Multi-Criteria Photo/Thermal/Infrared Detectors: FPTI-951 Series
Multi-Criteria Photo/Thermal/Infrared Detectors: FPTI-951 Series
General Description
The FPTI-951/-IV and FPTI-951A/-IV are plug-in addressable multi-
criteria detectors that replace the FAPT-851 Series. They combine
photoelectric, thermal, and infrared (PTIR) sensors in one unit to
sense multiple components of a fire. This approach enables
enhanced sensitivity to real fire with heightened immunity to nui-
sance particulates.
Multiple sensors and communication can greatly reduce nuisance
alarms compared to single sensing methods. Sophisticated algo-
rithms maximize the advantages of the sensor types. This detection
strategy offers heightened immunity to nuisance particulates and
enhanced sensitivity to real fire.
• Photoelectric sensors detect airborne particles associated with
smoke.
• Thermal sensors detect heat and rate-of-rise (135°F fixed tem-
perature threshold).
FPTI-951 Multi-Criteria Detector installed in
• The Infrared sensor discerns light patterns in the environment as B200S-WH sounder base
an additional data point for alarm determination.
This ability to reject certain nuisance alarm triggers, such as theater
smoke, supports the use of the detector in applications where mod- ELECTRICAL SPECIFICATIONS
erate to heavy nuisance conditions exist that might cause single • Operating Voltage Range: 15 to 32 VDC
sensing detectors to trigger a false alarm. • Operating Current @ 24 VDC: 200 uA (one communication every
The PTIR detector meets both UL 268 7th edition and UL 521 listing 5 seconds with green LED blink on communication)
requirements and can indicate distinct smoke and heat alarms. This • Maximum Alarm Current: 2 mA @ 24 VDC (one communication
dual nature supports a local alarm setting for photoelectric detection every 5 seconds with red LED solid on)
and a general evacuation setting based on thermal detection. This
• Maximum Current: 4.5 mA @ 24 VDC (one communication every
can minimize work interruptions in multi-level buildings. Canadian
5 seconds with amber LED solid on)
models meet listing requirements of CAN/ULC S529 and CAN/ULC
S530. • Isolator Load Rating: 0.0063
Standards
Features
The devices in this datasheet meet the standards of UL 268 7th Edi-
• Multi-criteria detection tion and CAN/ULC S529.
• UL 268 7th Edition and UL 521 Listed; Canadian models CAN/
ULC S529 and CAN/ULC S530 Agency Listings and Approvals
• New modern profile The listings and approvals below apply to the FPTI-951 Series. In
• Analog communications some cases, certain modules may not be listed by certain approval
• Low standby current agencies, or listing may be in process. Consult the factory for the lat-
• Rotary address switches est listing status.
• Dual LEDs for 360° visibility UL/ULC: S1111
• Expanded color options FM Approved
• FlashScan® protocol support on all models; FlashScan and CLIP CSFM: 7272-0028:0510
protocol support on -IV models
Specifications
PHYSICAL
• Height: 2.0" (51 mm) installed in B300(A)-6 base
• Diameter: 6.2" (156 mm) installed in B300(A)-6 base; 4.1" (104
mm) installed in B501-WHITE/-IV/-BL base
• Weight: 3.4 oz. (95 g)
• Color: White (-IV models are ivory)
• Operating Humidity Range: 15% to 90% Relative Humidity, Non-
condensing
• Operating Temperature Range: 32°F to 100°F (0°C to 38°C)
• Air Velocity: 0 to 300 ft./min. (0 to 91.4 m/min.)
203.484.7161
www.notifier.com Country of Origin: Mexico