0% found this document useful (0 votes)
298 views

LPD and Lux Minimum Values

The document provides a table categorizing different types of interior spaces and the recommended lighting power density (LPD) and illuminance for each space type. It lists space types such as offices, meeting rooms, classrooms, laboratories, food preparation areas, circulation areas, hotel rooms, retail spaces, and manufacturing areas. The LPD ranges from 3 to 16 watts per square meter and the illuminance ranges from 75 to 1000 lux depending on the specific needs of the space.

Uploaded by

aisha nakato
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
298 views

LPD and Lux Minimum Values

The document provides a table categorizing different types of interior spaces and the recommended lighting power density (LPD) and illuminance for each space type. It lists space types such as offices, meeting rooms, classrooms, laboratories, food preparation areas, circulation areas, hotel rooms, retail spaces, and manufacturing areas. The LPD ranges from 3 to 16 watts per square meter and the illuminance ranges from 75 to 1000 lux depending on the specific needs of the space.

Uploaded by

aisha nakato
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Type of Usage Interior Space

Office, meeting rooms, copy/ print rooms, class rooms


Office, work and
Lecture theatres, computer rooms, reading areas
study
Laboratories

Food courts, canteens (inc. dining areas and food preparation)


Food and relax
Restaurants, lounges, bars (inc dining areas and food
preparation, accent, display)
Circulation areas, corridors and ware houses
Stairs, escalators, travellators
Transport and goods Car parks
Loading docks
Storage areas
Hotel guest rooms
Rest, clean, exercise,
Toilets, changing rooms, laundries, washing areas
play areas
Gymnasiums and physical exercise areas
Entrance halls, atriums, concourses, lobbies, auditoriums and
concert halls
Multipurpose halls

Atrium, halls and Jewelry and crystal


retail Retail, general
lighting, and Furniture, clothing and accessories,
(accent, display, cosmetics, artwork
decorative)
Others (e.g. supermarket, vehicles, etc.)

Mechanical and electrical room


Manufacturing and
Manufacuring - Low to extra high bays
maintenance
Manufacturing - electronic and fine detail
Illuminance
LPD (W/m2)
(lux)
12 300
12 500
16 500

10 200

12 200

7 100
6 150
3 75
5 150
10 100
12 200
10 100
11 300

10 200

16 300

15 (+20) 1000

15 (+10) 750

15 (+5) 500

10 200
13 500
14 500