0% found this document useful (0 votes)
79 views

Stationary Louver J Blade: Application and Design

Uploaded by

Carlos Jiménez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views

Stationary Louver J Blade: Application and Design

Uploaded by

Carlos Jiménez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

ESJ-401

Stationary Louver
J Blade
Application and Design
ESJ-401 is a weather louver designed to protect air intake and
exhaust openings in building exterior walls. Design incorporates J style
blades, sloped sill and high free area to provide maximum resistance
to rain and weather while providing minimum resistance to airflow.
The ESJ-401 is an extremely efficient louver with AMCA LICENSED
PERFORMANCE DATA enabling designers to select and apply with
confidence.

Standard Construction
Frame ���������������Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.081 in. nominal wall thickness
Blades ���������������J style, heavy gauge extruded 6063-T5 aluminum,
0.081 in. nominal wall thickness, positioned at 37º
and 45º angles on approximately 4 in. centers
Construction �����Mechanically fastened
Birdscreen ���������3/4 in. x 0.051 in. flattened expanded aluminum in
removable frame, inside mount (rear)
Finish �����������������Mill
Minimum Size ���12 in. W x 12 in. H
Maximum Single
Section Size ������120 in. W or 120 in. H. (limited to 70 ft. sq.)

Options (at additional cost)


• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Glazing adaptor
• Hinged frame
• Security bars
• Welded construction
• 0.125 in. nominal wall thickness
• A variety of architectural finishes including:
Clear anodize
Integral color anodize
Baked enamel paint
Kynar paint

*Width and height dimensions furnished


approximately ¼ inch under size.
PERFORMANCE DATA ESJ-401
Stationary Louver J Blade
Extruded Aluminum
Free Area Chart (Sq. ft.)
Width in Inches
Greenheck Fan
Height in
Inches 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120
Corporation
certifies that
12 0.29 0.49 0.68 0.87 1.06 1.25 1.44 1.58 1.77 1.97 2.16 2.35 2.54 2.73 2.92 3.06 3.26 3.45 3.64
the ESJ-
18 0.54 0.89 1.24 1.59 1.94 2.29 2.64 2.91 3.26 3.61 3.96 4.31 4.66 5.01 5.36 5.62 5.97 6.32 6.67
401 louvers
24 0.75 1.24 1.73 2.22 2.71 3.20 3.69 4.05 4.54 5.03 5.52 6.01 6.50 6.99 7.47 7.84 8.33 8.82 9.31
shown herein
30 1.01 1.67 2.32 2.98 3.63 4.29 4.94 5.43 6.09 6.74 7.40 8.05 8.71 9.36 10.02 10.51 11.17 11.82 12.48 are licensed
36 1.26 2.07 2.89 3.70 4.51 5.33 6.14 6.76 7.57 8.38 9.20 10.01 10.83 11.64 12.46 13.07 13.88 14.70 15.51 to bear the
42 1.47 2.42 3.38 4.33 5.28 6.23 7.19 7.90 8.85 9.81 10.76 11.71 12.67 13.62 14.57 15.29 16.24 17.19 18.15 AMCA Seal.
48 1.73 2.85 3.96 5.08 6.20 7.32 8.44 9.28 10.40 11.52 12.64 13.76 14.88 16.00 17.12 17.96 19.08 20.19 21.31 The ratings shown are based
54 1.97 3.25 4.53 5.81 7.09 8.37 9.64 10.60 11.88 13.16 14.44 15.72 17.00 18.28 19.56 20.51 21.79 23.07 24.35
on tests and procedures
60 2.18 3.60 5.02 6.44 7.85 9.27 10.69 11.75 13.17 14.58 16.00 17.42 18.84 20.25 21.67 22.73 24.15 25.57 26.98
performed in accordance
with AMCA Publication
66 2.44 4.02 5.61 7.19 8.78 10.36 11.94 13.13 14.71 16.30 17.88 19.46 21.05 22.63 24.21 25.40 26.99 28.57 30.15
511 and comply with the
72 2.69 4.43 6.17 7.92 9.66 11.40 13.15 14.45 16.20 17.94 19.68 21.42 23.17 24.91 26.65 27.96 29.70 31.45 33.19
requirements of the AMCA
78 2.90 4.78 6.66 8.54 10.43 12.31 14.19 15.60 17.48 19.36 21.24 23.12 25.01 26.89 28.77 30.18 32.06 33.94 35.82 Certified Ratings Program.
84 3.16 5.20 7.25 9.30 11.35 13.40 15.44 16.98 19.03 21.07 23.12 25.17 27.22 29.26 31.31 32.85 34.90 36.94 38.99 The AMCA Certified
90 3.40 5.61 7.82 10.02 12.23 14.44 16.65 18.30 20.51 22.72 24.92 27.13 29.34 31.54 33.75 35.41 37.61 39.82 42.03 Ratings Seal applies to air
96 3.62 5.96 8.31 10.65 13.00 15.34 17.69 19.45 21.79 24.14 26.48 28.83 31.17 33.52 35.87 37.62 39.97 42.32 44.66 performance and water
102 3.87 6.38 8.90 11.41 13.92 16.43 18.94 20.83 23.34 25.85 28.36 30.87 33.39 35.90 38.41 40.29 42.81 45.32 47.83
penetration ratings.
108 4.12 6.79 9.46 12.13 14.80 17.48 20.15 22.15 24.82 27.49 30.16 32.84 35.51 38.18 40.85 42.85 45.52 48.20 50.87

