
transmission or the loop number can be enrolled manually. If using the
E number (if using RF Learning)
1-4 = loop number for the zone of the
RF Learning Mode, there is no need to manually enter a loop number.
Proceed directly to RF Learning
transmitter being entered.
0 + [✻] = continue to DELETE ZONE Notes: (1) BR type devices cannot be enrolled by using UR or RF type.
PARAMETERS CONFIRMATION Likewise, UR or RF type devices cannot be enrolled by using a
prompt (F) BR type device. There is a 52-second time-out for RF
[✻] = continue to the ENROLL MODE prompt enrolling. At the end of the time-out, the system returns to
the INPUT TYPE prompt (d). If enrolled, loop number and “L”
(1A) if not entered, or VOICE
are displayed.
DESCRIPTOR prompt if already entered (2) Once encrypted (high-security) devices have been enrolled they
[#] = return to previous prompt must be activated. Refer to the device’s Installation
Instructions to activate the High-Security Mode.
–28–
✻56 Enhanced Zone Programming Mode
RF Learning - Two (2) transmissions (2 key depressions) at least 5
seconds apart will be required for BR type devices (device type 5). Two
beeps will sound after the second transmission, confirming that the loop
number and serial number have been learned.
For all other device types, four (4) transmissions are required (fault,
restore and fault, restore). A single beep will sound after the second
transmission confirming that the loop and serial number have been
captured. Following the fourth transmission the system will confirm that
the loop number and serial number have been learned and announce the
Voice Descriptor for the zone, if it is programmed, followed by two beeps.
Press [✻] to continue.
Manual Entry - Enter the desired loop number and press [✻] to
continue (see the transmitter’s Installation Instructions for specific loop
designations).
Note: The loop number can be changed even if the zone has already
been entered. Care should be taken when using this feature as it
has the capability to make zones inoperable by creating a
mismatch of a working serial number/loop number combination.
This should be re-confirmed if the loop number is changed.
“L” indicates that the zone’s serial number has already been enrolled.
Delete zone parameters This function deletes either the serial number or all zone information
that is programmed for the zone.
confirmation
F 0 = discard the delete request
If “00” was entered in the zone type, the confirmation of the delete
request will delete all information associated with the zone currently
1 = confirm requested delete being programmed.
Note: If 00 was entered as a zone type in prompt If “0” was entered in the loop number, the confirmation of the delete
(b), 00 will be retained and system will request will delete the serial number of to the zone currently being
advance to prompt (1C) programmed.
Enroll mode If “L” is displayed, the serial number for this transmitter has already
been entered. It may, however, still be viewed, confirmed (only if in
0 = advance to the VOICE DESCRIPTOR
IA LC prompt (1C).
listen mode), or deleted.
Note: This will save all zone parameters.
View serial number
1 = enter now and proceed to SERIAL Enter “3”. Each digit will be redisplayed, and the keypad will beep once
NUMBER prompt (1b). for digits 1-6, and three times for the last digit.
Note: Not applicable if the serial number is
already present. Confirm serial number
2 = copy the last serial number entered into The serial number/loop number combination can be confirmed after one
transmission from a BR type device or two transmissions (fault and
local ram.
restore) from a UR or RF type device. If a transmission is received that
Note: If this is the 1st zone, none will be in the matches the serial number and loop number entered, the system will
buffer and the panel will emit a long tone. confirm the reception by announcing the Voice Descriptor for the zone, if
Not valid if serial number is already present. it is programmed, followed by three beeps, and a “C” will appear on the
3 = view existing serial number. display indicating the received serial number and loop number have
Note: Only if “L” is displayed. If “L” is not been confirmed. No further transmissions will be received.
displayed, panel will emit a long beep.
Delete serial number
9 = advance to F; delete existing serial
The serial number can be deleted by entering “9”.
number.
Note: Only if “L” is displayed. If “L” is not If “L” is not displayed, the serial number for this transmitter has not
displayed, panel will emit a long beep. been previously entered. You may enter the serial number manually,
[✻] = advance to the VOICE DESCRIPTOR copy the previous serial number, return to Prompt (E) or enter the serial
prompt (1C). This will save all zone number later using the ✻83 Enhanced Sequential Mode.
parameters.
[#] = return to the LOOP NUMBER prompt
(E).
Note: In order for all entered parameters to be
accepted, you must advance to the VOICE
DESCRIPTOR prompt (1C).
–29–
✻56 Enhanced Zone Programming Mode
Manual entry
Enter "1" to advance to Serial number prompt (1b).
Copy the previous serial number
Enter “2” to copy the previous serial number entered.
Return to Prompt (E)
Enter “#” to return to Loop Number prompt (E).
Enter transmitter later
Enter “0” or “✻” if you wish to enter the transmitter later, using the ✻83
Enhanced Sequential Mode described later in this manual.
Notes: (1) The panel will listen only when it is in the idle loop waiting for
key entry and a serial number has been entered. If a key is
entered, the function must be completed and the panel will
listen again.
(2) A long beep indicates illegal entry or duplicate serial
number/loop entry
Serial number In this mode, the transmitter serial numbers can only be entered
manually.
Enter the transmitter’s 7-digit serial number.
Ib [#] = return to prompt 1A and reject any serial Enter the 7-digit serial number printed on the transmitter. If an incorrect
numbers entries that have been made. digit is entered, press the [#] key to backup to prompt (1A) and start over.
[✻] = return to prompt 1A, (if a valid serial When all 7 digits are entered, press the [✻] key.
number has been entered, the "L" is
displayed and the serial number will be If 52 seconds passes and no entry has been made, the system returns to
copied into EEROM from the last serial prompt (1A).
entered into the buffer.)
Notes: (1) If the serial and loop number combination is already present
Note: This prompt can be used only to manually the keypad will emit a single long beep and the system will
enroll a serial number. RF enrollment will be return to the (1A) prompt and “L” will be displayed.
rejected and the current zone descriptor will (2) If less than 7 digits have been entered, the keypad will emit a
be announced, followed by a single long single long beep and return to the (1A) prompt without
beep and the system will return to prompt displaying the “L”.
(1A). (3) If more than 7 digits have been entered, the first 6 digits will
be saved along with the last digit that was entered (entering
123456789 yields the serial number 1234569).
Voice descriptor Each zone can have a voice descriptor of up to 3 words that will be
announced whenever the system announces status for that zone.
0 = skip to next zone (A)
IC 1 = enter descriptor mode; existing descriptor
for this zone will be announced
Descriptor 1 † see ✻84 Assign Zone Voice Descriptors section for vocabulary index
Enter [#] + 2-digit vocabulary index number†
Id vi of first descriptor word for this zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press
6 = accept word and advance to descriptor 2 [#] + desired 2-digit vocabulary index number.
(descriptor 2 will be announced) If descriptor 1 is not desired, enter [#] + 99 (blank), then press [8] to return
8 = accept word and advance to next zone to zone number prompt.
(prompt A) – entire zone descriptor will be
announced
Press any other key to repeat the selected word.
Descriptor 2 † see ✻84 Assign Zone Voice Descriptors section for vocabulary index
Enter [#] + 2-digit vocabulary index number†
IE vi of second descriptor word for this zone. Use the [6] or [8] key to advance as described.
6 = accept word and advance to descriptor 3 To change the entered index number before pressing [6] or [8], simply press
(descriptor 3 will be announced) [#] + desired 2-digit vocabulary index number.
If descriptor 2 is not desired, enter [#] + 99 (blank), then press [8] to return
8 = accept word and advance to next zone
to zone number prompt.
(prompt A) – entire zone descriptor will be
announced
Press any other key to repeat the selected word.
Descriptor 3 † see ✻84 Assign Zone Voice Descriptors section for vocabulary index
Enter [#] + 2-digit vocabulary index number†
IF vi of third descriptor word for this zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press
6 or 8 = accept word and advance to next [#] + desired 2-digit vocabulary index number.
zone (prompt A) – entire zone If descriptor 3 is not desired, enter [#] + 99 (blank), then press [8] to return
descriptor will be announced to zone number prompt.
Press any other key to repeat the selected word.
–30–
✻80 Device Programming Menu Mode
Powerline Carrier devices (eg., X-10 brand devices) are programmable switches that can be used to perform
many different functions. They can be used to turn lights on and off, control sounders, or for status
indications. In this system, each device must be programmed as to how to act (ACTION), when to activate
(START), and when to deactivate (STOP). Each of these is described below.
The control supports a total of 8 output devices.
The 1332X10 transformer sends signals from the control panel through the premises AC wiring to the
Powerline Carrier Devices (which are plugged into AC outlets). Devices plugged into Powerline Carrier
Devices can then be made to perform various functions in response to commands entered at the keypads in
the security system.
UL Powerline Carrier Devices are not UL Listed for fire or burglary functions and are intended for home automation.
–31–
✻80 Device Programming Menu Mode
STOP The "STOP" programming determines when and under what conditions the device will be de-
activated. The following options are available:
Upon Restore of a Zone List
Restore Zone List: If a "ZONE LIST" is used as the “Stop” event, the device will de-activate when all the
zones in that list restore from a previous fault, trouble, or alarm condition. This will occur regardless of
what is programmed to "START" the device; therefore, a "RESTORE ZONE LIST" would normally only be
used when a "ZONE LIST" is used to start the device.
Upon a Zone Type or System Operation
Zone Type/System Operation: Instead of using a "RESTORE ZONE LIST," a specific zone (response) type or
system operation action can be selected to de-activate the device.
• If a specific "ZONE TYPE" is chosen, any zone of that response type that restores from a previous alarm,
trouble, or fault condition will cause the device to de-activate.
• If a "SYSTEM OPERATION" is chosen, that operation will cause the device to de-activate.
During normal system operation, any devices may be manually started by keypad entry of: Code* + [#]
+ 4 + “n;” or manually stopped by keypad entry of: Code* + [#] + 7 + “n,” where “n” = the device number to
be controlled.
* Code is required for devices 7 and 8. For devices 1-6, code is not required. See User Manual for more
information.
Programming Powerline Carrier Devices
While in program mode, press ✻80 to enter Output Device Menu Mode. This mode is used to program
all output devices used in the system. Refer to the output device table for ✻80 on the separate programming
form when programming output devices.
Note: The House ID of the Powerline Carrier Devices must be entered in data field ✻25.
The prompts for ✻80 are as follows:
b Device Action ----------------------- for defining the action the device will perform when active
C Start Event Type ------------------ for assigning the event type to start the action
d Start Zone List --------------------- for assigning the zone list to start the action
E Start Zone Type-------------------- for assigning the zone type to start the action
F Stop Zone List ---------------------- for assigning the zone list to stop the action
1A Stop Zone Type--------------------- for assigning the zone type to stop the action
–32–
✻80 Device Programming Menu Mode
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Note: Entering a number other than one specified will give unpredictable results.
Powerline Carrier Device Entering “1” advances to the next prompt below.
Entering “0” exits mode, upon which this prompt blinks, indicating the
80 programming
0 = exit mode
mode is inactive.
1 = enter mode
Device action Enter the 1-digit action (0-3) for the device being programmed (current
b aa 0 = No response
1 = Close for 2 seconds
action is displayed).
