ACS 600 MultiDrive Control Electronics LED Indicators
ACS 600 MultiDrive Control Electronics LED Indicators
6 YPQ-112A DDCS Interface Unit (5 MBd) V27 B (upper) WD Red Watchdog is expired (Not triggered)
YPQ-112B DDCS Interface Unit (10 MBd) V27 A (lower) 5V OK Green Logic voltage +5 V is OK (Reset inactive)
V23 B (upper) - Green Not in use
V23 A (lower) TXD Green Channels 1-4 are sending a message
V19 B (upper) RXD4 Green Channel 4 is receiving a reply message
V19 A (lower) RXD3 Green Channel 3 is receiving a reply message
V17 B (upper) RXD2 Green Channel 2 is receiving a reply message
V17 A (lower) RXD1 Green Channel 1 is receiving a reply message
7 NLMD-01 LED Monitoring Display V1 READY Yellow Drive in standby state (Stopped)
(Drive Monitoring Display) V2 RUN Green Drive is running
V3 FAULT Red Fault situation detected by SW
V4-24 0 … 100 % Green Parameter value in %
V25-34 100 … 150 % Yellow Parameter value in %
8 NDPI-21 Drives Panel Interface 2 V1 (24 V) Green Power supply voltage +24 V is on
V2 (FAULT) Red Fault situation detected by SW
9 NINT-45 Main Circuit Interface Board V11 - Green Logic voltage +5 V is on
10 NINT-46 Main Circuit Interface Board V11 - Green Logic voltage +5 V is on
NINT-66
11 NINT-54 Main Circuit Interface Board V18 TU Green Indicates that inverter phase U is the hottest
NINT-64 V19 TV Yellow Indicates that inverter phase V is the hottest
NINT-68 V20 TW Red Indicates that inverter phase W is the hottest
V11 T1 Yellow Indicates that Power Plate 1 is hotter (V-phase)
V10 T2 Green Indicates that Power Plate 2 is hotter (V-phase)
12 NINT-67 Main Circuit Interface Board V21 U Green Indicates that inverter phase and Power Plate U is the hottest
V22 V Yellow Indicates that inverter phase and Power Plate V is the hottest
V23 W Red Indicates that inverter phase and Power Plate W is the hottest
ABB Industry Oy ACS 600 MULTIDRIVE CONTROL ELECTRONICS 3AFE 6428 9721
Drives, System AC LED INDICATORS 00047862.DOC
Dept. Project Date Author Approved Revision Page
EIX 05.04.2000 Mika J Leppänen Ismo Toikka A 3/6
13 NINT-70 Main Circuit Interface Board V18 U Green Indicates that inverter phase U is the hottest
V19 V Yellow Indicates that inverter phase V is the hottest
V20 W Red Indicates that inverter phase W is the hottest
V21 1 Green Indicates that Power Plate 1 is the hottest (V-phase)
V22 2 Yellow Indicates that Power Plate 2 is the hottest (V-phase)
V23 3 Red Indicates that Power Plate 3 is the hottest (V-phase)
14 NXPP-02 Control Distribution Board V4 T1 Yellow Indicates that Power Plate 1 is hotter (U / W-phase)
V5 T2 Green Indicates that Power Plate 2 is hotter (U / W-phase)
15 NXPP-03 Control Distribution Board V4 1 Green Indicates that Power Plate 1 is the hottest (U / W-phase)
V5 2 Yellow Indicates that Power Plate 2 is the hottest (U / W-phase)
V6 3 Red Indicates that Power Plate 3 is the hottest (U / W-phase)
16 NPOW-41, -42, Power Supply Board V15 - Green Output voltage +15 V on
-43, -61, -62
17 NDSC-01 Diode Supply Unit Controller V20 +24 V Yellow Power supply voltage +24 V is on and the use OK
V18 TXD Yellow DDCS channel is sending a message
V29 RXD Yellow DDCS channel is receiving a reply message
V16 DI1 Yellow Digital input 1 is active: Fan is on and main contactor is closed
V78 DI2 Yellow Digital input 2 is active: RUN command on
V88 DI3 Yellow Digital input 3 is active: Fault RESET on
V32 DO1 Yellow Digital output 1 is active: Indication of an error situation (FAULT)
V5 DO2 Yellow Digital output 2 is active: DSU running normally
V22 DO3 Yellow Digital output 3 is active: Main contactor is closed
V19 DO4 Yellow Digital output 4 is active: ALARM signal is on
