1.tbe1 Fire Pump

The document is a technical bid evaluation sheet for main fire water pumps. It contains requirements for the pumps such as operating conditions, performance parameters, codes and standards to be complied with. The bidder is to fill in responses and clarifications in the columns provided and attach any documents. It evaluates the bid response for items like pump type, capacity, design conditions, power requirement and compliance to the request for quotation.

Uploaded by

vinoj chandran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
233 views11 pages

1.tbe1 Fire Pump

The document is a technical bid evaluation sheet for main fire water pumps. It contains requirements for the pumps such as operating conditions, performance parameters, codes and standards to be complied with. The bidder is to fill in responses and clarifications in the columns provided and attach any documents. It evaluates the bid response for items like pump type, capacity, design conditions, power requirement and compliance to the request for quotation.

Uploaded by

vinoj chandran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 11

DOC.

NO: T-25-2018-00-ME-TBE-1064
TECHNICAL BID EVALUATION SHEET REV. NO.: 0

MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C) REQ'N N: T-25-2018-00-ME-REQ-1053

BIDDER BIDDER
DESCRIPTION REQ'N REQUIREMENT CLARIFICATIONS VENDOR TO FILL IN & ATTACH WITH TECHNICAL QUERY - 2
VENDOR TO FILL IN & ATTACH WITH OFFER
OFFER

A. GENERAL:

1) PUMP TYPE AXIALLY SPLIT HORIZONTAL CENTRIFUGAL PUMP Comply with Horizontal Split Case Type Complied - Closed

Comply & Noted. Sequence of Operation Based on the Pressure Settings


2) NO. REQ'D WORKING 2, STAND-BY 1 Complied - Closed
& Installation Contrcator Scope of Work

3) MANUFACTURER SIZE / MODEL VTA SFP 2000-29SM-2G Noted SFP 2000-29SM-2G Closed

4) DESIGN CODE API 610/ NFPA 20/ UL 1247 ANSI/UL 448 Noted - Closed

5) TABLE OF COMPLIANCE TO RFQ REQUIRED Comply Complied - Closed

6) FILLED IN PUMP DATASHEET REQUIRED Comply Complied - Closed

7) LOCATION OF PUMP INDOOR Comply Complied - Closed

8) OPERATION INTERMITTENT Comply Complied - Closed

9) PERFORMANCE AND TESTING CODE VTA Comply With UL Testing Standards Noted Closed

10) OPERATE IN SERIES OR PARALLEL PARALLEL Comply Complied Closed

THE PUMPS OFFERED ARE SUITABLE TO OPERATE IN


11) YES Comply Complied Closed
PARALLEL THROUGHOUT THE RANGE

B. OPERATING COND. & PERFORMANCE:

1) PUMPED FLUID FIRE WATER (FRESH WATER/SALT WATER) Fresh Water Complied. Vendot to provide compliance for Sea water. Complied. Vendor to provide compliance for sea water.

2) DESIGN TEMPERATURE ℃ 5/82 50 Deg. Ambient Temperature Noted Closed

3) FLUID DENSITY Kg/m3 1000 Comply Complied Closed

4) SUCTION PRESSURE max / min kPa 362.75 / 88.23 Comply with 9 Bar Noted Noted

5) DISCHARGE PRESSURE kPa VTA Comply with 9 Bar Noted Noted

6) DIFF. HEAD. @ DUTY POINT m 120 9 bar (91.80 m head) Noted Noted

7) FLOW RATED m3 /hr 454 Comply Complied Closed

8) MIN, CONTINUOUS FLOW m3 /hr VTA Comply with 454 m³/hr Complied Closed

9) EFFICIENCY @ RATED POINT % VTA 62.40% Complied Closed

10) BHP @ RATED POINT kW VTA 256HP Noted Noted

11) MAX. POWER @ RATED IMPELLER kW VTA 256HP Noted Noted

Not Clear for EOC with Water Point. Kindly advise for the Exact
12) DRIVER SIZED FOR EOC WITH WATER REQUIRED Vendor to size the driver for water -
Requirement.