NOTES:
1. If “3” is entered (pulse), only up to 3 different devices can be pulsed
2 = Close and Stay Closed if one of the devices is a siren/horn (X-10 Powerhouse Security
3 = Continuous Pulse on & off (1 sec ON, 1 sec model SH10A). In addition, the siren/horn cannot be manually
OFF) activated using the lights on/lights off keypad commands.
[✻] = continue 2. If using an X-10 Powerhouse Security SH10A siren:
[#] = return to previous prompt • you must use device action “3.”
• you must change the device action default to “3” if using default
table 2 or 4
Start event type Enter the 1-digit event type (0-3) to activate the device being
programmed. A zone list must be used in conjunction with an event. If
C et 0 = Not used
1 = Alarm
3 = Trouble
[✻] = continue
a zone type/system operation is to be used instead of an event, enter
“0”.
2 = Fault [#] = return to previous
prompt
Start zone list If a zone list will be used to start the device action, enter the zone list
d zl
number at this prompt.
1-3 = zone list number (to be programmed in
field ✻81)
0 = zone list not used for this device
[✻] = continue
[#] = return to previous prompt
Start zone type If a zone type or system operation will be used to start the device
01-58 = zone type to start this device action
E zt (select only those that are applicable)
action, enter the appropriate 2-digit code for the device being
programmed (see table that follows).
00 = zone type not used for this device Choices for zone types
[✻] = continue 00 = Not Used 04 = Interior Follower 08 = 24 Hr Aux
[#] = return to previous prompt 01 = Entry/Exit #1 05 = Trouble Day/Alarm Night 09 = Fire
02 = Entry/Exit #2 06 = 24 Hr Silent 10 = Interior w/Delay
03 = Perimeter 07 = 24 Hr Audible 24 = Silent Burglary
Choices for system operation
20 = Arming–Stay 33 = Any Alarm (except zt 08) 42 = Sys. Batt. Low
21 = Arming–Away 36 = At Bell Timeout** 43 = Comm. Failure
22 = Disarm. (Code + OFF) 38 = Chime 52 = Kissoff
31 = End of Exit Time 39 = Any Fire Alarm 58 = Duress
32 = Start of Entry Time 40 = Bypassing
** Or at Disarming (which ever occurs earlier)
Note: If an X-10 device has been programmed to ZT05 or ZT07 and *55
has been enabled, the device response will be dependent upon the
selection made in *55 Field "Ln".
Stop zone list If a zone list will be used to STOP, or restore, the device action, enter
the zone list number 1, 2, or 3 (to be programmed in ✻81 mode). If not
F zl 1-3 = zone list to stop this device action
0 = zone list not used
used, enter “0”.
[✻] = continue
[#] = return to previous prompt
Stop zone type If a zone type or system operation will be used to STOP the device
action, enter the appropriate 2-digit code (see the "ZT" choices listed
IA zt 01-58 = zone type to start this device action
(select only those that are applicable)
above). If not, enter 00.
The display then returns to the DEVICE NUMBER prompt (A) so that
00 = zone type not used for this device you can enter the next device number to be programmed, or enter [0][0]
[✻] = continue to end device programming.
[#] = return to previous prompt
–33–
✻81 Zone List Menu Mode
While in Program mode, press ✻81 to enter Zone List Menu Mode. This mode is used to program zone
lists for output devices (programmed in ✻80 menu mode) or Chime-by-Zone in Zone List 3.
NOTES:
• Any list may include any or all of the systems zone numbers.
• A zone list can be assigned to more than one Powerline Carrier Device.
A 01 Zone List Number --------------------------- for entering the zone list number to be programmed
b Zone Entry to List --------------------------- for entering zones to the assigned zone list
C Delete Entire List? -------------------------- for deleting the entire zone list and its contents
d Delete Specific Zones From List? ------- Selects whether to delete zones or return to next zone list number
E Delete Zones----------------------------------- for deleting specific zones from the current zone list
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Notes: (1) Entering a number other than one specified will give unpredictable results.
(2) Do not assign zones with zone types 20, 21 or 22 to a zone list.
Zone list programming Pressing 1 advances to the next prompt below.
Pressing 0 exits mode, upon which this prompt blinks, indicating
0 = exit mode
8I 1 = enter mode
the mode is inactive.
Zone list number Enter the Zone List Number 01, 02, or 03 to program (or 00 if no
zone lists are used).
01-03 = zone list number to be programmed
A 0I 00 = exit Zone List mode
[✻] = continue
Zone entry to list Enter each zone number to add to the zone list by first entering
Delete entire zone list? To delete the zone list, enter “1”. All zones in the zone list will be
deleted automatically and programming will return to the ZONE
0 = don’t delete; continue to next prompt
C 1 = delete the current zone list
LIST NUMBER prompt.
To save the zone list or delete specific zones from the list, enter
“0”.
Delete zones from list? To save the entire zone list, enter “0” and programming will
Delete zones When deleting a zone(s) from the zone list, if the selected zone
has a Voice Descriptor programmed, upon deletion it will be
Enter each 2-digit zone number to be deleted
E from the current zone list, followed by the [✻]
announced as a confirmation that it has been deleted. After all
zones to be deleted are entered, enter “00” to return to the ZONE
key. LIST NUMBER prompt so that another list can be programmed,
[✻] = delete zone and enter next zone to be if desired.
deleted
00 = delete zone and return to next zone list
number prompt (A….01) desired
–34–
✻83 Enhanced Sequential Mode
By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain
all other existing data that has been programmed for that zone. Note that the ✻83 Enhanced Sequential
mode requires that all zone information must first be entered using the ✻56 Enhanced Zone Programming
mode for all zones below zone number 26 (4 button key area).
Note: Any zone which already has a serial number learned in will not be accessible in ✻83 Enhanced
Sequential mode!
Certain button-type transmitters have more than one button (e.g., 5804). Note that each button must be
assigned to a different zone. Similarly, the 5816 Transmitter has contact terminals and a reed switch for use
with a magnet. If using both, each must also be assigned to a different zone.
This means that the procedures that follow must be repeated for each button-type zone below zone number
26 or contact on the transmitter. Four zone button-type devices are held in zones 26 and above. They will be
started on boundaries of zones 26, 30, 34, and 38. These four zone button-type devices will have the option to
have all information entered in this field. One entry will set the loop number, report code, zone type, and
input device type for all 4 buttons, and a second entry will enter one serial number into four zones.
Note: Use this mode only after all other zone information has been programmed, including transmitter loop
numbers except for button-type zones over zone number 26. The panel will stop at zones 26, 30, 34
and 38 and zone data can be entered as a default here.
Enter Serial Number Sequential mode by pressing ✻83. The prompts for ✻83 are as follows:
A 01 Zone Number ------------------------------------ for entering the zone number to be programmed
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Notes: (1) Entry of a number other than one specified will give unpredictable results.
(2) In Enhanced Sequential Mode, 4 button type keys will always be enrolled simultaneously. They will be stopped at the 4 button
boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zone of the key has a serial number
enrolled, the remaining keys cannot be programmed in sequential mode. In addition, if the zone has not been set up (duplicate
loop, missing zone type, etc.) only entries 0 (skip to the next zone) and 4 (copy the key template) will be allowed.
(3) You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to clearly
hear feedback announcements or system beeps.
Zone number Enter the 2-digit zone number of the first transmitter to have its serial
number entered. The system will announce the Voice Descriptor for the
Enter the 2-digit zone number.
A 0I [✻] = continue; system searches for zones not
selected zone number, if it is programmed.
yet entered (for zones 2 through 25 a zone Press [✻] to continue. Starting with this zone number, the system will
type must be entered), then advances to search for the first transmitter that has all of the following attributes
ENROLL SERIAL NUMBER prompt “1b” pre-programmed in ✻56 ENHANCED ZONE PROGRAMMING:
a) Make sure that the appropriate input type was selected in ✻56 (RF,
00 = exit Sequential mode
UR, or BR programmed)
b) Make sure that the appropriate loop number was selected in ✻56.
c) No serial number programmed
d) Zone type
If the first zone number entered does not have one or more of the above
attributes, the system will search its database for the first zone that
does, and will display it at the enroll SERIAL NUMBER prompt (1b).
Pressing 00 exits mode, upon which the prompt “83” blinks, indicating
the mode is inactive.
Note: Two exceptions to the requirement above exist for keys. Four zone
button type devices (zone numbers 26, 30, 34, and 38) will be
stopped only if there are no serial numbers enrolled in all 4 zones
of the key, regardless of the attributes that have been entered. In
addition, zone types are not required to be present. In this case,
1A, Option 4 must be selected prior to “Learn”.
–35–
✻83 Enhanced Sequential Mode
Enroll mode Note: If “L” is displayed, the serial number for this transmitter has
zz 0 = advance to next zone to be enrolled already been entered, however, it may still be confirmed,
IA 1 = enter now and proceed to SERIAL NUMBER viewed or deleted.
prompt (1b). If the transmitter’s serial number has not been previously entered, you
For 4 button keys (zones 26-29, 30-33, 34-37, & may enter the enroll serial number mode (1A) by entering “1”, or copy
38-41) the serial number will be enrolled to all four the last serial number that was entered by entering “2”.
IA LC buttons.
If enrolling a key, the panel will emit a long beep If the transmitter’s serial number has been previously entered, you may,
view the present serial number by entering “3”. If view is selected each
when entering a 1 to indicate that the present key
digit will be re-displayed, and the keypad will beep once for digits 1-6,
set up is invalid. and three times for the last digit. Once the serial number has been
Notes: 1. A valid template or key has 4 existing entered by either selecting a “1” or a “2”, you will return to this prompt
zones, each with a zone type, unique loop with the “L” on the display. The serial number/loop number combination
number. that was entered can be confirmed by getting two transmissions (fault
2. If the display automatically advances to and restore) from the RF or UR device or one transmission from the BR
"1A" rather than "1b" the configuration of device. If a transmission is received that matches the serial number and
the key is not valid. At that point copy loop number entered, the system will announce the Voice Descriptor for
template, skip, or return are the only legal
the loop followed by three beeps, and a “C” will be displayed indicating
entries.
that the received serial number and loop number transmission has
2 = copy the previous serial number entry from been confirmed to match. No further transmissions will be received.
the buffer. When confirming a 4 button key, only the serial number is confirmed,
Notes: 1. Before you can copy a serial number you since it assumed that all loops are used. Pressing any key will allow a
must first enter a serial number. If no confirmation.
serial is stored in the buffer and a copy is *Long beep indicates illegal entries, or duplicate serial number/loop
attempted the panel will emit a long beep
entry*
indicating an invalid operation.
2. Not applicable for 4 button key zones 26- When the last zone has been entered, the display will remain on that
29, 30-33, 34-37, & 38-41. zone. To exit this mode and return to data field program mode, press 00
3 = view existing serial number. at the ZONE NUMBER prompt.
