0% found this document useful (0 votes)
170 views15 pages

Dassault Systemes Project - HVAC - IO Summary

This document contains two data point summaries listing HVAC equipment for two towers, Tower A and Tower B. It includes items such as exhaust fans, fresh air fans, lift pressurization fans, and environmental sensors. For each item it lists quantities, monitoring points including on/off status, and control capabilities such as starting and stopping fans. It also lists the potential free contacts and relay outputs that would be used for integration.

Uploaded by

Shruti Nand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
170 views15 pages

Dassault Systemes Project - HVAC - IO Summary

This document contains two data point summaries listing HVAC equipment for two towers, Tower A and Tower B. It includes items such as exhaust fans, fresh air fans, lift pressurization fans, and environmental sensors. For each item it lists quantities, monitoring points including on/off status, and control capabilities such as starting and stopping fans. It also lists the potential free contacts and relay outputs that would be used for integration.

Uploaded by

Shruti Nand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 15

DATA POINT SUMMARY (HARD POINT)

SR. NO. ITEM QTY

TOWER-A
A LMR FLOOR ( BASE BUILDER )

1 Toilet EX-haust FAN ( base-Builder) 1W+1S 2

2 Pantry EX-haust FAN ( base-Builder) 1W+1S 2

3 Lift Pressrization FAN (Base Builder) 6

3 Staircase Pressrization FAN (Base Builder) 5


MONITO

ALARM
CONTR
FUNCTION AI DI AO DO

OL
R
Monitor
On/Off Status 2 X
Auto Manual Switch Status 2 X
Trip status 2 X X
Control
Fan Start/Stop 2 X

Monitor
On/Off Status 2 X
Auto Manual Switch Status 2 X
Trip status 2 X X
Control
Fan Start/Stop 2 X

Monitor
On/Off Status 6 X
Auto Manual Switch Status 6 X
Trip status 6 X X
Fire panel I/P 6 X XX
Control
Fan Start/Stop 6 X

Monitor
On/Off Status 5 X
Auto Manual Switch Status 5 X
Trip status 5 X X
Fire panel I/P 5 X XX
Control
Fan Start/Stop 5 X
EQUIPMENT TO BE USED

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact
Through the control module in FAS

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact
Through the control module in FAS

Relay Output
DATA POINT SUMMARY (HARD POINT)

SR. NO. ITEM QTY

TOWER-B
A LG-2 FLOOR
1 EXHAUST FAN (Base-Builder) 1

B LG-1 FLOOR
1 FRESH AIR FAN (Base-Builder) 5

2 STAIRCASE PRESS. FAN AIR FAN (Base-Builder) 2

C TERRRACE FLOOR
1 FRESH AIR FAN 5

2 KITCHEN FAN 1

D LMR FLOOR ( BASE BUILDER )

1 Toilet EX-haust FAN ( base-Builder) 1W+1S 2

2 Pantry EX-haust FAN ( base-Builder) 1W+1S 2


3 Lift Pressrization FAN (Base Builder) 6

7 Staircase Pressrization FAN (Base Builder) 5

8 ENVIRONMENTAL CONDITION 1
Outside Air
MONITO

ALARM
CONTR
FUNCTION AI DI AO DO

OL
R
Monitor
On/Off Status 1 X
Auto Manual Switch Status 1 X
Trip status 1 X X
Control
Fan Start/Stop 1 X

Monitor
On/Off Status 5 X
Auto Manual Switch Status 5 X
Trip status 5 X X
Control
Fan Start/Stop 5 X

Monitor

On/Off Status 2 X
Auto Manual Switch Status 2 X
Trip status 2 X X
Fire panel I/P 2 X XX
Control
Fan Start/Stop 2 X

Monitor
On/Off Status 5 X
Auto Manual Switch Status 5 X
Trip status 5 X X
Control
Fan Start/Stop 5 X

Monitor
On/Off Status 1 X
Auto Manual Switch Status 1 X
Trip status 1 X X
Control
Fan Start/Stop 1 X

Monitor
On/Off Status 2 X
Auto Manual Switch Status 2 X
Trip status 2 X X
Control
Fan Start/Stop 2 X

Monitor
On/Off Status 2 X
Auto Manual Switch Status 2 X
Trip status 2 X X
Control
Fan Start/Stop 2 X
Monitor
On/Off Status 6 X
Auto Manual Switch Status 6 X
Trip status 6 X X
Fire panel I/P 6 X XX
Control
Fan Start/Stop 6 X

