Relief Load Calculation For Fire Case - As Per API 521
Relief Load Calculation For Fire Case - As Per API 521
Only equipements or part of equipements below 25ft from ground are considered under fire case.
Equipement adjescent to fire source within the diameter of 24m are only considered to have direct impact on relief load.
Q= C*F*A^0.82
2
A (M ) Area covered by liquid to be calculated
F Environmental Factor API-521 PP-41
C For SI units 43200 43200
lambda (joule/Kg)
From Simulation / Based on
Molecular Wt (g)
thermodynamic calculation
Real gas const 8.314
Number of moles
#DIV/0!
Relieving temperature#
Relief load at relieving condition can be calculated using ideal gas equation PV=nRT
# SULZER CONFIDENTIAL