Note: Only if “L” is displayed. If the “L” is not
displayed the panel will emit a long beep. When all zones have been programmed, test each zone using the
system’s Test mode. Do not use the Transmitter ID Sniffer mode for this,
4 = copy the 4 button key template that has been
since it will only check for transmission of one zone on a particular
set in zone numbers 26-29 (all zone para- transmitter, and not the zones assigned to each additional loop.
meters except serial numbers). (Only valid on
zones 30-33, 34-37, & 38-41 that do not have For Zones 26-29, 30-33, 34-37, and 38-41 any loop can be used for RF
serial numbers enrolled.) enrollment. If enrolling via RF, it will be confirmed without additional
Notes: 1. Template acceptance is indicated by two transmissions.
beeps after copying.
2. A single long beep emitted when copying
a indicates the template is not valid.
9 = delete existing serial. Go to the (1A) prompt.
For 4-button key, zones 26-29, 30-33, 34-37,
& 38-41 have serial numbers. Delete all four
at one time.
Note: Only if “L” is displayed. If the “L” is not
displayed the panel will emit a long beep.
[✻] = advance to next zone to be enrolled
[#] = return to previous prompt (A)
–36–
✻83 Enhanced Sequential Mode
Serial number This prompt can be used to enroll the transmitter serial number via
RF transmission or manually. If using the RF Learning Mode there
Ib zz Enter transmitter’s 7- digit serial number via RF is no need to manually enter a serial number. Proceed directly to RF
learning or manually. Learning. Upon entering the Serial Number mode, the Zone
[#] = return to (1A) prompt and reject whatever Descriptors will be announced.
serial number entries have been made. Note: BR type devices can be enrolled only by transmission from BR
[✻] = return to (1A) prompt (if a valid serial devices. Likewise, UR and RF devices can only be enrolled by
Ib number has been enrolled, “L” is displayed transmission from a UR or RF device
and the serial number will be copied into RF Learning - Two (2) transmissions (2 key depressions) at least
EEROM and the last serial entered buffer. five seconds apart, will be required for BR type or four (4)
transmissions (fault, restore and fault, restore) for UR or RF type. If
Note: For zones 26, 30, 34 and 38 only BR type the learned serial number has a different loop number than that
entered in ✻56 the system will announce the Voice Descriptor, if it
devices can be used.
is programmed, followed by two beeps and will return to Prompt (1A)
and “L” will be displayed.
If the loop number captured by RF transmission and that entered in
✻56 mode match, the system will announce the Voice Descriptor, if it
is programmed, followed by three beeps and return to Prompt (1A)
and “LC” will be displayed. No additional transmissions are needed
for confirmation.
Manual Entry - Enter the 7-digit serial number printed on the
transmitter. If you enter an incorrect digit, press the [#] key to
backup to prompt (1A) and start over. When all 7 digits are entered,
press the [✻] key. If less than 7 digits are entered, the keypad will
emit a single long beep and return to the (1A) prompt without
displaying the “L”.
If more than 7 digits have been entered, the first 6 digits will be
saved along with the last digit that was entered (entering 123456789
yields the serial number 1234569).
Note: If 52 seconds pass and no entry has been made, the system
returns to prompt (1A).
Delete serial number This function deletes only the serial number.
0 = discard the delete request
F 1 = confirm requested delete
Entering a “9” at prompt (1A). Confirmation of the delete request will
cause deletion of the serial number pertaining to the zone being
Note: Entering a “9” at prompt (1A) will cause the programmed.
panel to return to prompt (1A) regardless of
the confirmation answer.
Note: In Enhanced Sequential Learn Mode, 4 button type keys will always be learned simultaneously. They will be stopped at the 4
button boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zone of the key has a serial
number learned, the remaining keys cannot be programmed in sequential learn mode. In addition, if the zone has not been set
up (duplicate loop, missing zone type, etc.) only entries 0 (skip to the next zone) and 4 (copy the key template) will be allowed.
–37–
✻84 Assign Zone Voice Descriptors
Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when
the system announces any event involving a zone number. Each descriptor can consist of up to 3 words.
Press ✻84 while in Programming mode.
The prompts for ✻84 are as follows:
84 Voice Descriptors ---------------------- Main Menu prompt
b Descriptor 1 ----------------------------- for assigning the first word of this zone’s descriptor
C Descriptor 2 ----------------------------- for assigning the second word of this zone’s descriptor
d Descriptor 3 ----------------------------- for assigning the third word of this zone’s descriptor
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Note: Entering a number other than the one specified will give unpredictable results.
Assign zone voice descriptors Pressing 1 advances to the next prompt below.
Pressing 0 exits mode, upon which this prompt blinks, indicating the
84 0 = exit mode
1 = enter mode
mode is inactive.
Zone number Enter the 2-digit zone number for which this descriptor is being
assigned, then press [✻]. The Voice Descriptor for the selected zone will
A zz [✻] = continue to next prompt (any existing
descriptors will be announced, then
be announced, if it is programmed.
Descriptor 1 Enter the first word of the descriptor for the selected zone.
Descriptor 2 Enter the second word of the descriptor for the selected zone.
Use the [6] or [8] key to advance as described.
C vv Enter [#] + 2-digit vocabulary index number of
second descriptor word for this zone.
To change the entered index number before pressing [6] or [8], simply
press [#] + desired 2-digit vocabulary index number.
6 = accept word and advance to descriptor 3 If descriptor 2 is not desired, enter [#] + 99 (blank), then press [8] to
(descriptor 3 will be announced) return to zone number prompt.
8 = accept word and advance to prompt (A) for
next zone. Press any other key to repeat the
selected word.
Descriptor 3 Enter the last word of the descriptor for the selected zone.
–38–
✻84 Assign Zone Voice Descriptor
VOICE VOCABULARY INDEX
00 ½ second pause G P Z SYSTEM WORDS
48 GARAGE 61 PATIO 81 ZERO AC LOSS
A 49 GUEST ROOM 62 POLICE 86 ZONES ARMED
82 ALARM 09 GUN 18 POOL AWAY
32 ATTIC 29 1ST BYPASSED
R 30 2ND CHIME
B H 63 REAR 31 3RD DISARMED
01 BABY 50 HALL 19 ROOM DISARM SYSTEM
33 BACK 70 Custom Word #1 NOW
I S 71 Custom Word #2
34 BASEMENT 10 INSIDE EXIT NOW
35 BATHROOM 64 SECOND FLOOR 72 Custom Word #3 FAULT
36 BEDROOM 65 SEVEN 73 Custom Word #4 INSTANT
K 20 SHED 74 Custom Word #5
51 KITCHEN LOW BATTERY
C 21 SHOP NOT
83 CHECK 66 SIDE 99 Blank (for erasing READY TO ARM
L 67 SILENT POLICE a previously
11 LAUNDRY STAY
D 68 SIX programmed
52 LAUNDRY 69 SLIDING word)
37 DELAY DOOR ROOM
38 DEN 22 SMOKE
12 LIBRARY 23 SOUTH
02 DETECTOR 13 LIVING
03 DINING 24 STORAGE
53 LIVING ROOM 85 SYSTEM
39 DINING ROOM
04 DOOR M
40 DOWNSTAIRS T
14 MAIN 25 THIRD FLOOR
05 DRIVEWAY 15 MASTER 75 THREE
54 MASTER 76 TRANSMITTER
E BEDROOM
06 EAST 77 TWO
55 MEDICAL
41 EIGHT 84 MESSAGE
42 EMERGENCY U
56 MOTION 78 UPSTAIRS
DETECTOR 26 UTILITY
F 79 UTILITY ROOM
43 FAMILY ROOM N
87 FIRE 57 NINE W
44 FIRE DETECTION 16 NORTH 27 WEST
07 FIRST FLOOR 58 NURSERY 80 WINDOW
45 FIVE
08 FLOOR O Y
46 FOUR 59 OFFICE 28 YARD
47 FRONT 60 ONE
17 OUTSIDE
Note: If button type device is used to Arm Away, Arm Stay, and disarm the system it is recommended to assign “Check” and
“Zones” voice descriptors to each of the three zones. This will allow the system to announce “Check Zones” “Low
Battery” if the button device has a low battery.
–39–
✻85 Record Custom Voice Descriptors
Use this mode to record up to 5 custom voice descriptors. Press ✻85 while in Programming mode.
Note: Entering a number other than one specified will give unpredictable results.
Assign custom voice descriptors Entering “1” advances to the next prompt below.
Entering “0” exits mode, upon which this prompt blinks, indicating the
0 = exit mode
85 1 = enter mode
mode is inactive.
A 7d Enter 7 + d + [✻]
–40–
Voice Prompt Programming
The LYNXR Series features a quick programming mode that allows you to program the system by
responding to a series of voice prompts. The Voice Prompt Programming Guide provides you with the
information required to use this feature.
AWAY 4 5 6
3. DELETE/ STAY key: Used to ADD LIGHTS ON TEST BYPASS
STAY 7 8 9 6
delete a sensor when in the delete DELETE LIGHTS OFF CODE CHIME
0 #
Sensors Menu.
3
AUX
SELECT *
STATUS NO DELAY FUNCTION
confirm a selection. 7
4
5. 3↑ key: Used to scroll forward 01009-021-V0
Notes: (1) Keying in any new command will terminate the active voice prompt.
(2) If an irrelevant command is entered LYNXR will generate a long rejection beep and repeat the previous voice prompt.
(3) Phone numbers and account numbers can be left blank by pressing the “ADD/ AWAY ” key without entering any data.
(4) LYNXR automatically saves phone and account number data once all available digits are entered.
–41–
Voice Prompt Programming
Enter Voice Prompt Programming Mode: (Installer Code + 8 8 8). Follow the voice prompts to
advance to the selected item in the Main Programming Menu.
Program each option as shown below. Use the 6↓ and 3↑ keys to scroll through the voice menu and follow the voice prompts to
program the LYNXR.
The LYNXR will enroll a sensor once the transmitter has been activated two times. The system will confirm the
! enrollment following each subsequent activation of the same transmitter.
–42–
Voice Prompt Programming
To Delete Sensors
Select
Select Sensor to
"Delete Sensors" be Deleted
Press Press
[SELECT] [DELETE]
Press
Press
[SELECT]
[ADD]
LYNXR automatically saves phone and account number data once all available digits are entered.
! All four digits of the Central Station Account number must be entered. If ten-digit format is selected, all ten digits
must be entered.
Press Press
[SELECT] [ADD]
–43–
Voice Prompt Programming
! All four digits of the Central Station Account number must be entered. If ten-digit format is selected, all ten digits
must be entered.
Press Press
[SELECT] [ADD]
Refer to the LYNXR Series Installation and Setup Guide to view the complete set of Template (default table) selections.
Press Press
[SELECT] [SELECT]
Template 1
Template 2
Template 3
Template 4
! Once you have entered the Expert Programming Mode, the [ESCAPE] key can be used to return to the Voice Prompt
Programming mode.
Select
"Expert
programming
System switches to Expert
mode"
Programming Mode
(Refer to the LYNXR
Series Installation and
Press
Setup Guide or the
[SELECT]
LYNXR Series
Programming Guide for
additional programming
instructions)
–44–
Remote Programming/Control
(Downloading)
General Information
The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), a HAYES
Modem, and ADEMCO’s Compass Downloader for Windows (as specified below).
UL Downloading may only be performed if a technician is at the site.
Multiple security levels protect remote programming against compromise by attempts to defeat the system.
