Busbar Calculation Report

The document provides a busbar calculation report for the Hamad Women's Hospital project. It details the busbar ratings, fault ratings, protective devices, and sizing calculations for busbars BBT-01A and BBT-01B. The calculations show that the 2500A rated busbars meet the required ratings based on the overload settings and fault levels at the tap off points.

Uploaded by

waseem kausar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
199 views

Busbar Calculation Report

The document provides a busbar calculation report for the Hamad Women's Hospital project. It details the busbar ratings, fault ratings, protective devices, and sizing calculations for busbars BBT-01A and BBT-01B. The calculations show that the 2500A rated busbars meet the required ratings based on the overload settings and fault levels at the tap off points.

Uploaded by

waseem kausar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar BBT-01A (2500A TPN+E )

Supplied By : Trans. No. G

Active Source TRANS. No. G (Exisiting )

Location Mezzanine LV -Room Function BUSDUCT

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent Protection: Terasaki ACB standard AR216S -21BL-PS LSI


Rating In (A): 1600 [f] Overload Setting Ir (A): 1152 [f]

Busbar Details [a] = Auto, [f] = Fixed

Type: Generic Generic Copper


Rating (A): 2500 [f] [Busbar rating for adjustable devices is based on the overload setting Ir]

Length (m): 20

No. of Phases: 3 No. of Poles: 4


Mounting: Horizontal

Fault Rating

Busbar Peak Fault Rating (kA peak): 237.0


Calculated Peak Fault Current (kA peak): 62.6
Short-time Withstand (kA rms/sec): 109.0/ 1.0
10
8
Phase Fault Withstand (A²s): Calculated Energy Let-Through: 4 x 10 Busbar: 1.2 x 10
9
Earth Fault Withstand (A²s): Calculated Energy Let-Through: 8.6 x 10 7
Busbar: 4.8 x 10

CPC Type: Integral

Correction Factors

Factor:
Ambient Temperature (deg C): 50.0 0.84

Mounting Method: Horizontal 1.00

Harmonics (%): 0 1.00

Total: 0.840

Busbar Sizing (A)

Design Current (Ib): 545.2

Device Rating (In): 1600 Overload Setting (Ir): 1152

Required Rating (Iz): 1371.4 [Iz = In/0.840]

Actual Rating (It): 2500 [It >= Iz]

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 1 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar Section Section Fault Level Zs Earth Fault Volt Drop Section
inc. Cmin
From: To: Length at Tap Off (kA) (Total) at Tap Off Load
(exc. Cmin)
(m) Min Max ( W) (kA) (%) (A)

Swing Panel -1A SLVP-01A 20 24.35 28.77 0.0101 22.45 0.79 545.2
(23.63)

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 2 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar BBT-01B (2500A TPN+E )

Supplied By : Trans. No. G

Active Source TRANS. No. G (Exisiting )

Location Mezzanine LV -Room Function BUSDUCT

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent Protection: Terasaki ACB standard AR216S -21BL-PS LSI


Rating In (A): 1600 [f] Overload Setting Ir (A): 1280 [f]

Busbar Details [a] = Auto, [f] = Fixed

Type: Generic Generic Copper


Rating (A): 2500 [f] [Busbar rating for adjustable devices is based on the overload setting Ir]

Length (m): 20

No. of Phases: 3 No. of Poles: 4


Mounting: Horizontal

Fault Rating

Busbar Peak Fault Rating (kA peak): 237.0


Calculated Peak Fault Current (kA peak): 62.6
Short-time Withstand (kA rms/sec): 109.0/ 1.0
10
8
Phase Fault Withstand (A²s): Calculated Energy Let-Through: 2.8 x 10 Busbar: 1.2 x 10
9
Earth Fault Withstand (A²s): Calculated Energy Let-Through: 8.6 x 10 7
Busbar: 4.8 x 10

CPC Type: Integral

Correction Factors

Factor:
Ambient Temperature (deg C): 50.0 0.84

Mounting Method: Horizontal 1.00

Harmonics (%): 0.03 1.00

Total: 0.840

Busbar Sizing (A)

Design Current (Ib): 991.5

Device Rating (In): 1600 Overload Setting (Ir): 1280

Required Rating (Iz): 1523.8 [Iz = In/0.840]

Actual Rating (It): 2500 [It >= Iz]

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 3 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar Section Section Fault Level Zs Earth Fault Volt Drop Section
inc. Cmin
From: To: Length at Tap Off (kA) (Total) at Tap Off Load
(exc. Cmin)
(m) Min Max ( W) (kA) (%) (A)

Swing Panel -1A SLVP-01B 20 24.35 28.77 0.0101 22.43 0.87 991.5
(23.61)

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 4 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar BTS-04B

Supplied By : Trans. No. G

Active Source TRANS. No. G (Exisiting )

Location Function

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent Protection: Terasaki ACB standard AR208S -21BL-PS LSI


Rating In (A): 800 [f] Overload Setting Ir (A): 640 [f]

Busbar Details [a] = Auto, [f] = Fixed

Type: Generic Generic Copper


Rating (A): 1000 [f] [Busbar rating for adjustable devices is based on the overload setting Ir]

