0ROGHG&DVH&LUFXLW%UHDNHUV
/'$)UDPH6HQWURQ6HULHV 6HOHFWLRQ
Type LXD6-A ad Blue Label Ordering Information
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) Complete Breaker Unassembled
2-Pole (3-Pole Width) 3-Pole with Lugs
Continuous Prices of LD6, HLD6, and HHLD6
Current Rating 600V AC 250V DC 600V AC 500V DC
breakers include frame, trip, and
@ 40°C Catalog Number Catalog Number both line and load lugs (TA2J6500).
450 LXD62B450Q LXD63B450 When ordered by these catalog
500 LXD62B500Q LXD63B500 numbers, the customer will receive
600 LXD62B600 LXD63B600 the frame, trip and lugs separately
packaged. For applications requiring
different lugs, order individual items
Type LD6-Ad Blue Label as needed.
Interchangeable Trip Complete Breaker Assembled with-
Continuous Complete Breaker out Lugs
Current Rating Unassembled w/Lugs Frame Only Trip Unit Only Prices of LXD6, HLXD6, HHLXD6,
@ 40°C Catalog Number Catalog Number Catalog Number and CLD6 include frame with non-
interchangeable trip unit installed
2-Pole 600V AC, 250V DC (3-Pole Width) only. Order required lugs separately.
250 LD62B250Q JD62T250Q For line and load lugs (TA2J6500)
300 LD62B300Q JD62T300Q installed, add suffix “L” to catalog
350 LD62B350Q JD62T350Q number (add 2 times list price of
400 LD62B400 LD62F600 JD62T400 lugs for each pole).
450 LD62B450Q LD62T450Q
500 LD62B500Q LD62T500Q 100% Rated (3-pole only)
600 LD62B600 LD62T600 Types LXD6 and HLXD6 breakers
3-Pole 600V AC, 500V DC b are available with 100% ratings.
To order add suffix “H” to catalog
250 LD63B250 JD63T250
300 LD63B300 JD63T300
number, and 10% to list price. 100%
350 LD63B350 JD63T350
rated LD breakers require the use of
400 LD63B400 LD63F600 JD63T400
90°C Cu cable sized at 75°C
450 LD63B450 LD63T450 ampacity and lugs TC1J6600
500 LD63B500 LD63T500 or TC2J6500.
600 LD63B600 LD63T600 50°C Applications see page 7-91.
400Hz Applications see page 7-91.
Interrupting Ratings
RMS Symmetrical Amperes (KA) Shipping Weights
UL 489 AIR (File E10848) IEC 947-2 Number of Number per Shipping
Volts AC (50/60Hz) Volts DC Volts AC (50/60Hz) Poles Carton Weight (lbs.)
Breaker
Type 240 480 600 250 500 c 220/240 380/415 500 LXD6, LD6, HLD6, HHLD6
7
Assembled Breaker (less terminals)
(lcu) (lcs) (lcu) (lcs) (lcu) (lcs)
2 1 17.5
LD6-A, LXD6-A 065 035 025 30 (2-P) 25 (3-P) 065 033 040 20 — —
&,5&8,7%5($.(56
02/'('&$6(
3 1 19.5
HLD6-A, HLXD6-A 100 065 035 30 (2-P) 35 (3-P) 100 050 065 33 — — LD6, HLD6, HHLD6 Frame Only
HHLD6, HHLXD6 200 100 050 — — — — — — — — 2 1 14
CLD6-A 200 150 100 — 50 (3-P) — — — — — — 3 1 15.5
LD6, HHLD6 Trip Unit Only
2 1 03.5
Instantaneous Adjustment Trip Range 3 1 04
Nominal Instantaneous Values CLD6 Complete Assembled Breaker
+20% +20% (less terminals)
Breaker Ampere Tolerance Tolerance 2 1 29.5
Rating Low 2 3 4 5 6 7 High 3 1 31.5
250-300 1250 1430 1610 1790 1960 2140 2320 2500
350-450 2000 2290 2570 2860 3140 3430 3710 4000 Lugs For 75°C Wire c
500-600 3000 3430 3800 4290 4710 5140 5570 6000 Cables
Catalog per Wire
Number Lug Range
TA2J6500 1, 2 #3/0 500 kcmil Cu
2 #4/0 500 kcmil Al
TC2J6500 2 #3/0-500 kcmil Cu
Q Built to order. Allow 2–3 weeks for delivery. TA1L6750 1 500-750 kcmil Al
1 500-600 kcmil Cu
a Type LXD6A circuit breakers are UL Listed for reverse
fed applications.
TC1J6600 1 #3/0-600 kcmil Cu
b When wired as shown on page 7-4, this circuit breaker is Compression Lug
UL listed and rated for use on 500V DC ungrounded Modifications page 7-91 CCL600 1 500 kcmil Cu/Al
UPS systems only.
c See Note: A, page 7-88. Enclosures Section 6
d HACR rated. Accessories pages 7-58 and 7-95 to 7-100
Note: LD frame qualified to UL489 supplement SB “NAVAL”.
See page 7-91 for additional information.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog