Mitigating Harmonics From Solar Power Plant BY Filters Using Etap
Mitigating Harmonics From Solar Power Plant BY Filters Using Etap
This article presents the harmonic analysis of voltage and current signals at PCC of a
grid connected Solar PV power plant. It also includes the mitigation of harmonics at PCC
within the desired limits as recommended by the standard IEEE519-2014.
In recent years, distribution network-connected single-phase and three-phase solar
inverter has many positive impacts like increased network sustainability, reduction in loss,
and enhanced voltage profile. The use of power electronic devices in photovoltaic systems
leads to the injection of harmonic and inter-harmonic components into the distribution
networks and, consequently, deviation of the network frequency around the main frequency.
In regard to sensitivity of the distribution network charges, among the power quality
parameters, the harmonic and inter-harmonic generation and propagation is particularly
important compared to the other parameters. The propagation of harmonic and inter-
harmonics cause’s losses in transformers, electrical machines, failure of capacitor banks,
relays and switches dysfunction, impaired communication and control systems, errors in
measuring devices, and the insulation failure of equipment. The size and rate of generation
harmonics depends on the type of technology and configuration of static converters.
The permitted harmonic range of current and voltage as per standard IEEE 519-
2014 is given below.
(Refer SIMULATION 3 for fifth harmonic voltage and SIMULATION 5 for fundamental
voltage)
Thus fifth harmonic voltage distortion is exceeding the limit which clearly depicts the
remaining individual voltage harmonic distortion will exceed the limit.
The harmonic order of components that exist for a particular system is given by the
formula,
h=np±1
Where, n=no. of converters used
p=no. of pulse of the converter used
For the minimum short circuit current (10 kA), considering the third row of Table 2,
3rd to 9th harmonic currents are taken to check with their individual limits.
Third harmonic current =Nil
Fifth harmonic current =48.4A (refer Simulation 3)
Seventh harmonic current=16.5A (refer Simulation 4)
Ninth harmonic current=Nil
Fundamental current=147.3A (refer Simulation 5)
Thus the fifth and seventh order harmonic currents are dominant in a six pulse inverter fed
system which can be clearly seen from the values given above.(Refer Simulation 3 and 4)
SIMULATION 3 SHOWING FIFTH HARMONIC VOLTAGE AND CURRENT
THD= *100
TDD= *100
HD= *100
It is clear the individual current harmonic distortions are exceeding the limit.
Thus both the voltage and current harmonic distortions are violating the limits mentioned in
IEEE519 2014 which necessitate the need of a harmonic filter.
DESIGN OF SINGLE TUNED FILTER:
It is clear the fifth and seventh harmonic currents are dominant and if those are
reduced, the current THD and TDD can be reduced to a great extent. Thus a suitable
passive filter especially a single tuned filter is employed at 11 kV to filter the 5 th harmonic
current.
Thus the filter has reduced the voltage THD from 3.19% to 0.92% and current THD from
35.58% to 6.47%.
TABLE-3 RESULTS
%HDV %HDI
FILTER STATUS BUS %THDV %THDI
(5th harmonic) (5th harmonic)
PCC(110
Without filter 2.409 3.12 32.85 35.58
kV bus)
PCC(110
With filter 0.445 0.92 4.99 6.47
kV bus)
SIMULATION 10 SHOWING THE DESIGN OF SINGLE TUNED FILTER
The filter parameters are designed as follows.
Q=P (tanՓ1-tanՓ2),
Where, Փ1 represents the angle of existing power factor
Փ2 represents the angle of desired power factor
P=S*pf
Q =31*0.912(0.4497-0.3286)
=3423 kVar
Xc=V2/Q
Where V=phase voltage of the bus where the filter is connected.
=6.35 2 /3.423
=11.77Ω
C=
=270.21microfarad
2
h =XC/XL
Where h is the harmonic order.
XL=11.77/52 =0.4708Ω