1. Security Code Handshake: An 8-digit download ID code must be matched between the Control and
downloader.
2. Site-Initiated Remote Programming: The installer or subscriber initiates the call from the subscriber
premises (by entering Installer Code + # + 1) while disarmed. All parameters can then be downloaded via
the phone lines using a personal computer.
3. Station-Initiated Remote Programming: The operator calls the site from your office to initiate the
download call. The Control hangs up and then calls back the PC via the preprogrammed telephone
number. The unit can then be uploaded, downloaded, or controlled from your office.
4. Telco Handoff: The installer or subscriber performs a download session on the call initiated from the
site or from local laptop computer (by entering Installer or Master Code + # + 1 at the control panel).
5. Data Encryption: Data passed between the PC and the Control is encrypted for security so that it is
very difficult for a foreign device tapped into the phone line to take over communication and substitute
system-compromising information.
Equipment required to download to a system at the premises
• An IBM PC compatible computer and appropriate interconnecting cables.
• Either a HAYES brand SMARTMODEM 1200 (Level 1.2 or higher external or Level 1.1 or higher [with 4
position DIP switch] internal style), a HAYES brand Optima 336 external, a HAYES brand Optima 24
Plus FAX96, or an Ademco CIA Modem.
• Compass Downloader for Windows (at revision level supporting LYNXR, LYNXR24 or LYNXR-EN).
Initial Download: Enter Installer Code + # + 5. This sets field ✻95 to 4 rings, and system to “no call-back”
option. The download computer can then call the subscriber, make connection, and download all
programming data.
Flexible Callback: If enabled in field ✻93, the download operator can temporarily change the last 1, 2, or 3
digits (depending on selection) of the call back number. This allows the control to call back a computer other
than the one programmed, which may be helpful at times of high computer traffic. See field ✻93 for a full
description.
Remote Programming Information
LYNX must be connected to the telephone line if using Remote Programming.
The downloading system can perform many functions when in communication with the Control. Besides
uploading and downloading, the status of the system can be observed and various commands can be
initiated, as follows:
• Arm the system in the away mode; disarm the system.
• Bypass a zone.
• Force the system to accept a new program download.
• Shut down communication (dialer) functions (for nonpayment of monitoring fees in an owned system).
• Shut down all security system functions (for nonpayment for a leased system).
• Inhibit local keypad programming (prevents account takeover).
–45–
Remote Programming/Control (Downloading)
• Command the system to upload a copy of its resident program to the office.
• Set the time
• View/Modify
• X-10/ Scheduling
• Read: arming status, AC power status, lists of faulted zones, bypassed zones, zones currently in alarm,
zones currently in trouble, and RF sensors with low battery conditions; read control’s time.
Notes: (1) After the control and the PC have established valid communication, the keypad will become inactive and will display “CC.”
(2) The keypad will become active after the download communication is terminated.
(3) The detailed operation of the download functions is covered in the installation instructions for the Compass Downloader for
Windows.
–46–
System Operation
Security Codes
Installer Code
The installer programs the 4-digit Installer Code initially as part of the programming procedure. The
factory default Installer Code is 4-1-1-2, but may be changed in field ✻20.
The Installer Code is the only code that can enter Programming mode and also, in normal operation
mode, is used to enter the Master Code, which allows access to the normal functions of the system.
Master Code
In normal operation mode, the Installer Code is used to enter the 4-digit Master Security Code.
To enter/change the Master code by installer, using the keypad enter:
Installer Code + [CODE key] + [02] + desired 4-digit Master Code
To change the Master code by master, using the keypad enter:
Current Master Code + [CODE key] + [02] + new Master Code + new Master Code again
Panic Keys
There are three panic key pairs that, if programmed, can be used to manually initiate alarms and send a
report to the central station.
Each can be individually programmed for 24-hour silent, audible, personal or fire emergency responses. The
panic function is activated when both keys of the appropriate key pair are pressed at the same time.
The panic functions are identified by the system as follows:
Keys Displayed as Zone
Important: For the silent panic functions
[1] & [✻] 95 to be of practical value, the system must be
connected to a central station.
[✻] & [#] 99
[3] & [#] 96
–47–
System Operation
Keypad Functions
The keypad allows the user to arm and disarm the system, and perform other system functions, such as
bypassing zones. Zone and system conditions (alarm, trouble, bypass) are displayed in the display window.
When an alarm occurs, keypad sounding and external sounding will occur, and the zone(s) in alarm will be
displayed on the keypad. Pressing any key will silence the keypad sounder for 10 seconds (only once).
Disarming the system will silence both keypad and external sounders. When the system is disarmed, any
zones that were in an alarm condition during the armed period will be displayed (memory of alarm). To
clear this display, simply repeat the disarm sequence (enter the security code and press the OFF key). The
keypad also features chime annunciation, and 3 panic key pairs for silent, audible, fire or personal
emergency alarms. These keys can notify the central station of an alarm condition, if that service is
connected. A summary of system functions is provided below for more detailed information refer to the
User’s Manual.
Security Functions (Empty boxes represent the user’s security code)
Checking system status: STATUS (high level messages); press STATUS again for secondary messages
To arm in STAY mode: + STAY (or installer code + [3])
To restart exit delay: STAY (applies only if system is armed in Stay mode)
To arm in AWAY mode: + AWAY (or installer code + [2])
To arm with NO DELAY: + AWAY or STAY + NO DELAY
To arm if Quick Arm is programmed: AWAY or STAY (hold down for at least 2 seconds)
To disarm the system and silence alarms: + OFF
Message Center
NOTE
To record a message: FUNCTION + RECORD FUNCTION + RECORD
If a 5827 Wireless keypad has been installed, it cannot be used to
To stop recording before end of 20 seconds: OFF activate message playback/recording, programming the real time clock
or scheduling remotely. In this case, you must use the master keypad on
To play back a message: FUNCTION + PLAY the control panel to perform these functions.
To skip a message: [✻]
To delete all messages: FUNCTION + DELETE (during message replay)
Volume Control
To adjust message playback/system announcement volume: FUNCTION + VOLUME + [3] or [6]
To mute system announcements: FUNCTION + VOLUME + OFF
To use the defined AUX function: Press and hold AUX key 2 secs (4 beeps) +
To define AUX function: + FUNCTION + AUX + action separated by + AUX terminated by + AUX + AUX
To send message to pager: Press and hold AUX key 2 seconds (4 beeps)
To program Follow Me Announcement telephone number: + FUNCTION + [65]
–48–
System Operation
Speaker Phone Operation (LYNXR-EN Only) NOTE
To place a call or answer a call using the speaker phone: [#] + AUX The ARMED and READY LEDs blink alternately
when the Speaker Phone is active.
To flash (switch between two calls using call waiting): AUX
To return the keypad to telephone mode after disarming the system: [#] + AUX
Keypad Functions
Remote Phone Control Feature Quick Arm Note
To remotely disarm system: + [1] The installer code and
babysitter code cannot
To remotely arm in AWAY mode: + [2] disarm the system if
To remotely arm in STAY mode: + [3] armed by Quick Arm
method.
To remotely arm in AWAY or STAY with no delay: + [2] or [3] + [0]
To remotely activate X-10 devices 1-6: [#] + [4] + device no.
To remotely activate X-10 devices 7 & 8: + [#] + [4] + device no.
To remotely deactivate X-10 devices 1-6: [#] + [7] + device no.
To remotely deactivate X-10 devices 7 & 8: + [#] + [7] + device no.
To remotely Bypass zones: + [6] + zone no.
To remotely activate Forced Bypass: + [6] + [#]
To remotely check system status: [✻]
To end remote phone control session: Hang Up or + [9]
–49–
System Operation
UL Alarm audio verification cannot be used for UL installations.
Operator Commands
The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AVM
commands shown in the table below. The session may be extended 5 minutes, without changing the
operating mode, by pressing the [7] key on the touch-tone phone. Selecting another operating mode also
resets the session an additional 5 minutes. During the last minute of the 5 minute, session, the LYNXR-EN
generates two beeps every 30 seconds to alert the Central Station operator that the session is about to time
out. The Central Station operator may then extend the session by pressing the [7] key on the touch-tone
phone. If the session is not extended the phone line is disconnected, and the session is ended. Sessions may
be ended at any time by pressing the [9] key on the touch-tone phone. The AVM modes are described as
follows:
Note: When entering AVM commands make sure the Central Station receiver has been disconnected from the phone line, otherwise
AVM commands may not go through.
Key Function
1 Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication from the central station
to the violated premises, and allows the operator to talk communicate through the LYNXR-EN speaker. In this mode the
ARMED (red) and READY (green) LEDs blink alternately.
2 VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice communications between the central
station and the violated premises. In this mode the ARMED (red) and READY (green) LEDs blink alternately.
3 Listen Mode: Pressing the [3] key on the touch-tone phone, enables one-way audio from the violated premises to the central
station. The Listen Mode is the start up default mode of the voice feature and allows the operator to listen through the
LYNXR-EN microphone. This mode does not affect the existing LED pattern.
–50–
System Operation
“Follow Me” Reminder Feature
This feature allows the user to schedule a time driven message. When activated the system will dial a phone number, that the
installer programs in Field ✻46, and deliver a voice message (custom words 72, 73, and 74). The LYNXR will immediately
begin transmitting the voice message and will repeat the message for 45 seconds. Pressing any touch-tone key on the
answering phone will acknowledge the message ending the session and preventing the system from redialing the programmed
number. Delivery of a reminder message on the local LYNXR keypad will continue. If the message has timed out the system
will redial the programmed number a maximum of seven additional times or until it is acknowledged. Pressing any key on
the LYNXR keypad will terminate (acknowledge) both the follow me reminder and the local reminder announcements.
Notes: (1) This feature is only supported if programmed in field ✻49.
(2) The follow me reminder will be terminated if any other event requires the system to dial out, or if an audible alarm has
occurred, however, delivery of the local schedule reminder message will continue.
–51–
System Operation
Trouble Conditions
The word “FAULT” on the keypad’s display, accompanied by a rapid “beeping” at the keypad, indicates that
there is a trouble condition in the system. Pressing any key can silence the audible warning sound. Instruct
users to call for service immediately upon seeing any of the following messages.
• “Fault” and “Battery” Displays
• “FAULT” and one or more zone numbers indicates that a problem exists with the displayed zone(s)
and requires attention. After correcting the problem, the display can be cleared by entering the security
code plus the OFF key twice.
• The fault condition may also be caused by some change in the environment that prevents the built-in
receiver from receiving signals from a particular wireless sensor.
• “LOW BAT” with no zone number indicates that the system’s backup battery is weak.
• “LOW BAT” with a zone number and a once-per-45 seconds “beeping” at the keypad indicates that a
low battery condition exists in the wireless sensor displayed (zone “00” indicates a wireless button/keypad).
If the battery is not replaced within 30 days, a “FAULT” display may occur.
• “Fault Zone 93”, along with a flashing “AC” and a once per 45-seconds “beeping” at the keypad indicates
a loss of AC power to the 5842 Wireless Dialer (if this feature is supported by the Wireless Dialer being
installed).
• “Fault Zone 93”, along with a single beep indicates that setup information from the 5842 Wireless Dialer
has not been properly received.