114 4.33 7.14 9..95 12.76 15.57 18.38 21.19 23.30 26.11 28.92 31.73 34.53 37.34 40.15 42.96 45.07 47.88 50.69 53.50

120 4.59 7.56 10.54 13.52 16.49 19.47 22.44 24.68 27.65 30.63 33.60 36.58 39.56 42.53 45.51 47.74 50.72 53.69 56.67

Airflow Resistance (Standard Air - .075 lb/ft3) Water Penetration (Standard Air - .075 lb/ft3)
Pa in. wg Test size 48 in. x 48 in. Test duration of 15 min.
1 ml/m2 oz/ft2
0.9
0.30
200 0.8 Test Size 48 in. x 48 in.
0.7 Standard Air - .075 lb/ft
3
Test Size 48 in. x 48 in.
0.6 Test Period 15 minutes
80 0.25 Standard Air - .075 lb/ft
3
0.5
Water Penetration per Unit Free Area

100 0.4
90
80 0.20
0.3
70 60

60
Static Pressure Drop

50 0.2 0.15

40
40
ke

t
aus
Inta

Exh

30 0.10

0.1
0.09
20 0.08
20
0.05
0.07

0.06

0.05
0 0.00
10 0.04 600 650 700 750 800 850 900
ft/min:
9
8
0.03 m/s: 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5
7

6 Free Area Velocity


5 0.02
The AMCA Water Penetration Test provides a method for comparing
ft/min 200 300 400 500 600 700 800 900 1000 2000 3000
various louver models and designs as to their efficiency in resisting
m/s
the penetration of rainfall under specific laboratory test conditions. The
2 3 4 5 6 7 8 9 10
beginning point of water penetration is defined as that velocity where the
Free Air Velocity water penetration curve projects through .01 oz. of water (penetration)
Model ESJ-401 resistance to airflow (pressure drop) varies per sq. ft. of louver free area. *The beginning point of water
depending on louver application (air intake or air exhaust). penetration for Model ESJ-401 is 691 fpm free area velocity.
Free area velocities (shown) are higher than average These perfor­mance ratings do not guarantee a louver to be weather­proof
velocity through the overall louver size. See louver selection or stormproof and should be used in combination with other factors
information. including good engineering judgement in selecting louvers.
INSTALLATION DETAILS ESJ-401
Stationary Louver J Blade
Maximum Size and Installation Information Extruded Aluminu