13) SPEED rpm VTA 2900 rpm Noted Noted

14) SUCTION SPECIFIC SPEED LIMIT rpm VTA 2900 rpm Noted Noted

15) NPSH (1) NPSH available m 8.72 Noted Vendor to confirm compliance Vendor to confirm compliance

(2) NPSH required m VTA NPSH Required for Propose Pump 4.2mtr Noted Vendor to confirm compliance

16) NPSHav - NPSHre m >1 Comply Complied Complied

17) NPSH @ EOC/150% flow < NPSH available m VTA Comply with 4.2mtr Noted Vendor to confirm compliance

18) RATED IMPELLER DIA. mm VTA 279 mm Noted Complied

19) MAX. / MIN. IMPELLER DIA. mm VTA 300/240 mm Vendor to provide performance curve for impeller diameter Vendor to provide performance curve for impeller diameter

20) MAX. HEAD @ RATED IMPELLER m VTA 11.24 bar @ 300mm dia Vendor to provide performance curve for impeller diameter Vendor to provide performance curve for impeller diameter

21) HEAD OF MAX. IMPELLER DIA. @ RATED FLOW m VTA 11.24 bar @ 300mm dia @ 2000GPM Vendor to provide performance curve for impeller diameter Vendor to provide performance curve for impeller diameter
DOC. NO: T-25-2018-00-ME-TBE-1064
TECHNICAL BID EVALUATION SHEET REV. NO.: 0

MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C) REQ'N N: T-25-2018-00-ME-REQ-1053

BIDDER BIDDER
DESCRIPTION REQ'N REQUIREMENT CLARIFICATIONS VENDOR TO FILL IN & ATTACH WITH TECHNICAL QUERY - 2
VENDOR TO FILL IN & ATTACH WITH OFFER
OFFER

22) HEAD RISE TO SHUTOFF / SHUT OFF PRESSURE % VTA 9.35 bar Noted Noted

23) CAPACITY AT THE END OF CURVE m3 /hr VTA 4400 GPM Noted Noted

24) RATED FLOW AS PERCENTAGE OF B.E.P FLOW % VTA 239.52 HP Noted Noted

25) MAXIMUM ALLOWABLE WORKING PRESSURE kPa VTA 250PSI Noted 1723kPa Vendor to confirm compliance

26) EQUIPMENT SUITABLE FOR BLACK BULB TEMP. VTA Proposed Pump 50Deg. Ambient Temperature Noted Complied

27) TEMPERATURE OF LIQUID ℃ 15 / 40 / 50 50Deg. Ambient Temperature Noted Complied

28) SHUT OF HEAD VTA 9.35Bar Noted Complied

29) SPECIFIC GRAVITY OF LIQUID @ 15℃ 0.992 Comply Complied closed

30) TYPE OF SUCTION DOUBLE SUCTION TYPE Comply Complied Closed

31) PUMP BHP VTA 256HP Noted Noted

32) RATED HEAD mWC VTA 9 bar Noted Noted

33) POSITION OF DISCHARGE VALVE AT PUMP STARTING OPEN ( STANDBY PUMP IS IN PARALLEL POSITION) Comply Complied Closed

34) NPSH REQUIRED AT RUNOUT CONDITION mWC VTA 4.5mtr Noted Vendor to confirm compliance

35) PUMP SHAFT INPUT POWER AT RATED FLOW kw VTA 239.52 HP Noted Closed

C. CONSTRUCTION:

1) CASING (1) TYPE AXIALLY SPLIT Comply Complied Closed

(2) MOUNTING FOOT MOUNTED Comply Complied Wall mounting Vendor to Confirm compliance for Foot mounting type

2) SUCTION NOZZLE (1) SIZE VTA Comply with 8 Inch Dia Noted Noted

(2) RATING : VTA ANSI B16.1 Class 250 Vendor to provide ASME B16.5 Vendor to confirm complaince for ASME B16.5

(3) POSITION SIDE SUCTION Comply Complied Closed

3) DISCHARGE NOZZLE (1) SIZE : VTA Comply with 6 inch Dia Noted Noted

(2) RATING : VTA ANSI B16.1 Class 250 Vendor to provide ASME B16.5 Vendor to confirm complaince for ASME B16.5