Power Failure
• If there is no display at all, and both indicators are not lit, operating power for the system has
stopped and the system is inoperative.
• If the display is lit and the AC display is off, the system is operating on battery power only.
• During an AC power loss, the backlighting will turn off and the indicators will flicker slightly to
minimize deep discharge of the battery.
Other Displays
dI = Busy-Standby: Displayed upon power-up. After approximately 1 minute* the green “READY” LED
should light. If the “dI” remains displayed for more than 1 minute, the system is disabled.
*To bypass the 1-minute delay, press [#] + [0]. Important: Do not try to bypass 1 minute delay before “dI”
is displayed!
CC = Modem Comm: The system is communicating with the central station for change of function or
status verification.
FC = Comm. Failure: A communication failure has occurred. This message clears only when the system
is subsequently armed.
90 = RF Jam: The system has detected an RF jamming condition or excessive interference.
93 = Wireless Dialer: Tamper (alarm or trouble), phone line cut, loss of supervision, low battery, or AC
power loss*.
*If supported by the 5842 Wire Dialer that is installed.
PH = Speaker Phone Mode: The system is in Speaker Phone mode.
PC = Phone Control: The remote Phone Control feature is active.
“ -- ” Displayed when entering programming mode if a 5842 Wireless Dialer is enabled.
–52–
Testing the System
Test Mode
After installation is completed, the security system should be carefully tested, as follows.
1. With the system in the disarmed state, check that all zones are intact. If the READY LED is
not lit, press the [ ✻] key to display the faulted zone(s). Restore faulted zone(s) if necessary, so
that READY LED lights. Fault and restore every sensor individually to assure that it is being
monitored by the system.
2. Enter the security code and press the TEST key. The outside sounder will sound for 1 second
and all the LED segments on the keypad display light for 3 seconds. LYNX announces the
zone’s voice descriptor (if programmed) followed by 3 beeps, each time a contact is faulted. A
test report should be transmitted (if programmed) to the central station immediately. If the
backup battery is discharged or missing, the sounder may not turn on and a LOW BATTERY
report will be transmitted with a TEST report. The keypad will beep once every 45 seconds as a
reminder that the system is in the Test mode.
3. To turn off the Test mode enter security code and press the OFF key.
Notes: (1) Triggering a zone set to Arm AWAY, Arm STAY, or Disarm will take the system out of Test and
cause that action.
(2) BR type transmitters do not display during Test mode (keypad beeps only)
(3) Macros cannot be run from the Test mode.
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the
user are vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance
program to the user as well as acquainting the user with the proper operation and limitations of the
alarm system and its component parts. Recommendations must be included for a specific program of
frequent testing (at least weekly) to ensure the system’s proper operation at all times.
–53–
System Communication
This section provides an explanation of formats this system accommodates for reporting alarms and
other system conditions to the central station. The process of a successful transmission consists of
both the method of communication between the control panel and the central station receiver, and
the actual way the information is sent and displayed at the central station.
Communication Overview
When the panel calls the central station receiver, it waits to hear a “handshake” frequency from the
receiver to confirm that the receiver is on-line and ready to receive its message. Once the panel
hears the handshake it is programmed to listen for, it sends its message. The panel then waits for a
“kissoff” frequency from the receiver acknowledging that the message was received and understood.
3
If the handshake frequency is not given or is not understood by the panel, the panel will not send its
message. Once the handshake frequency is received and understood by the panel, the panel will
send its message. If there is an error in the transmission (the receiver does not receive a “valid”
message), the kissoff frequency will not be given by the central station receiver.
The panel will make eight attempts to the primary telephone number and eight attempts to the
secondary telephone number (if programmed) to get a valid message through. If the panel is not
successful after its numerous attempts, the keypad will display “FC.” If the secondary number is a
pager, “FC” displays after the first 8 attempts to the primary number.
The following chart defines the three sets of (handshake/kissoff) frequencies that the panel supports, and
the different formats that can be sent for each.
FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME
Low Speed 1400Hz 1900Hz (10PPS) 1400Hz Under 15 seconds
3+1 (Standard report)
4+1
4+2
Sescoa/Rad 2300Hz 1900Hz (20PPS) 2300Hz Under 10 seconds
3+1 (Standard report)
4+1
4+2
Express 1400–2300Hz DTMF (10 cps) 1400Hz Under 3 seconds
4+2
Contact ID® 1400–2300Hz DTMF (10 cps) 1400Hz Under 3 seconds
The following table shows the message formats for 3+1, 4+1 and 4+2 reports, where:
SSS or SSSS = Subscriber ID C = Close Code (1st Digit)
A = Alarm Code (1st digit) U = User Number (in hex)
Z = Typically Zone Number* (2nd digit) Gg = Test Code (1st & 2nd digits)
Tt = Trouble Code (1st & 2nd digits) R = Alarm Restore Code
Bb = Bypass Code (1st & 2nd digits) RTt = Trouble Restore Code (1st & 2nd digits)
E A C = AC Loss Code (1st & 2nd digits) R B b = Bypass Restore Code (1st & 2nd digits)
L L B = Low Battery Code (1st & 2nd digits) R A A C = AC Restore Code (1st & 2nd digits)
O = Open Code (1st Digit) R L L B = Battery Restore Code (1st & 2nd digits)
*Zone numbers for: [*] & [#], or [B] = 99; [1] + [*], or [A] = 95; [3] + [#], or [C] = 96; Duress = 92
–54–
System Communication
Report 3+1/4+1 Standard 3+1/4+1 Expanded 4+2
Alarm SSS(S) A SSS(S) A SSSS AZ
AAA(A) Z
Trouble SSS(S) T SSS(S) T SSSS Tt
TTT(T) t
Bypass SSS(S) B SSS(S) B SSSS Bb
BBB(B) b
AC Loss SSS(S) E SSS(S) E SSSS EAC
EEE(E) AC
Low Battery SSS(S) L SSS(S) L SSSS LLB
LLL(L) LB
Open SSS(S) O SSS(S) O SSSS OU
OOO(O) U
Close SSS(S) C SSS(S) C SSSS CU
CCC(R) U
Test SSS(S) G SSS(S) G SSSS Gg
GGG(G)g
Restore Alarm SSS(S) R SSS(S) R SSSS RZ
RRR(R) Z
AC Restore SSS(S) RA SSS(S) RA SSSSRA Ac
RARARA(RA)Ac
Low Battery Restore SSS(S) RL SSS(S) RL SSSS RLLB
RLRLRL(RL)LB
Trouble Restore SSS(S) RT SSS(S) RT SSSS RTt
RTRTRT (RT)t
Bypass Restore SSS(S) RB SSS(S) RB SSSS RBb
RBRBRB (RB)b
ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where:
CCCC = Customer (subscriber) ID
Q= Event qualifier, where: E = new event, and R = restore
EEE = Event code (3 hex digits) (for a complete list of event codes, refer to the central office receiver manual)
GG = Always “00”
ZZZ = Zone/Contact ID® number reporting the alarm, or user number for open/close reports. System
status messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.
–55–
Troubleshooting Guide
SYSTEM (including Wireless)
SYMPTOM POSSIBLE CAUSE REMEDY
1. Transmitter signal 1a. Transmitter not properly powered. 1a Check or change transmitter's battery.
not received at 1b. If Transmitter is 5827, House Code not 1b. Check code switches inside transmitter.
control. set in field ✻24, or transmitter is not set Must match with RF House Code
to same House Code set in that field. programmed.
1c. Transmitter is located too far from RF
receiver. 1c. Move transmitter or RF receiver.
1d. There is metal shielding between 1d. Check for large metal obstructions, then
transmitter and RF receiver. relocate transmitter if necessary.
1e. Transmitter is malfunctioning. 1e. Verify by activating control with
another, similar transmitter. If O.K.
1f. Transmitter No. (zone) is not now, return defective transmitter.
programmed. 1f. Verify programming.
2. Transmitter zone 2a. Transmitter zone type (ZT) is set to 00 2a. Set ZT to a valid active zone type in
number appears (Not Used). field ✻56.
during Transmitter 2b. Transmitter battery not installed.
Sniffer mode, but 2b. Install proper battery.
2c. 5800 System transmitter not "entered" in
does not clear.
system. 2c. "Enter" unit in field ✻56 or ✻83.
4c. A supervision fault has occurred. 4c. Check the transmitter indicated.
Restore communication to the receiver
to cancel the condition.
4d. System low battery
4d. Replace system battery
5. With 5800 System, Put control in Test mode. If zone does not
there is no response respond, try operating the tamper switch or
to a transmitter in another input to the transmitter.
normal operation, 5a. If another input causes the zone to be 5a. Delete input's serial number (not the
although zone displayed, the wrong input was "entered" zone), and enter the proper input (see
number clears during when programming. field ✻56).
Transmitter Sniffer 5b. If no response at all from this
mode. transmitter, this physical transmitter 5b. Determine which transmitter is
has not been entered by the system. programmed for this zone and
Transmitter Sniffer display is being reprogram as necessary.
cleared by another unit programmed for
this zone.
6. Nuisance or phantom 6a. Sensors not properly installed, wired, or 6a. Check installation to see if in
alarm. monitored. accordance with established procedure.
6b. Universal transmitter (5817) 6b. Check programming switches on
programmed wrong. transmitter.
7. Intrusion alarm for 7a. Protected door or window opened while 7a. Check with all occupants of protected
no apparent reason. system armed. home.
7b. Improper user operation of exit/entry
delays. 7b. Check setting of entry and exit delays.
7c. Magnets located too far from switches, 7c. Check all openings for proper switch
and/or doors and windows not properly and magnet orientation.
aligned.
–56–
Troubleshooting Guide
CONTROL
SYMPTOM POSSIBLE CAUSE REMEDY
1. The word “AC” is not 1a. Interrupted AC power supply. 1a. Check transformer connection and
displayed. powerline circuit breaker.
2. Digital communicator 2a. System in Test mode. 2a. Remove from Test mode.
message not being 2b. Telephone connection not secure. 2b. Check all connections.
received. 2c. Digital communicator 2c. Check with a different CONTROL
malfunctioning. PANEL.
2d. Program prefix or access code into the
2d. Telephone number in program needs CONTROL PANEL.
prefix or access code. 2e. System cannot work in this situation.
2e. Telephone call to central monitoring
station requires operator assistance.
3. Does not arm properly.
READY light not on. Open or faulted zone(s) Check for faulted zones and make intact,
or use Bypass arming, if desired.
4. System doesn't respond to
keystrokes on keypad.
4a. "CC" displayed. 4a. System is in communication with 4a. Wait until download session is
downloader at central station. finished.
4b. "d1" displayed. 4b. System has just been powered and is
in its one minute initialization. 4b. Wait for initialization to finish, or
bypass this time by pressing '#' + '0.'
SMOKE DETECTOR
SYMPTOM POSSIBLE CAUSE REMEDY
1. Detector alarms, no 1a. Dust, dirt in sensing chamber. 1a. Clean unit's sensing
apparent reason. chamber with vacuum
1b. Improper location. cleaner per unit's
instructions.
1c. Unit malfunctioning. 1b. See unit's instructions
for locations to avoid.