Maximum single section size for model ESJ-401 is 120 in. W x 84 in. H or 84 in. W x 120 in. H (70 sq. ft). Larger openings require
field assembly of multiple louver sections to make up the overall opening size. Individual louver sections are designed to withstand
a 25 PSF wind load (please consult Greenheck if the louvers must withstand higher wind-loads). Structural reinforcing members
may be required to adequately support and install multiple louver sections within a large opening. Structural reinforcing members
along with any associated installation hardware is not provided by Greenheck unless indicated otherwise by Greenheck. Options
and accessories including, but not limited to, screens, filter racks, louver doors, and blank off panels are not subject to structural
analysis unless indicated otherwise by Greenheck. Additional information on louver installation may be found in AMCA Publication
#501, Louver Application Manual.

Minimum Single Section Size Maximum Single Section Size


12 in. W x 12 in. H 70 ft. sq.
PRODUCT DETAILS ESJ-401
Stationary Louver J Blade
Extruded Aluminu
OPTION DRAWINGS ESJ-401
Stationary Louver J Blade
Extruded Aluminu

FINISHES
Standard Warranty
Finish Type Description/Application Color Selection
(Aluminum)
Standard Colors: Any of the 24
“Best.” The premier finish for extruded aluminum. Tough, 10 Years
2-coat 70% KYNAR 500®/HYLAR 5000® AAMA 2605 – standard colors shown can be
long-lasting coating has superior color retention and (Consult Greenheck for
Dry film thickness 1.2 mil. (AKA: Duranar®, Fluoropon®, furnished in 70% or 50% KYNAR
abrasive properties. Resists chalking, fading, chemical availability of extended
Trinar®, Flouropolymer, Polyvinylidene Fluoride, PVDF2) 500®/HYLAR 5000® or Baked Enamel.
abrasion and weathering. warranty)

2-Coat Mica:
“Better.” Tough, long-lasting coating has excellent color Greenheck offers 9 standard 2-
2-coat 50% KYNAR 500®/HYLAR 5000® AAMA 2604
retention and abrasive properties. Resists chalking, fading, coat Mica colors. Other colors are 5 Years
– Dry film thickness 1.2 mil. (AKA: Acroflur®, Acrynar®)
chemical abrasion and weathering. available. Consult Greenheck for
possible extra cost when selecting
Baked Enamel AAMA 2603 – Dry film thickness 0.8 mil. “Good.” Provides good adhesion and resistance to non-standard colors or special
1 Year
(AKA: Acrabond Plus®, Duracron®) weathering, corrosion and chemical stain. finishes.

“Two-step” anodizing is produced by following the normal Light, Medium or Dark Bronze;
Integral Color Anodize AA-M10C22A42 (>0.7 mil) 5 years
anodizing step with a second, colorfast process. Champagne; Black

Clear, colorless and hard oxide aluminum coating that resists


Clear Anodize 215 R-1 AA-M10C22A41 (>0.7 mil) Clear 5 years
weathering and chemical attack.

Clear, colorless and hard oxide aluminum coating that resists


Clear Anodize 204 R-1 AA-M10C22A31 (0.4-0.7 mil) Clear 1 Year
weathering and chemical attack.

Greenheck offers a number of industrial coatings such as Hi-Pro Polyester, Epoxy, and Permatector®.
Industrial coatings Consult Greenheck
Consult a Greenheck Product Specialist for complete color and application information.

Materials may be supplied in natural aluminum or galvanized steel finish when normal weathering is
Mill n/a
acceptable and there is no concern for color or color change.

Finishes meet or exceed AAMA 2605, AAMA 2604, and AAMA 2603 requirements. Please consult www.greenheck.com for complete information on standard and
extended paint warranties. Paint finish warranties are not applicable to steel products.

ESJ-401
September 2018
Copyright © 2018 Greenheck Fan Corporation

Greenheck Fan Corporation reserves the right


to make product changes without notice.

You might also like