T.7.7.6 Shrinkage Curvature: RAPT User Manual
T.7.7.6 Shrinkage Curvature: RAPT User Manual
where
εcs = Shrinkage strain modified for shape, environment and time effects. See T.7.3.5
n = Modular ratio
Es = Steel Modulus
Ee = Effective Concrete Modulus
Ss = the first moment of area of the reinforcement about the centroid of the cracked or gross
section, whichever is appropriate
It = The transformed Inertia based on Èe.
To extrapolate the method to apply to partially prestressed sections one must modify the effective inertia equation to
bring the curvature of the section back to the zero datum. We should therefore subtract the total prestress bending
moment. Readers are referred to the work by Branson and Trost (ref 32). RAPT uses the decompression bending
moment as a conservative lower bound for the total prestress bending moment as given by
The Eurocode II approach is given in EurocodeII Section A4.3. The following formula accounts for tension stiffening by
giving an effective curvature.
where
β1 = 1 for deformed reinforcement bars
= 0.5 for plain reinforcement bars
β2 = 0.5 for sustained loads.
Note: If the section is uncracked then ξ = 0, thus the Effective Curvature is set to the uncracked
curvature.
For BS8110 and SABS 0100, RAPT limits the concrete stress at the bottom layer of tension reinforcement to 1N/mm2
as defined in these codes. A section is defined as uncracked before this limit is reached and cracked once the limit is
reached. For all other codes, RAPT uses the curvatures based on gross section properties (ie uncracked) until the
applied moment causes the concrete tensile stress at the outer face to exceed the allowable concrete tensile stress as
specified by the user in Input Screen F9 (cracked condition). When the applied stress in the concrete is greater than
the tensile strength of the concrete, the tension stress in the concrete at the bottom tension steel layer is limited to
1N/mm2thus assuming that the tension stiffening effect after cracking occurs is equivalent to a tensile strength of the
concrete of 1N/mm2.
(a) Where provision is made to minimise cracking (commonly taken as when brickwork joints are spaced less than or
equal to 5000 mm)
According to AS3600 TABLE 2.4.2 NOTE 1, deflection limits given are to apply to the theoretical deflection of the line
diagram representing the idealised frame for flat slabs. This implies that it is the deflection of the full panel width prior
to the proportioning of the load to the column and the middle strips. The deflection of the full panel line diagram would
therefore be a weighted average deflection of the column and middle strip deflections. Applying the deflection limits to
the separate strips should provide conservative results as the column strip deflection would be higher than this
"average" deflection.
It is suggested that one should limit the total deflection to an absolute limit of 20 - 30 mm. This is proposed as the
limit where one may notice the deflection by visual inspection.
The designer must decide if the average deflection, or the column strip deflection or the total panel deflection is critical
in each case. It should be remembered that in many cases with brickwork on slabs, the walls are placed on column
lines. In this case the column strip deflection would be more critical.
δdiagonal = δc + δm
Figure T.7.7.5
T.8 Transfer
RAPT carries out a serviceability check for the transfer condition. The loading used to check the transfer case is
SW + PT
RAPT calculates the top and bottom fibre stresses based on gross section properties. If the stress at transfer is
greater than this limit, RAPT will carry out a cracked section analysis and add reinforcement to satisfy maximum
allowable stresses in the reinforcement. because of this, for transfer members where stage stressing is being used, it
is important that the designer investigate all stages in the construction with the relevant loads applied. The final stage
will have all tendons stressed and the structure weight at the final stressing stage included in the transfer load case
and the full loading of the building included in the ultimate and service cases.
RAPT will inform the user of the state of the member. The users attention is drawn to
• AS3600 Clause 8.1.4.2 (RAPT complies with the second paragraph of this clause only)
• BS8110 and CP65 Clause 4.3.5
• ACI318 Clause 18.4
• Eurocode2 Clause 4.2.3.5.4
• SABS0100 Clause 5.3.2.3
• CP2004 clause 12.3.5
• IS1343 clause 22.8.2
In essence there is no difference between checking at transfer and checking at working, except that at working an
ultimate design has been carried out first and there will usually be sufficient steel detailed to ensure compliance at
working.
Comments on AS3600
When the only loads acting are self-weight and transfer prestress then the usual worst case would be 0.8 times self-
weight and 1.15 times the prestress. The authors are not at this stage clear as to what the code is referring to in this
clause for the prestress bending moment. If one compares the ultimate check at transfer to the ultimate check at full
working then presumably the secondary prestress at transfer is the bending moment to be used however the factor of
1.15 then appears inappropriate as generally the secondary moment are acting in the opposite sign as applied
moments.
The method suggested by Faulkes (ref 25) is that M*t be calculated using an ultimate factor of 0.8. The internal
equilibrium of the section is then found in terms of an unknown ultimate prestress force, P u. This force is then
multiplied by the capacity reduction factor of 0.6 to give the design prestress force to cause failure at transfer, φPu.
This is then compared to an ultimate applied prestress force, P*, using an ultimate factor of 1.15.
This method is limited in that it is only easily applicable to cross-sections which have only one layer of prestressing.
A Helpful hint
If users wish they could perform a cracked section analysis on the transfer moments by using the Cross Section Design
Utility to perform a cracked section analysis on the transfer moments by inputting the transfer moments as service
moments.
The program will automatically check punching shear at every column and save the results to the output file. For edge
columns where no cantilever is present the user must define the extent of the edge of the slab with respect to the
column centre-line.[see Input F2 [Spans]] The frame is input with all span lengths and widths centred along the
centre-line of the frame. The critical shear perimeter around an edge column would, in the case where no cantilever
was input, be under-estimated if modelled to the column centre-line. For each column RAPT calculates the critical
perimeter. RAPT will calculate this perimeter for both rectangular and circular columns. In all cases RAPT will calculate
the shortest failure perimeter.