Relocate as necessary.
1c. Replace detector.
2. Detector's siren sounds. 2a. Unit not receiving required power. 2a. Check for proper
installation of battery.
2b. Unit malfunctioning. Try new battery.
2b. Replace detector.
–57–
Contacting Technical Support
PLEASE, before you call Technical Support, be sure you:
• READ THE INSTRUCTIONS!
• Check all wiring connections.
• Determine that the power supply and/or backup battery are supplying proper voltages.
• Verify your programming information where applicable.
• Note the proper model number of this product, and the version level (if known) along with
any documentation that came with the product.
• Note your ADEMCO customer number and/or company name.
Having this information handy will make it easier for us to serve you quickly and effectively.
You may contact Technical Support via Toll Free Fax. Please include your return fax number. You will
receive a reply within 24 hours.
–58–
Regulatory Agency Statements
UL NOTICE: This is a "Grade A" residential system.
FCC ID: CFS8DLLYNXREN-2
CANADA: 1748A-LYNXREN2
FCC STATEMENT
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1)
THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE
RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets
telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment
Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer
should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations
made by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to
disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal
metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection
authority, or electrician, as appropriate.
–59–
Specifications
LYNXR-Series 1. Physical: 10-3/8” W x 7-1/8” H x 1-3/4” D
Security
Controls 2. Electrical:
VOLTAGE INPUT: 9VAC from plug-in 15VA transformer.
RECHARGEABLE BACKUP BATTERY: Six 1.2-volt/cell nickel-metal hydride
rated at 1100 mA.
ALARM SOUNDER: Piezo = 6-14VDC, 30mA max/ Bell = 6-14VDC, 120mA max
(e.g., ADEMCO’s WAVE2EX).
LONG RANGE RADIO: Rated 12mA@12-volt nominal (negative trigger signal).
3. Communication:
FORMATS SUPPORTED:
ADEMCO Express, 10 characters/sec, DTMF (TouchTone) Data Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
ADEMCO Contact ID® Reporting, 10 characters/sec., DTMF (TouchTone)
Data Tones, 1400/2300Hz ACK, 1400Hz KISSOFF.
ADEMCO Low Speed, 10 pulses/sec, 1900Hz Data Tone,
1400Hz ACK/KISSOFF.
Radionics/SESCOA, 20 pulses/sec, 1800Hz Data Tone, 2300Hz
ACK/KISSOFF. Can report 0–9, B–F.
Line Seize: Double Pole
Ringer Equivalence: 0.6B
FCC Registration No.: 5GBUSA-25623-AL-E
–60–
LYNXR/LYNXR24 PROGRAMMING DEFAULT TABLES
(boldface indicates defaults that differ between tables)
Function Table 1 Table 2 Table 3 Table 4
*20 Installer code 4112 4112 4112 4112
*21 Quick arm enable 1 1 1 1
*22 Keypad backlight timeout 0 0 0 0
*23 Forced bypass 0 0 0 0
*24 RF house ID code 0,0 0,0 0,0 0,0
*25 Powerline carrier device house code 0 0 0 0
*26 Chime-by-zone 0 0 0 0
*27 Real-time clock display 1 1 1 1
*29 Daylight saving time start/end month 4,10 4,10 4,10 4,10
*30 Daylight saving time start/end weekend 1,5 1,5 1,5 1,5
*31 Single alarm sounding per zone 0 0 0 0
*32 Fire sounder timeout 0 0 0 0
*33 Alarm bell timeout 1 1 1 1
*34 Exit delay 7,0 6,0 7,0 7,0
*35 Entry delay 1 (zone type 01) 3,0 4,5 3,0 3,0
*36 Entry delay 2 (zone type 02) 6,0 6,0 6,0 6,0
*37 Audible exit warning/quick exit 1,1 0,1 1,1 1,1
*38 Confirmation of arming ding 0 0 0 0
*39 Power up in previous state 1 1 1 1
*40 PABX access code --- --- --- ---
*41 Primary phone number --- --- --- ---
*42 Secondary phone number --- --- --- ---
*43 Primary subscriber account number 15,15,15,15 15,15,15,15 15,15,15,15 15,15,15,15
*44 Secondary subscriber account number --- --- --- ---
*46 “Follow Me Reminder” Phone Number --- --- --- ---
*47 Phone system select 1 1 1 1
*48 Report format 7,7 7,7 7,7 7,7
*49 Split/dual reporting 0 0 0 9
*50 15 second dialer delay (burglary) 0 1 0 0
*51 Periodic test report 0 3 0 0
*52 First test report offset 2 2 2 2
*53 Sescoa/radionics select 0 0 0 0
*54 Lack of usage notification 0 0 0 0
*55 Wireless Dialer 0, 0, 0, 0 0, 0, 0, 0 0, 0, 0, 0 0, 0, 0, 0
*56 Enhanced Zone programming See *56 table See *56 table See *56 table See *56 table
*58 RF jam detection 0 0 0 0
*59 Exit error report code 1 0 1 1
*60 Trouble report code 1,0 1,0 1,0 1,0
*61 Bypass report code 0,0 0,0 0,0 0,0
*62 AC loss report code 0,0 0,0 0,0 0,0
*63 Low battery Report code 1,0 1,0 1,0 1,0
*64 Test report code 1,0 1,0 1,0 1,0
*65 Open report code 0 0 0 0
*66 Arm away/stay report code 0,0 0,0 0,0 0,0
*67 RF transmitter low battery report code 1,0 1,0 1,0 1,0
*68 Cancel report code 1,0 1,0 1,0 1,0
*70 Alarm restore codes 1 1 1 1
*71 Trouble restore report code 1,0 1,0 1,0 1,0
*72 Bypass restore report code 0,0 0,0 0,0 0,0
*73 AC restore report code 0,0 0,0 0,0 0,0
*74 Low battery restore report code 1,0 1,0 1,0 1,0
*75 RF transmitter low battery restore report code 1,0 1,0 1,0 1,0
*76 Test restore report code 0,0 1,0 0,0 0,0
*80 Powerline Carrier Devices See *80 table See *80 table See *80 table See *80 table
*81 Zone lists for devices See *81 table See *81 table See *81 table See *81 table
*84 Assign zone voice descriptors Refer to *84 Programming
*87 Auxiliary Function/ 1-button paging 0 1 0 1
*88 Pager characters --- --- --- ---
*89 Event log 80% full report code 0,0 0,0 0,0 0,0
*90 Event logging 3 15 3 3
*91 LRR/AAV Trigger/Remote Phone Control 2 2 2 2
*92 Number of reports in armed period 0 0 0 0
*93 Flexible call back 0 0 0 0
*94 Download phone number --- --- --- ---
*95 Ring detect count for downloading/remote phone control 15 15 15 15
Default Master Code 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4
Default Duress Code --- --- --- ---
By activating *96, Field 43, and 44 will be changed to 15, 15, 15, 15.
– 61 –
LYNXR-EN PROGRAMMING DEFAULT TABLES
(boldface indicates defaults that differ between tables)
Function Table 1 Table 2 Table 3 Table 4
*20 Installer code 4112 4112 4112 4112
*21 Quick arm enable 1 1 1 1
*22 Keypad backlight timeout 0 0 0 0
*23 Forced bypass 0 0 0 0
*24 RF house ID code 0,0 0,0 0,0 0,0
*25 Powerline carrier device house code 0 0 0 0
*26 Chime-by-zone 0 0 0 0
*27 Real-time clock display 1 1 1 1
*29 Daylight saving time start/end month 4,10 4,10 4,10 4,10
*30 Daylight saving time start/end weekend 1,5 1,5 1,5 1,5
*31 Single alarm sounding per zone 0 0 0 0
*32 Fire sounder timeout 0 0 0 0
*33 Alarm bell timeout 1 1 1 1
*34 Exit delay 7,0 6,0 7,0 7,0
*35 Entry delay 1 (zone type 01) 3,0 4,5 3,0 3,0
*36 Entry delay 2 (zone type 02) 6,0 6,0 6,0 6,0
*37 Audible exit warning/quick exit 1,1 0,1 1,1 1,1
*38 Confirmation of arming ding 0 0 0 0
*39 Power up in previous state 1 1 1 1
*40 PABX access code --- --- --- ---
*41 Primary phone number --- --- --- ---
*42 Secondary phone number --- --- --- ---
*43 Primary subscriber account number 15,15,15,15 15,15,15,15 15,15,15,15 15,15,15,15
*44 Secondary subscriber account number --- --- --- ---
*46 “Follow Me Reminder” Phone Number --- --- --- ---
*47 Phone system select 5 5 5 5
*48 Report format 7,7 7,7 7,7 7,7
*49 Split/dual reporting 0 0 0 9
*50 15 second dialer delay (burglary) 0 1 0 0
*51 Periodic test report 0 3 0 0
*52 First test report offset 2 2 2 2
*53 Sescoa/radionics select 0 0 0 0
*54 Lack of usage notification 0 0 0 0
*55 Wireless Dialer 0, 0, 0, 0 0, 0, 0, 0 0, 0, 0, 0 0, 0, 0, 0
*56 Enhanced Zone programming See *56 table See *56 table See *56 table See *56 table
*58 RF jam detection 0 0 0 0
*59 Exit error report code 1 0 1 1
*60 Trouble report code 1,0 1,0 1,0 1,0
*61 Bypass report code 0,0 0,0 0,0 0,0
*62 AC loss report code 0,0 0,0 0,0 0,0
*63 Low battery Report code 1,0 1,0 1,0 1,0
*64 Test report code 1,0 1,0 1,0 1,0
*65 Open report code 0 0 0 0
*66 Arm away/stay report code 0,0 0,0 0,0 0,0
*67 RF transmitter low battery report code 1,0 1,0 1,0 1,0
*68 Cancel report code 1,0 1,0 1,0 1,0
*70 Alarm restore codes 1 1 1 1
*71 Trouble restore report code 1,0 1,0 1,0 1,0
*72 Bypass restore report code 0,0 0,0 0,0 0,0
*73 AC restore report code 0,0 0,0 0,0 0,0
*74 Low battery restore report code 1,0 1,0 1,0 1,0
*75 RF transmitter low battery restore report code 1,0 1,0 1,0 1,0
*76 Test restore report code 0,0 1,0 0,0 0,0
*80 Powerline Carrier Devices See *80 table See *80 table --- See *80 table
*81 Zone lists for devices See *81 table See *81 table See *81 table See *81 table
*84 Assign zone voice descriptors Refer to *84 Programming
*87 Auxiliary Function/ 1-button paging 0 1 0 1
*88 Pager characters --- --- --- ---
*89 Event log 80% full report code 0,0 0,0 0,0 0,0
*90 Event logging 3 15 3 3
*91 Alarm audio verification/remote phone control 2 2 2 2
*92 Number of reports in armed period 0 0 0 0
*93 Flexible call back 0 0 0 0
*94 Download phone number --- --- --- ---
*95 Ring detect count for downloading/remote phone control 15 15 15 15
Default Master Code 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4
Default Duress Code --- --- --- ---
By activating *96, Field 43, and 44 will be changed to 15, 15, 15, 15.