Monitor
On/Off Status 5 X
Auto Manual Switch Status 5 X
Trip status 5 X X
Fire panel I/P 5 X XX
Control
Fan Start/Stop 5 X

Monitor
Room temperature & Humidity 2 X X
EQUIPMENT TO BE USED

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact
Through the control module in FAS

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact

Relay Output
Pot. Free contact
Pot. Free contact
Pot. Free contact
Through the control module in FAS

Relay Output

Pot. Free contact


Pot. Free contact
Pot. Free contact
Through the control module in FAS

Relay Output

Temp.cum humidity sensor


HVAC SYSTEM
DATA POINT SUMMARY (SOFT POINT)
AI AO DI DO Soft

A C  HILLER PLANT  WATER COOLED CHILLER - HVAC PLANT ROOM 4


M  ANAGER
1 CPM Chiller On/Off Command 4
2 CPM Chiller Auto/Manual status 4
3 CPM Chiller On/Off Status 4
4 CPM Chiller Trip Status 4
5 CPM Common Supply Header Temperature 4
6 CPM Common return Header Temperature 4
7 CPM Common Condenser Inlet Temperature 4
8 CPM Common Condenser Outlet Temperature 4
9 CPM Common Supply Header Pressure 4
10 CPM Common return Header Pressure 4
11 CPM Chiller Evaporator Isolation Valve On/Off Status 4
12 CPM Chiller Condenser Isolation Valve On/Off Status 4
13 CPM Flow switch on Supply Header 4
14 CPM Chiller's VFD Command 4
15 CPM Chiller's VFD Bypass Status 4
16 CPM Chiller's VFD Speed Feedback 4
17 CPM Chiller's VFD Frequency 4
18 CPM Chiller's VFD Current 4
19 CPM Chiller's VFD Voltage 4
20 CPM Chiller's VFD Power 4
21 CPM Chiller's VFD Run Time 4
22 CPM Condenser inlet Pressure 4
23 CPM Condenser outlet Pressure 4
24 CPM Compressor Suction Pressure 4
25 CPM Compressor Discharge Pressure 4
26 CPM Compressor Current Feedback 4
27 CPM Compressor Power Feedback 4
28 CPM IKW/Tr (Calculated by BMS Software) 4
29 CPM Compressor Loading Status 4
30 CPM individual chiller Supply Header Temp 4
31 CPM individual chiller return Header Temp 4
32 CPM individual chiller Condenser Inlet Temp 4
33 CPM individual chiller Condenser Outlet Temp 4
34 CPM Condenser Pump Auto/Manual Status 4
35 CPM Condenser Pump Trip Status 4 4
36 CPM Condenser Pump On/Off Status 4
37 CPM Condenser Pump On/Off Command 4
38 CPM Cooling Tower Fan On/Off Status 4 4
39 CPM Cooling tower fan Trip Status 4
40 CPM cooling tower Fan Auto/Manual Status 4
41 CPM cooling tower Fan On/off Command 4
42 CPM Cooling Tower Isolation Valve On/Off Status 4
43 CPM Cooling Tower Isolation Valve On/Off Command 4
44 CPM Cooling TowerVFD Command 4
45 CPM Cooling TowerVFD Bypass Status 4
46 CPM Cooling Tower VFD Speed control 4
47 CPM Outside Air Temperature Monitoring 4
48 CPM Outside Air Relative Humidity monitoring 4
49 CPM Ambient CO2 level 4
50 CPM Primary Pump On/Off Status 4 4
51 CPM Primary Pump Trip Status 4
52 CPM Primary Pump Auto/Manual Status 4
53 CPM Primary Pump on/Off Command 4
54 CPM Secondary Pump On/Off Status 6 6
55 CPM Secondary Pump Trip Status 6
56 CPM Secondary Pump Auto/Manual Status 6
57 CPM Secondary Pump Run Status 6
58 CPM Secondary Pump's VFD Bypass Status 6
59 CPM Pressure Sensor for pump load estimation 6

