Impluse Voltage
Impluse Voltage
CHAPTER 2
2.1 INTRODUCTION
most severe one is the Very Fast Transient Overvoltage (VFTO) which occurs
in the Gas Insulated Substations (GIS) due to switching operation or earth
faults. VFTO also occurs due to switching of vacuum circuit breakers and at
certain conditions due to lightning. The VFTO has a rise time of about 3-10 ns
with a peak magnitude of about 2.8 p.u (approximately 1000 kV for a 420 kV
substation) (Mohana Rao 2007).
1.2/50 µs 0.58/50 µs
0.09/50 µs
Figure 2.4 (b) Very fast transient (generated)
Figure 2.5 Electrode arrangement and Test cell for Solid insulation as per
ASTM D149-97a
Figure 2.6 Electrode arrangement and Test cell for gaseous and liquid
insulations as per IEC-60156
(Acrylic) having effective volume between 300 to 500 ml with adjustable and
removable electrodes.
1
Standard deviation ( (tb)) = ( ) (2.5)
1
34
1 ( )
( )= – (2.6)
2 2
Figure 2.9 v-t characteristics of air for impulse voltages with varying tf
The v-t characteristics for all tf follow the same pattern and the
characteristics are steeper for tb less than 2 µs.
The percentage shift (down) with reference to 1.2/50 µs is not uniform for
the entire region and increases with decreasing tb, (for tb less than 2 µs).
36
% tb=1.0 s tb =8.0 s
VBD
Waveshape decrease
(kV) V % V %
in VBD
(kV) decrease (kV) decrease
From Table 2.2, it is observed that, the percentage shift is almost equal
for VBD and after 2 s (17% and 40% for 0.58/50 s and 0.09/50 s
respectively) and is more (30% and 49% for 0.58/50 s and 0.09/50 s
respectively) around the knee point of the characteristics (here for less
than 2 s).
From the above discussion, it is evident that the VBD is 40% lesser
and withstand capability over the entire region of tb is almost 40-50% lesser for
air under VFTO than the standard lightning impulse voltage.
1.2/50 s 1241
0.58/50 s 1050
0.09/50 s 831
Figure 2.10 v-t characteristics of OIP for impulse voltages with varying tf
The lower time regions (for tb less than 2 µs) of v-t characteristics are
steeper and the steepness increases with decreasing tf.
38
Table 2.4 gives the percentage shift in VBD and v-t characteristics of
OIP for decreasing tf.
tb=1.0 s tb =8.0 s
%
VBD
Waveshape decrease
(kV)
in VBD V % %
V (kV)
(kV) decrease decrease
It is observed from the table, that, the percentage shift is almost equal
for VBD and after 2 s (15% and 33% for 0.58/50 s and 0.09/50 s
respectively) and is more around the knee point of the characteristics as in the
case of air (here for less than 2 s).
From the above results, it is found that the VBD is 33% lesser and
withstand capability is almost 33-50% lesser for OIP under VFTO than the
standard lightning impulse voltage.
= + (2.7)
The VBD and the Hyperbolic parameters for air are plotted against tf
and are shown in Figure 2.11.
40
The Table 2.5 and Figure 2.11 show that the Hyperbolic model
parameters which are proportional to maximum voltage withstood by the
insulation and are increasing with increasing tf. With reference to 1.2/50 s, A
reduces by 15% and 37% and B reduces by 42% and 64% for 0.58/50 s and
0.09/50 s respectively.
The values of VBD and the Hyperbolic model parameters for OIP are
plotted with respect to tf and are shown in Figure 2.12.
41
2.7.3 Prediction
In order to validate the Hyperbolic model for both the insulations (air
and OIP), a non-oscillatory test waveform of 0.8/50 µs is considered. The
parameters are taken (predicted) for tf of 0.8 µs from Figures 2.11 and 2.12 for
air and OIP respectively.
42
The v-t characteristics are experimentally obtained for air with an air
gap of 1.0 cm and OIP of thickness 0.25 mm with the same electrode
configurations and the hyperbolic model parameters are extracted. Thus
extracted parameters are compared with the predicted parameters (obtained
from Figure 2.11 and Figure 2.12) and the percentage errors are shown in Table
2.7.
Table 2.7 Hyperbolic model parameters for 0.8/50µs impulse
Hyperbolic
Insulation model Predicted Experimental % Error
parameters
The Table 2.7 shows that the percentage errors between the predicted
and experimental parameters are less than 4%. This shows that the prediction of
43
v-t characteristics for the given insulation under standard overvoltages (without
oscillation) is possible with Hyperbolic model.
The Hyperbolic model parameters are taken for tf of 0.46 µs for air
(A=26 kV & B=14 kV- µs) and OIP (A=24.1 kV & B=8.8 kV-µs) from Figures
2.11 and 2.12 respectively. Using these parameters, tb is predicted for a set of
voltage magnitudes. The generated overvoltage as shown in Figure 2.14 is
applied on air and OIP for the same set of voltage magnitudes and the
corresponding tb are experimentally obtained.
tb ( s)
Insulation V (kV) % Error
Predicted Experimental
2.8 CONCLUSION
The following conclusions are derived from the above mentioned analysis:
VBD decreases with decreasing tf and the decrease of VBD is not linear with
respect to tf.
The v-t characteristics shift down with decreasing tf and the shift is
maximum for tb less than 2 s and almost same for tb greater than 2 s.
Hyperbolic Model
v-t characteristics are modeled using Hyperbolic model. From the model
parameters, the v-t characteristic for any intermediate tf can be predicted
and verified experimentally.