– 62 –
✻56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLE 1
Zone No. Zone Type Alarm Code Input Type Loop Number Zone Descriptor
1 0 0,0 --- ---
2 1 1,0 3 (RF) 2 47, 04 (FRONT DOOR)
3 1 1,0 3 (RF) 2 33, 04 (BACK DOOR)
4 3 1,0 3 (RF) 2 80 (WINDOW)
5 10 1,0 3 (RF) 1 56 (MOTION DETECTOR)
26 21 1,0 5 (BR) 3
27 22 1,0 5 (BR) 2
28 20 1,0 5 (BR) 4
29 23 0,0 5 (BR) 1
30 21 1,0 5 (BR) 3
31 22 1,0 5 (BR) 2
32 20 1,0 5 (BR) 4
33 23 0,0 5 (BR) 1
92 --- 1,0 --- ---
99 6 1,0 --- ---
NOTE: Zone 1 is a hardwire zone; Zone 2 to 41 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic
– 63 –
✻80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 4 (devices 2-7 have no default values)
Start Stop
Zone Type Restore of Zone type
Device Number Action Event Zone List System Operation Zone List System operation
1 2 2 1 2
8** 2 33 36
** NOTE: If using an X-10 Powerhouse Security SH10A siren as device 8, you must change the device action default to “3” if using default
table 4.
✻80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 1 and 2 (devices 1-7 have no default values)
Start Stop
Zone Type Restore of Zone type
Device Number Action Event Zone List System Operation Zone List System operation
8** 2 33 36
✻81 ZONE LIST FOR OUTPUT DEVICES DEFAULT TABLE: Applies To Default Table 1 - 4.
Zone List 1 28, 32
Zone List 2 29, 33
Zone List 3 2, 3
– 64 –
–Index –
*55 Enabling the 5842 Wireless Dialer ................................... 25 B
*56 Enhanced Zone Programming Mode................11, 20, 24, 27 Babysitter Code ........................................................................47
*80 Device Programming Menu Mode....................24, 31, 32, 33 Back Plate...................................................................................5
*81 Zone List Menu Mode.................................................. 24, 34 Backlighting .............................................................................17
*83 Enhanced Sequential Mode ........... 24, 27, 29, 30, 35, 36, 37 Backup Battery...........................................................................9
*84 Assign Zone Voice Descriptors .........................24, 30, 38, 39 Backup Reporting.....................................................................18
*85 Record Custom Voice Descriptors ............................... 24, 40 Battery Life ..............................................................................12
*96 Initialize Download ID And Subscriber Acct. No. For Battery, Low .............................................................................52
Downloading ........................................................................ 24 Bell............................................................................................60
*97 Set All Program Fields To 1 Of 4 Sets Of Default Values 24 BR .......................................................................................11, 28
*98 Exits Programming Mode ................................................. 24 Burglary Zones .........................................................................17
*99 Exits Programming Mode ................................................. 24 Busy-Standby ...........................................................................52
1.2-Volt Nickel-Metal Hydride Batteries................................. 10 Button Transmitters ..........................................................11, 12
1332CN ...................................................................................... 9 Button Type ..............................................................................28
15 Second Dialer Delay................................................ 20, 61, 62 Button Zones.......................................................................26, 28
24-Hour Audible Alarm ........................................................... 16 Bypass Report Code......................................................21, 61, 62
24-Hour Auxiliary Alarm......................................................... 16 Bypass Restore Report Code ........................................21, 61, 62
24-Hour Silent Alarm ........................................................ 15, 47
5800 Series Transmitters ........................................................ 11 C
5800RL ............................................................................... 11, 13 CA Message Display.................................................................51
5801.......................................................................................... 11 Callback Number......................................................................23
5802MN.............................................................................. 11, 12 Cancel Report Code ............................................................61, 62
5802MN2.................................................................................. 12 Canceled Alarm ........................................................................21
5804.............................................................................. 11, 12, 35 CC .............................................................................................52
5804BD......................................................................... 11, 12, 17 Change the Master Code ..........................................................47
5804BDV ...................................................................... 11, 12, 17 Chime By Zone .............................................................17, 61, 62
5804E ................................................................................. 11, 12 Chime Mode........................................................................17, 48
5804WATCH ............................................................................ 11 Closing Report ..........................................................................18
5816.................................................................................... 11, 35 Comm. Failure..........................................................................52
5817.......................................................................................... 11 Communication ....................................................................4, 54
5827.............................................................................. 11, 13, 17 Compass Downloader ...............................................................45
5828V ....................................................................................... 13 Confirmation of Arming Ding ......................................18, 61, 62
5842.......................................................................................... 25 Connecting AC Power and Backup Battery ...............................9
90 ............................................................................................. 52 Contact ID ................................................................................54
Contact ID Event Codes ...........................................................55
A Contact ID Format .............................................................21, 47
AC Loss Report Code ................................................... 21, 61, 62 Contact ID Reporting .........................................................55, 60
AC Power ................................................................................... 9 Contacting Technical Support..................................................58
AC Power and Rechargeable Backup Battery......................... 10 Custom Descriptor Number .....................................................40
AC Power Loss ........................................................................... 9 Custom Voice Descriptors ..................................................24, 40
AC Restore Report Code .................................................... 61, 62
AC Transformer ......................................................................... 6 D
ADEMCO 1332/1332X10 ........................................................... 9 Data Encryption .......................................................................45
ADEMCO Express ............................................................. 19, 60 Data Field.................................................................................14
ADEMCO Low Speed......................................................... 19, 60 Daylight Savings Time Start/End................................17, 61, 62
Alarm Audio Verification (AAV)/Remote Phone Control ........ 23 Daylight Savings Time Start/End Week..................................17
Alarm Audio Verification (Two-Way Voice Feature)............... 50 Default Master Code ..........................................................61, 62
Alarm Bell Timeout ..................................................... 17, 61, 62 Default Tables ....................................................................61, 62
Alarm Output............................................................................. 4 Delete a Secondary Security Code ...........................................47
Alarm Restore Codes ......................................................... 61, 62 Delete Entire Zone List ............................................................34
Alarm Restore Report Code ..................................................... 21 Delete Zone Parameters Confirmation ..............................29, 37
Alarm Sounder......................................................................... 60 Delete Zones .............................................................................34
Arm Away/Stay Report Code ............................................. 61, 62 Descriptor ...........................................................................30, 38
Arm AWAY/STAY Report Code ............................................... 21 Desktop Mounting ......................................................................5
Arm–Away ............................................................................... 16 Device Action ............................................................................33
Armed System Test.................................................................. 53 Device Number .........................................................................33
Arm–Stay ................................................................................. 16 DI Display.................................................................................52
Assign (Or Change) A Secondary Security Code..................... 47 DIP Switches ............................................................................11
Assign Custom Voice Descriptors............................................ 40 Disable Local Sounder................................................................7
Assign Zone Voice Descriptors..................................... 38, 61, 62 Disarm ................................................................................16, 48
Audible Exit Warning/Quick Exit ............................... 18, 61, 62 Displays ....................................................................................52
AUX Function .......................................................................... 48 Download Call Back Phone Number........................................23
AUX Function/1-Button Paging................................... 22, 61, 62 Download Phone Number...................................................61, 62
AUX Key .................................................................................. 22 Download, Initial......................................................................45
AWAY Mode............................................................................. 48 Downloader...................................................................22, 45, 46
Duress Code........................................................................47, 63
– 65 –
E Low Battery Report Code.........................................................21
EA ............................................................................................ 51 Low Battery Restore Report Code ............................... 21, 61, 62
Earth Ground............................................................................. 6 Low Speed ................................................................................54
Enabling the 5842 Wireless Dialer ......................................... 25 LYNX-DM...................................................................................5
Enroll Mode ....................................................................... 29, 36 LYNXR/LYNXR24 Programming Default Tables ...................61
Enter/Change the Master Code............................................... 47 LYNXRCHKIT-HC...................................................................10
Entry Delay ..................................................................18, 61, 62 LYNXRCHKIT-SC ...................................................................10
Entry/Exit Burglary ................................................................ 15 LYNXR-EN Programming Default Tables ..............................62
Error Code 374......................................................................... 21
Event Log 80% Full Report Code .................................22, 61, 62 M
Event Logging...............................................................22, 61, 62 Macro Function ........................................................................22
Exit Alarm ............................................................................... 21 Master Code .............................................................................47
Exit Delay ...............................................................17, 18, 61, 62 Master Security Code...............................................................17
Exit Delay Restart ............................................................. 18, 48 Memory Of Alarm.....................................................................48
Exit Door.................................................................................. 17 Message Center ........................................................................48
Exit Error Alarm Displays ...................................................... 51 Modem Comm...........................................................................52
Exit Error Report Code.................................................21, 61, 62 Mounting Base ...........................................................................5
Exit Warning ........................................................................... 18 Mute System Announcements .................................................48
Exiting Program Mode ............................................................ 14
Expert Programming............................................................... 14 N
Express .................................................................................... 54 No Alarm Response ..................................................................16
External Sounder..................................................................... 17 No Delay ...................................................................................48
Number of Reports in Armed Period ........................... 23, 61, 62
F Open Report Code ........................................................ 21, 61, 62
Factory Defaults ...................................................................... 14 Operator Commands ................................................................50
Fault......................................................................................... 52 Optima 24 Plus FAX96 Modem................................................45
FC....................................................................................... 52, 54 Other Features ...........................................................................4
FCC Statement ........................................................................ 59 Other Functions .......................................................................48
Features ..................................................................................... 4
Fire Sounder Timeout...................................................17, 61, 62 P
First Test Report Offset................................................20, 61, 62 PABX Access Code ....................................................... 18, 61, 62
Flexible Callback ....................................................23, 45, 61, 62 Pager.........................................................................................19
“Follow Me” Alarm Announcement ......................................... 51 Pager Characters.......................................................... 22, 61, 62
“Follow Me” Reminder Feature ............................................... 51 Pager Function .........................................................................48
Follow Me Reminder” Phone Number..................................... 19 Pager Message..........................................................................22
Forced Bypass.........................................................17, 49, 61, 62 Pager Report Format ...............................................................19
Paging Feature.........................................................................22
G Panic Keys ................................................................................47
General Information ................................................................ 11 PC .............................................................................................52
General Programming Information......................................... 14 Perimeter Burglary ..................................................................15
Go/No Go Test Mode ................................................................ 12 Periodic Test Report..................................................... 20, 61, 62
PH.............................................................................................52
H Phone Lines................................................................................6
Handshake Frequency............................................................. 54 Phone System Select .................................................... 19, 61, 62
Hardwire Zone ................................................................6, 28, 63 Piezo .........................................................................................60
Hayes ....................................................................................... 45 Play Back a Message................................................................48
House ID .......................................................................13, 17, 32 Plug-In Transformer ..................................................................9