AHU @ Second Floor Tower-A 4


AHU @ Third Floor Tower-A 4
AHU @ LG1 Floor Tower-B 5
AHU @ Podium Level Tower-B 5
B AHU @ First Floor Tower-B 4
AHU @ Second Floor Tower-B 4
AHU @ Third Floor Tower-B 4
AHU @ Fourth Floor Tower-B 4
AHU @ Fifth Floor Tower-B 4
1 AHU Air Inlet Temp 38
2 AHU Air Outlet temp 38
3 AHU Water Inlet Temp 38
4 AHU Water Outlet Temp 38
5 AHU Air Flow Volume 38
6 AHU KW Consumpton 38
7 AHU CO2/VOC ppm 38
8 AHU CHW Valve status 38
9 AHU EC FAN Status 38
10 AHU Pressure Control 38
11 AHU A/M VFD Control 38
12 AHU Common Alram 38
13 AHU Filter Status 38
12 AHU ON/Off Status 38
EQUIPMENT TO BE USED

Integration through MODBUS/BACnet protocol for


monitoring & controlling parameters.Through Intergrator

Tower-A Future AHU for other floors not considered

Integration through MODBUS/BACnet protocol for


monitoring & controlling parameters.Through Intergrator
Integration through MODBUS/BACnet protocol for
monitoring & controlling parameters.Through Intergrator
HVAC SYSTEM
DATA POINT SUMMARY (SOFT POINT)
AI AO DI DO Soft

VAV @ Second Floor Tower-A 77


VAV @ Third Floor Tower-A 83
VAV @ Podium Level Tower-B 35
VAV @ First Floor Tower-B 74
C
VAV @ Second Floor Tower-B 73
VAV @ Third Floor Tower-B 68
VAV @ Fourth Floor Tower-B 72
VAV @ Fifth Floor Tower-B 56
1 VAV VAV Zone Temperature Set Point & Control 538
2 VAV VAV Zone Temperature 538
3 VAV VAV Damper opening 538
4 VAV Pressure across VAV unit 538
5 VAV VAV Actuator Vmax Set Value 538
6 VAV VAV Actuator Vmin Set Value 538
7 VAV VAV Actual Flow Rate of Actuator 538
8 VAV VAV Actuator Warning Signal 538
9 VAV VAV Modulating signal(2-10v) Output in % 538
10 VAV VAV Economy/Normal Mode Status 538

PAC UNIT @ Terrace Floor Tower-B 2

Unit command (on/off) 2

unit status (on/off) 2


fan status (on/off) 2
fan failure alarm 2
fan Overload 2
Cooling on 2
filter clogged alarm 2
return air temperature 2
supply air temperature 2
return air humidity 2
heater status (on/off) 2
F 2
humidifier status (on/off)
Humidity setpoint (room air) reading 2
compressors (on/off) or % Load 2
compressors failure alarms 2
Common Fault alarm 2
Power failure 2
Service alarm 2
Machine failure 2
Wellness/Maintenance alarm 2
Control circuit trip 2
Low /high chilled water temperatures Alarm 2
Water leak detection alarm 2
Fire Trip 2

G CASSETTE @ Second Floor Tower-A 22


CASSETTE @ Third Floor Tower-A 22
CASSETTE @ Ground Floor Tower-B 32
CASSETTE @ First Floor Tower-B 16
CASSETTE @ Second Floor Tower-B 16
CASSETTE @ Third Floor Tower-B 22
CASSETTE @ Fourth Floor Tower-B 22
CASSETTE @ Fifth Floor Tower-B 16
1680

VRF ODU @ Terrace Floor Tower-A 14


VRF ODU @ Terrace Floor Tower-B 14
On/Off Status 28
H Malfunction Status 28
Compressor Status 28
PPD Data 28

PAC ODU @ Terrace Floor Tower-B 2


On/Off Status 2
Malfunction Status 2
I
Compressor Status 2
PPD Data 2

Total 8008
EQUIPMENT TO BE USED

Tower-A Future AHU for other floors not considered

Integration through MODBUS/BACnet protocol for


monitoring & controlling parameters.Through Intergrator

Integration through MODBUS/BACnet protocol for


monitoring & controlling parameters.Through Intergrator

Tower-A Future AHU for other floors not considered

10 Points per Cassette Unit

Integration through MODBUS/BACnet protocol for


monitoring & controlling parameters.Through Intergrator

Integration through MODBUS/BACnet protocol for


monitoring & controlling parameters.Through Intergrator

You might also like