Micom P114D: Numerical CT and Auxiliary Voltage Powered Overcurrent Relays With Easy Setting
Micom P114D: Numerical CT and Auxiliary Voltage Powered Overcurrent Relays With Easy Setting
MiCOM P114D
Numerical CT and auxiliary voltage
powered overcurrent relays
with easy setting
AREVA T&D
APPLICATION GLOBAL FUNCTIONS
The MiCOM P114D numerical overcurrent protection The power supply to the electronic circuits of the
relay provides a simple and cost efficient solution MiCOM P114D has been optimised so that it can trip
where no external auxiliary power supply is available or the circuit-breaker with a load current of 0.2 In on at
guaranteed. least one phase.
The following features are generally available in the
Typical applications are: MiCOM P114D:
> A cost optimized MV switchboard with small > CT powered
dimensions > DIP switches for settings
> HV back up protection (HV/MV transformers) > Two types of case (HxWxD): flush panel
> Utility and industrial substations (183x160x107) or wall (203x138x95) mounting
> Retrofit of old technology relays > Settings referred to nominal current
FUNCTIONS OVERVIEW
ANSI FEATURES
FUNCTIONAL OVERVIEW
Local Remote
communication communication
I
Binary Input L2
Binary Input L1
MiCOM P114D
provides optimized solutions for small spaces
> I/O Configuration AREVA TRACK RECORD - SIMPLE OVERCURRENT
All protection settings are available using DIP and EARTH FAULT PROTECTION
switches only. Two pre-defined input/output >> Px1x family of simple overcurrent relays - P111, P114S, P114D, P115.
configurations can be selected using DIP switches or
>> MiCOM P111: First released Dec 2001. Over 6000 devices installed.
a customised configuration can be selected using
>> MiCOM P114/5: First released 2008.
the setting software. The DIP switches on the front
panel are a simple and visual way of setting the
relay's configuration without the need for additional
equipment. The setting software allows every input
and output to be freely configured to available
functions, such as blocking of protection elements,
> Fault Recording
resetting LEDs or outputs, starting, and tripping of
every protection element. This allows inputs and The last five faults are stored in non-volatile FRAM
outputs to be configured for specific applications. memory.
AUTOMATION-L3-P114D-BR-05.08-1845-GB - © - AREVA - 2008. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademark of AREVA.
Opto isolated digital inputs can be configured for a 100 logic events are stored in non-volatile FRAM
Remote Trip function which allows a circuit breaker to memory. All events are time stamped to 1 ms.
be opened using the MiCOM P114D with signalling.
This function works if powering of the relay is
guaranteed. > MiCOM S1 Studio Support Software
Support Software MiCOM S1 Studio is available for
the entire MiCOM family, including P114D relays.
> Blocking and Selective Scheme Logic
MiCOM S1 Studio is fully Windows TM compatible.
The scheme logic depends on the input/output
All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
configuration: This support software allows the readout of settings,
• DIP switch I/O configuration: L1 input can be used configuration of inputs/outputs, download of fault
to block I>> stage records and event records.
• Setting software configuration: logic inputs can be PC connection with the P114D is available via a
freely configured to block any selected protection USB port on the front panel of relay or rear RS485
stages. port (Modbus)