Length (m): 105

No. of Phases: 3 No. of Poles: 4


Mounting: Vertical

Fault Rating

Busbar Peak Fault Rating (kA peak): 137.0


Calculated Peak Fault Current (kA peak): 58.4
Short-time Withstand (kA rms/sec): 63.0 / 1.0
9
7
Phase Fault Withstand (A²s): Calculated Energy Let-Through: 7.7 x 10 Busbar: 4 x 10
9
Earth Fault Withstand (A²s): Calculated Energy Let-Through: 7.4 x 10 7
Busbar: 2.7 x 10

CPC Type: Integral

Correction Factors

Factor:
Ambient Temperature (deg C): 50.0 0.84

Mounting Method: Vertical 1.00

Harmonics (%): 0 1.00

Total: 0.840

Busbar Sizing (A)

Design Current (Ib): 617.5

Device Rating (In): 800 Overload Setting (Ir): 640

Required Rating (Iz): 761.9 [Iz = In/0.840]

Actual Rating (It): 1000 [It >= Iz]

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 5 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar Section Section Fault Level Zs Earth Fault Volt Drop Section
inc. Cmin
From: To: Length at Tap Off (kA) (Total) at Tap Off Load
(exc. Cmin)
(m) Min Max ( W) (kA) (%) (A)

SLVP-01B BTS-04B (1200A)_TAP-OFF 105 12.22 19.45 0.0197 11.54 2.27 617.5
(12.14)

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 6 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar BTS-05A (1000A, TPN)

Supplied By : Trans. No. G

Active Source TRANS. No. G (Exisiting )

Location Function

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent Protection: Terasaki TemBreak2 MCCB S250-PE LSI


Rating In (A): 250 [f] Overload Setting Ir (A): 237.5 [f]

Busbar Details [a] = Auto, [f] = Fixed

Type: Generic Generic Copper


Rating (A): 1000 [f] [Busbar rating for adjustable devices is based on the overload setting Ir]

Length (m): 100

No. of Phases: 3 No. of Poles: 4


Mounting: Vertical

Fault Rating

Busbar Peak Fault Rating (kA peak): 137.0


Calculated Peak Fault Current (kA peak): 58.5
Short-time Withstand (kA rms/sec): 63.0 / 1.0
9
6
Phase Fault Withstand (A²s): Calculated Energy Let-Through: 1.2 x 10 Busbar: 4 x 10
9
Earth Fault Withstand (A²s): Calculated Energy Let-Through: 1.1 x 10 6
Busbar: 2.7 x 10

CPC Type: Integral

Correction Factors

Factor:
Ambient Temperature (deg C): 50.0 0.84

Mounting Method: Vertical 1.00

Harmonics (%): 0 1.00

Total: 0.840

Busbar Sizing (A)

Design Current (Ib): 216

Device Rating (In): 250 Overload Setting (Ir): 237.5

Required Rating (Iz): 282.7 [Iz = In/0.840]

Actual Rating (It): 1000 [It >= Iz]

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 7 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar Section Section Fault Level Zs Earth Fault Volt Drop Section
inc. Cmin
From: To: Length at Tap Off (kA) (Total) at Tap Off Load
(exc. Cmin)
(m) Min Max ( W) (kA) (%) (A)

SLVP-01A BTS-05A ( TAP OFF ) 100 12.54 19.78 0.0191 11.90 1.25 216.0
(12.53)

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 8 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar BTS-05B (1000A, TPN)

Supplied By : Trans. No. G

Active Source TRANS. No. G (Exisiting )

Location Function

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent Protection: Terasaki TemBreak2 MCCB S250-PE LSI


Rating In (A): 250 [f] Overload Setting Ir (A): 250 [m]

Busbar Details [a] = Auto, [f] = Fixed

Type: Generic Generic Copper


Rating (A): 1000 [f] [Busbar rating for adjustable devices is based on the overload setting Ir]

Length (m): 120

No. of Phases: 3 No. of Poles: 4


Mounting: Vertical

Fault Rating

Busbar Peak Fault Rating (kA peak): 137.0


Calculated Peak Fault Current (kA peak): 58.5
Short-time Withstand (kA rms/sec): 63.0 / 1.0
9
6
Phase Fault Withstand (A²s): Calculated Energy Let-Through: 1.1 x 10 Busbar: 4 x 10
9
Earth Fault Withstand (A²s): Calculated Energy Let-Through: 1.1 x 10 6
Busbar: 2.7 x 10

CPC Type: Integral

Correction Factors

Factor:
Ambient Temperature (deg C): 50.0 0.84

Mounting Method: Vertical 1.00

Harmonics (%): 0 1.00

Total: 0.840

Busbar Sizing (A)

Design Current (Ib): 0

Device Rating (In): 250 Overload Setting (Ir): 250

Required Rating (Iz): 297.6 [Iz = In/0.840]

Actual Rating (It): 1000 [It >= Iz]

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 9 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.
Busbar Calculation Report

Project Reference: Hamad Women's Hospital Job Number:

Document No: Created On: 11/26/2018 Rev Date: 4/8/2020


Created By: SWAMINATHAN GNANESWARAN
Revised By: VAIBHAV KANTHE Revision: REV-A

Busbar Section Section Fault Level Zs Earth Fault Volt Drop Section
inc. Cmin
From: To: Length at Tap Off (kA) (Total) at Tap Off Load
(exc. Cmin)
(m) Min Max ( W) (kA) (%) (A)

SLVP-01A BTS-05B ( TAP OFF ) 120 11.35 18.51 0.0202 11.28 0.79 0.0
(11.87)

Project: Hamad Building Construction -SLVP-01 & 02 - Rev. 2.p18x Page 10 of 10 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.