Power System Previous Question PDF
Power System Previous Question PDF
Sl Question Exam
1 The annual load duration curve of a certain power station can be considered as straight line
from 20MW to 4MW. To meet this load, three turbine generator units, two rated at 10MW
each and one rated 5MW are installed. Determine (i) installed capacity (ii) plant factor (iii)
load factor (iv) utilization factor NESCO-2020
2 Why both directional and non-directional relays are used for parallel feeders? Venue: RUET
3 A generator is rated 500MVA, 22kV. It is Y-connected and solidly grounded. It reactance
are X``=X2=0.15ohm and X0=0.05 per unit. Find sub-transient line current for single lone to
ground fault
4 Explain the different sources of energy available in nature
5 What are the advantages of liquid fuels over solid fuels and solid fuels over liquid fuels for
power generation
6 What are the nuclear wastes and how are they managed?
7 A 100MW steam power station uses coal of calorific value 6400Kcal/kg. Thermal efficiency
of the station is 30% and electrical efficiency is 92&. Calculate the coal consumption per
hour when the station is delivering its full rated output.
8 Define and explain the following terms in generation: (i) Connected load (ii) Maximum
demand (iii) Demand factor (iv) Average load 40th BCS-2020
9 Derive a expression for the most economical v alue of power factor which may be attained
by a consumer.
10 Draw the single line diagram of a 132/33kV grid substatiob showing metering and
protection scheme
11 Mention the different types of protection used in a 3-phase transformer. Explain the working
principle of distance relay used in protection of power system
12 Write Short Notes: Generation Scheduling, Swing Equation
13 How a synchronous motor works as a power factor improvement device. Show the logic
14 The section bus-bars A & B are linked by a bus-bar reactor at 5000JVA with 10% reactance.
On bus-bar A, there are two generators each of 10000KVA with reactance 10% and on B
two generators each of 8000KVA with 12% reactance. Find the steady MVA fed into a dead
short circuit between all phases on B with bus-bar reactor in the circuit.
MIST MSc
Admission-
2020
15 Find the plant capacity of the station where power station has an annual load factor of 0.7.
Its total output in a year 1000 Million KWH and the utilization factor is 0.6
16 Two generators rated 10MVA, 132KV and 15MVA 13.2KV respectively are connected in
parallel to a bus. The bus fed to a synchronous motor rated 8MVA and 12MVA. The rated
voltage of the motor is 12.5KV. The reactance of each generator is 20% and each motor is EGCB-2020
15% on their own rating. [Assume 50MVA, 10kV base] Venue: BUET
17 Find Zbus and Ybus=?
RPCL-2019
Venue: MIST
36 A 3-phase, 5KW induction motor has a pf of 0.75 lagging. A bank of capacitor is connected
BR Power-2019
in Delta across the supply terminals and pf raised to 0.9 lagging. Determine the KVAR
Venue: MIST
rating of the capacitors connected in each phase.