For AS3600, stirrups will automatically be nominated in the transverse direction in order to satisfy punching shear
requirements. Note that this may occur even if no transverse beam is present. The centre-line of the ties is taken as
55 mm from all faces of beams and 35 mm from all faces of slabs. The term y1 is the longest dimension of the closed
tie.
For the other codes (BS8110, SABS0100 and Eurocode II, CP3004, IS456, IS1343, ACI318) RAPT calculates shear
head reinforcement, not torsion strip reinforcement.
The output provides the design parameters that are necessary to check the RAPT calculations. The design punching
shear force at the column is the sum of the total panel span reactions on either side of the column, not simply the load
on the tributary area.
To design punching shear RAPT considers 3 load cases
Thus RAPT will take patterning effects into account from the ultimate combinations cases. The critical case for the
maximum punching shear force will generally occur for full live loading on all spans.
Note:
T.9.1 Theory: Punching Shear 1
RAPT User Manual Copyright PCDC
1. RAPT will present the results for the case which gives the worst punching shear conditions.
2. These results will include a moment transferred to the column. RAPT does not check that the column can
adequately sustain the moment transferred to it or check that the slab has adequate reinforcement to
transfer the moment to the column.
For one-way systems the total punching shear force and bending moment transferred to each column is factored up in
the ratio of the one-way width being run to the transverse average column spacing, l 2.
1. The direct shear force, V*, on the column is distributed to each of the four faces of the critical perimeter in
the direct ratio of the length of a side to the total length of the perimeter.
Therefore
V1* = (a/u) V*
= the direct shear force on a side face
a = dimension of the critical shear perimeter measured parallel to the direction of M* v
u = length of the critical shear perimeter
The ultimate direct shear strength, Vuo, of the critical perimeter is given by
where
βh = the ratio of the longest dimension of the column, y, to the shorter dimension, x, measured at right
angles
σcp = the P/A due to prestress at the column based on the full panel width
The direct shear capacity of one side face of the critical perimeter is therefore
2. The greater proportion of the bending moment transferred to the column, M v*, is taken by the faces of the
critical perimeter which are parallel to the design direction as 0.4 M v* on each side face. This is transferred to
the column in a torsional mode on the side faces.
The ultimate strength of the side face torsional member, T uc, which is the depth of the slab and of width equal
to the parallel column width, a, is given by
Combining the shear and torsion in a linear relationship the column is considered satisfactory to resist the loading if
the following is satisfied
Substituting in the formulae above we find that the maximum bending moment that may be transferred
simultaneously with the direct shear force is given by
which for the case of no bending moment being transferred to the column reduces to
If V* > φVu then one must provide closed ties in the transverse direction. The minimum requirement for the ties is that
they have a minimum cross-sectional area per spacing (A sw/s)min as given below and that they are spaced no further
apart than the minimum of the depth of the slab; or 300 mm.
where
y1 = the longest overall dimension of the closed tie
fsy.f = the yield stress of the tie
Asw = the cross-sectional area of the bar forming a closed tie (1 leg)
s = the spacing of the ties
The shear strength of the connection including the capacity of the torsional member which has minimum closed ties is
then given by
If the applied ultimate loading, V*, exceeds the design strength with minimum ties, φVu.min, then one must provide
closed ties which are greater than the minimum given above.
Setting the design ultimate capacity φVu to the applied ultimate shear force, V*
where
Db = the depth of the transverse beam
Ds = the depth of the slab. Taken as the average drop panel depth if drop panels are present
bw = the width of the beam web
Similarly if V* > φVu.min then ties greater than the minimum are required as given above.
whichever is less
where
The design shear strength for the shear stress failure zone is given by
where
u = effective length of the perimeter of the critical zone (based on 1.5 d from column)
The shear capacity vc of the failure zone is determined by the following equations (see BS8110 table 3.9)
where
but the value of fcu should not be taken as greater than 40.
where
(v - vc) should not be taken as less than 0.4 N/mm2
fyv is the characteristic strength of the shear reinforcement
Asv is the area of shear reinforcement. This reinforcement should be distributed around the column in
accordance with the code.
The code sets out the following requirements for punching shear
Vu <= φVn
where
Vn = Vc + Vs
Vc = the nominal shear strength provided by the concrete
Vs = the nominal shear strength provided by shear reinforcement.
For non prestressed slabs vc is the smallest of
(i)
where
βc is the ratio of the long side to short side of the column
(ii)
where
αs is 40 for interior columns
is 30 for edge columns
is 20 for corner columns
(iii)
where
where
b1 = width of the critical section measured in the direction of the span for which moments are
determined
b2 = width of the critical section measured perpendicular to b 1
The shear stress resulting from moment transfer by eccentricity of shear shall be assumed to vary linearly about the
centroid of the critical sections. The maximum factored shear stress can be calculated from
where
Ac = area of concrete of assumed critical area
Jc = property of assumed critical section analogous to polar moment of inertia.
RAPT has the ability to calculate Jc for rectangular or circular columns. Jc will be calculated for any portion of a circular
column at an edge.
RAPT does not calculate a value for Vs. Users can use the Vc value calculated by RAPT to decide if extra shear
reinforcement is required but the calculation of the reinforcement required is left to the designer.
To help the designer in this calculation RAPT also calculates V nmax. The following formula is used