18 NGPS-02 GDR Power Supply, 10 W V8 PWR ON Green Output voltage +15 V is on
28 NPCT-01 Pulse Counter & Timer Unit V3 (upper) NOT READY Red Not ready signal (Not configured)
V15 (lower) 5V Green Logic voltage +5 V is OK (Reset inactive)
V80 (upper) CHA2 Yellow Indicates pulse encoder signal, Channel A2
V83 (lower) CHA1 Yellow Indicates pulse encoder signal, Channel A1
V81 (upper) CHB2 Yellow Indicates pulse encoder signal, Channel B2
V84 (lower) CHB1 Yellow Indicates pulse encoder signal, Channel B1
V82 (upper) CHZ2 Yellow Indicates pulse encoder signal, Channel Z2
V85 (lower) CHZ1 Yellow Indicates pulse encoder signal, Channel Z1
V60 (upper) DO1 Yellow Digital output 1 is active
V56 (lower) DI1 Yellow Digital input 1 is active
V61 (upper) DO2 Yellow Digital output 2 is active
V71 (lower) DI2 Yellow Digital input 2 is active
V70 (upper) DO3 Yellow Digital output 3 is active
V75 (lower) DI3 Yellow Digital input 3 is active
V69 (upper) DO4 Yellow Digital output 4 is active
V79 (lower) DI4 Yellow Digital input 4 is active
29 NMBC-01 Modbus Connection Unit V3 24V CDP Green Power supply voltage 24 V to CDP 80 is on
V4 24V IN Green Power supply voltage 24 V IN is on
30 NAPI-01 Alarm Printer Interface V24 B (upper) PAPER EMPTY Red No paper in printer
V24 A (lower) ERROR Red Printer fault
V23 B (upper) ON LINE Green Printer in On Line state
V23 A (lower) 5 V OK Green Logic voltage +5 V is OK (Reset inactive)
V22 B (upper) TXD Green A message transmitted to RS-485 port (Stretched light pulse)
V22 A (lower) RXD Green A message received from RS-485 port (Stretched light pulse)
31 NWIO-01 Watchdog & I/O Module W7 B (lower) DO 1 Yellow Digital output 1
W7 A (upper) DO 2 Yellow Digital output 2 (Watchdog output)
W6 B (lower) DI 1 Yellow Digital input 1
W6 A (upper) DI 2 Yellow Digital input 2
32 NCTI-01 Crane Transducer Interface V2 RS-485 TXD Green RS-485 link is sending a message
(Board 2) V5 RS-485 RXD Green RS-485 link is receiving a reply a message
V1 FAULT Red Fault situation detected by SW
33 NCSA-01 CS 31 Adapter V2 DDCS Green Indicates the status of the DDCS link
ABB Industry Oy ACS 600 MULTIDRIVE CONTROL ELECTRONICS 3AFE 6428 9721
Drives, System AC LED INDICATORS 00047862.DOC
Dept. Project Date Author Approved Revision Page
EIX 05.04.2000 Mika J Leppänen Ismo Toikka A 6/6
(NCSAM-01 Board) V5 UART Green Indicates the status of the CS 31 bus communication
V1 ERROR Red Indication of fault situation
34 NIBA-01 Interbus-S Adapter V2 DDCS Green Indicates the status of the DDCS link
V5 IB-S Yellow/Orange Process data and/or PCP communication enabled
V6 ERROR Red Indicates combined error and module status
D2 RC Green Cable connection correct, host not being reset
D1 BA Green Bus is active
D8 TR Green PCP communication is active
D3 UL Green Module power is OK (Reset inactive)
D6 RD Red Extended remote bus interface disabled
35 NMBA-01 Modbus Adapter V2 XMIT Green Indicates transmission on the Modbus network
(NMBAM-01 Board) V5 REC Green Indicates command receiving from the Modbus network
V1 ERROR Red Indicates combined error and module status
36 NMBP-01 Modbus Plus Adapter D1 STATUS Yellow/Orange Indicates error diagnostics by listed status codes
D2 MBP Green Indicates standard diagnostics by listed status codes
D3 POWER Green Logic voltage +5 V is OK (Reset inactive)
D4 DDCS Green Indicates the status of the DDCS link
37 NPBA-01/-02 Profibus Adapter V3 MASTER Red Indicates that correct baud rate found (in Auto Baud Rate mode)
(NPBAM-01 Board) V4 MSG Green Indicates data transfer with master active
V5 DDCS Green Indicates the status of the DDCS link