House Identification ................................................................ 11 Power Failure ...........................................................................52
Power Up in Previous State ......................................... 18, 61, 62
I Powerline Carrier Device ........................6, 17, 31, 32, 51, 61, 62
Input Type ....................................................................11, 28, 63 Powerline Carrier Device House Code............................... 61, 62
Installer Code .........................................................17, 47, 61, 62 Powerline Carrier Device Programming..................................33
Interactive Mode...................................................................... 14 Primary Phone Number ............................................... 18, 61, 62
Interior W/Delay ...................................................................... 16 Primary Subscriber Account Number.......................... 18, 61, 62
Interior, Follower..................................................................... 15 Program Mode, Entering..........................................................14
Programming Mode..................................................................17
K
Keypad Backlight Timeout...........................................17, 61, 62 Q
Keypad Functions.............................................................. 48, 49 Quick Arm ................................................................................48
Keys ......................................................................................... 11 Quick Arm Enable........................................................ 17, 61, 62
Kissoff Frequency .................................................................... 54 Quick Exit.................................................................................18
L R
Lack Of Usage Notification ..................................................... 20 Radionics ..................................................................................19
Local Sounder Disable Jumper ................................................. 6 Radionics/SESCOA ..................................................................60
Long Range Radio...................................................................... 6 Range........................................................................................11
Long Range Radio/Alarm Audio Verification Trigger/Remote Real-Time Clock Display.............................................. 17, 61, 62
Phone Control...................................................................... 23 Rechargeable Backup Battery ...................................................9
Loop Number ..................................................................... 28, 63 Record a Message .....................................................................48
LOW BAT................................................................................. 52 Remote Phone Access ...............................................................23
Low Battery Report Code .................................................. 61, 62 Remote Phone Control .............................................................49
– 66 –
Remote Programming .............................................................. 45 T
Remote Programming/Control........................................... 45, 46 Technical Support.................................................................... 58
Replacing the Rechargeable Battery ....................................... 10 Telco Handoff........................................................................... 45
Report Code........................................................................ 20, 28 Temporal Pulse........................................................................ 17
Report Code Formats ............................................................... 54 Test Mode ...............................................................48, 53, 56, 57
Report Format.............................................................. 19, 61, 62 Test Report Code ..........................................................21, 61, 62
Restart Exit Delay ............................................................. 18, 48 Test Restore Report Code.................................................. 61, 62
RF............................................................................................. 28 Testing The System................................................................. 53
RF (Supervised RF).................................................................. 11 Time and Date ......................................................................... 48
RF House ID Code ....................................................... 17, 61, 62 Transmitter Loop Numbers .................................................... 13
RF Transmitter Low Battery Report Code.................. 21, 61, 62 Transmitter Supervision ......................................................... 11
RF Transmitter Low Battery Restore ......................... 22, 61, 62 Transmitters............................................................................ 11
RF Jam..................................................................................... 20 Trouble By Day/....................................................................... 15
Ring Detect Count for Downloading............................ 23, 61, 62 Trouble Conditions .................................................................. 52
Trouble Report Code.....................................................21, 61, 62
S Trouble Restore Report Code .......................................21, 61, 62
Scheduling.......................................................................... 46, 48 Troubleshooting Guide ............................................................ 56
Secondary Phone Number ........................................... 18, 61, 62 Two-Way Voice .......................................................................... 6
Secondary Subscriber Account Number ...................... 18, 61, 62
Secondary User Codes ............................................................. 47 U
Security Code Handshake ....................................................... 45 Unsupervised Button RF......................................................... 11
Security Codes ................................................................... 17, 47 Unsupervised RF..................................................................... 11
Security Functions................................................................... 48 UR (Unsupervised RF) ...................................................... 11, 28
Serial Number.............................................24, 27, 29, 30, 35, 37 User Codes........................................................................... 4, 48
Sescoa/Rad ............................................................................... 54
Sescoa/Radionics Select ............................................... 20, 61, 62 V
Setting DIP Switches............................................................... 13 Voice Descriptor............................................................28, 30, 38
SH10A ...................................................................................... 33 Voice Prompt Programming Mode .......................................... 14
Signal Strength........................................................................ 12 Voice Vocabulary Index ........................................................... 39
Silent Burglary ........................................................................ 16 Voltage Input........................................................................... 60
Single Alarm Sounding Per Zone ................................ 17, 61, 62 Volume Control........................................................................ 48
Siren/Horn................................................................................ 33
Site-Initiated Remote Programming ....................................... 45 W
SMARTMODEM 1200 ............................................................. 45 Wall Mounting........................................................................... 5
Smoke Detectors ...................................................................... 57 WAVE2EX ............................................................................... 60
Sniffer Mode................................................................. 12, 53, 56 Wireless Buttons ..................................................................... 11
Sounders .................................................................................... 6 Wireless Dialer .............................................................19, 25, 26
Speaker Phone Operation........................................................ 49 Wireless Transmitter .............................................................. 21
Special Features ........................................................................ 4 Wiring Connections ................................. 6
Specifications ........................................................................... 60 World Wide Web Address...................... 58
Split/Dual Reporting.................................................... 19, 61, 62
Start By Event ......................................................................... 31 X
Start By Zone Type .................................................................. 31 X-10...............................................................................31, 46, 51
Start Event Type...................................................................... 33
Start Zone List ......................................................................... 33 Z
Start Zone Type ....................................................................... 33 Zone 1 Resistance .................................................................... 60
Station-Initiated Remote Programming.................................. 45 Zone Bypass............................................................................. 48
STAY Mode .............................................................................. 48 Zone Descriptor ....................................................................... 63
Stop Recording ......................................................................... 48 Zone Entry To List .................................................................. 34
Stop Zone List .......................................................................... 33 Zone List .......................................................................24, 62, 64
Stop Zone Type......................................................................... 33 Zone List Number.................................................................... 34
Supervised Fire........................................................................ 16 Zone List Programming........................................................... 34
Supervised RF.................................................................... 11, 28 Zone Lists For Devices ............................................................ 61
System Battery ........................................................................ 56 Zone Number ..........................................................26, 28, 35, 38
System Communication..................................................... 54, 55 Zone Programming ............................................................ 61, 62
System Features ........................................................................ 4 Zone Response Type .......................................................... 15, 16
System Operation ..................... 31, 32, 47, 48, 49, 50, 51, 52, 64 Zone Type .......................................................................... 28, 33
System Power............................................................................. 4 Zones and Devices ..................................................................... 4
System Words .......................................................................... 39
– 67 –
-Notes-
– 68 –
WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or
other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a
variety of reasons. For example:
• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work
without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put
in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the
Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may
not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not
sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of
closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector,
for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke
detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire
and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to
allow all occupants to escape in time to prevent injury or death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams
of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion
or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows.
Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical
system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the
ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection
performance can decrease.
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the
other side of closed or partly open doors. If warning devices are located on a different level of the residence from the
bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not
hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing
traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect
themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond
appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to
last as long as 20 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This
alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad
(and remote keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device
being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce
the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus
allowing time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for
insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to
insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones
to learn about these developments.
– 69 –
LIMITED WARRANTY
Honeywell International Inc. acting through its Security & Custom Electronics business ("Seller"), 165
Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and
specifications and to be free from defects in materials and workmanship under normal use and service for 24
months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12
months from date of original purchase unless the installation instructions or catalog sets forth a shorter
period, in which case the shorter period shall apply. Seller's obligation shall be limited to repairing or
replacing, at its option, free of charge for materials or labor, any product, which is proved not in compliance
with Seller's specifications or proves defective in materials or workmanship under normal use and service.
Seller shall have no obligation under this Limited Warranty or otherwise if the product is altered or
improperly repaired or serviced by anyone other than Honeywell factory service. For warranty service,
return product transportation prepaid, to Honeywell Factory Service, 165 Eileen Way, Syosset, New York
11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR
A PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE
FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL
OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR
DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the products it sells may not be compromised or circumvented; that the
products will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the
products will in all cases provide adequate warning or protection. Customer understands that a properly
installed and maintained alarm may only reduce the risk of a burglary, robbery, fire or other events
occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that
there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO
LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A
CLAIM THE PRODUCT FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE,
WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS
LIMITED WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM
LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT, WHICH
SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER. This warranty replaces
any previous warranties and is the only warranty made by Seller on this product. No increase or alteration,
written or verbal, of the obligations of this Limited Warranty is authorized.
– 70 –
AAV / LRR
TRIGGER
(LYNXR/LYNR24)
LRR
WARNING: EARTH TRIGGER
TO PREVENT GROUND PHONE ZONE (LYNXR-EN) SOUNDERS PLCD AC
RISK OF
SHOCK
DISCONNECT 8 3 5 6 8 11 12 13 14 15 16
1 2 4 7 9 10
TELEPHONE
emergency number.
RJ11 POSITION
LINE AT TELECOM JACK
JACK BEFORE TIP RING TIP RING (+) ( ) ( ) (+) ( ) (+) DATA SYNC
SERVICING OUT IN
THIS UNIT. HARD
WIRED
TO HANDSET INCOMING ZONE
PHONE PHONE
ALL OUTPUT LINE LINE
CIRCUITS
ARE POWER
LIMITED.
– 71 –
THIS EQUIPMENT SHOULD BE INSTALLED IN TRANSFORMERS
ACCORDANCE WITH THE NATIONAL FIRE PROTECTION INCOMING PROVIDED
ASSOCIATION'S STANDARD 72, CHAPTER 2 (NATIONAL TELEPHONE
FIRE PROTECTION ASSOC., BATTERYMARCH PARK, LINE
TO 24HR 110VAC
QUINICY, MA 02269). EARTH PREMISES UNSWITCHED
PIEZO
PRINTED INFORMATION DESCRIBING PROPER GROUND TELEPHONE OUTLET
INSTALLATION, EVACUATION PLANNING AND BELL
REPAIR SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT. 2k OHMS 6-14VDC AC
EOLR 30mA max. 1332/1332X10/1332CN
6-14VDC CONNECTIONS
AC
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. 120mA max.
OPERATION IS SUBJECT TO THE FOLLOWING TWO WEEKLY TESTING IS (e.g. WAVE2EX) SYNC
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE REQUIRED TO ENSURE
HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST PROPER OPERATION COM
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING
The System must be checked by a qualified technician once every three years.
OF THIS SYSTEM
INTERFERENCE THAT MAY CAUSE UNDESIRED DATA 1332X10 ONLY
OPERATION. CONNECTIONS
PLUG-IN
THE LYNX SERIES CONTROLS ARE EQUIPPED WITH FCC ID: CFS8 DLLYNX (LYNXR/LYNXR24) AND TRANSFORMER
AN INTEGRAL RECHARGEABLE BATTERY PACK. CFS8DLLYNXREN-1 (LYNXR-EN) COMPLIES WITH 9VAC, 15VA
LYNXR: P/N LYNXRCHKIT-SC FCC RULES, PART 68 FCC REGISTRATION
LYNXR24: P/N LYNXRCHKIT-HC No. 5GBUSA-25623-AL-E RINGER EQUIVALENCE: 0.6B
LYNXR-EN: P/N LYNXRCHKIT-SC
OR
P/N LYNXRCHKIT-HC
REPLACE EVERY FOUR YEARS
approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a police
NOTE: Connection of the fire alarm signal to a fire alarm headquarters or a central station shall be permitted with the
165 Eileen Way, Syosset, New York 11791
Copyright © 2004 Honeywell International Inc.
‡K5963V3oŠ
K5963V3bx 5/04 Rev. A www.honeywell.com/security