(3) POSITION SIDE DISCHARGE Comply Complied Closed

4) CASING DRAIN SIZE & RATING VTA 3/4inch dia Noted Noted

5) CASING VENT SELF VENTING Comply Complied Closed

6) SEAL TYPE GLAND PACKING Comply Complied Closed

Vendor to confirm compliance for type of bearing for efficient


7) BEARING TYPE (1) RADIAL BEARING VTA Comply with Roller Bearing Vendor to confirm compliance for type of bearing for efficient operation
operation

Vendor to confirm compliance for type of bearing for efficient


(2) THRUST BEARING VTA Comply with Roller Bearing Vendor to confirm compliance for type of bearing for efficient operation
operation

8) COUPLING (1) TYPE FLEXIBLE METALLIC DISC SPACER COUPLING Comply Complied Closed

(2) MFR. VTA Comply with Rigid Flexible Coupling Complied Vendor to clarify the type of coupling for efficient operation

(3) SERVICE FACTOR 1.5 1.15 Vendor to provide a service factor of 1.5 Vendor to provide a service factor of 1.5

9) BASE PLATE SLOPING DRIP PAN Comply Complied Closed

10) TYPE OF IMPELLER ENCLOSED IMPELLER (CAST IN ONE PIECE) Closed impellar Type Noted Closed

11) DRIVE TYPE DIESEL ENGINE Comply Complied Closed

12) FLANGE DRILLING (SUCTION & DISCHARGE) ASME B 16.5 ANSI B 16.1 Vendor to provide ASME B 16.5 Vendor to confirm complaince for ASME B 16.5
DOC. NO: T-25-2018-00-ME-TBE-1064
TECHNICAL BID EVALUATION SHEET REV. NO.: 0

MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C) REQ'N N: T-25-2018-00-ME-REQ-1053

BIDDER BIDDER
DESCRIPTION REQ'N REQUIREMENT CLARIFICATIONS VENDOR TO FILL IN & ATTACH WITH TECHNICAL QUERY - 2
VENDOR TO FILL IN & ATTACH WITH OFFER
OFFER

13) BEARING LIFE VTA 5 years Noted Noted

14) SIZE OF BASE PLATE VTA Will be provide After Fire Pump Assembled Noted Noted

15) PERFORMANCE / FAMILY CURVE ENCLOSED YES Comply Complied Noted

STUFFING BOX ( MECHANICAL SEAL) DESIGN OF GLAN


16) ASSEMBLY SHALL BE SUITABLE FOR MENTIONED RAW VTA Comply with Packing Gland Noted Noted
WATER QUALITY

17) GASKET VTA Comply Vendor to provide gasket Vendor to include gasket in their scope of supply

D. MATERIAL:

1) CASING CAST IRON Cast Iron Complied Closed

As per spec, impeller material is SS. But vendor to confirm the


As per spec, Casing material is SS. But vendor to confirm the suitablitity of
2) IMPELLER SS Bronze suitablitity of bronze impeller over SS impeller for fresh water Bronze Impeller
bronze impeller over SS impeller for fresh water application
application

3) SHAFT SS Alloy Steel Vendor to provide shaft material as SS Vendor to confirm compliance for shaft material as SS

4) SHAFT SLEEVE VTA Comply with SS304 Noted Closed

As per spec, Casing material is SS. But vendor to confirm the


As per spec, Casing material is SS. But vendor to confirm the suitablitity of
5) WEAR RING 1) CASING VTA Brass suitablitity of bronze impeller over SS impeller for fresh water
bronze impeller over SS impeller for fresh water application
application

As per spec, impeller material is SS. But vendor to confirm the


As per spec, impeller material is SS. But vendor to confirm the suitablitity of
2) IMPELLER VTA Bronze suitablitity of bronze impeller over SS impeller for fresh water
bronze impeller over SS impeller for fresh water application
application

6) COUPLING GUARD REQUIRED Comply Complied Closed

7) SHAFT DIAMETER VTA Comply with 3" dia Noted Noted

8) BASE PLATE SS 316 Comply with Mild Steel Noted Noted

E.DIESEL ENGINE

1) MAKE VTA BLACK STALLION-UAE Noted Noted

2)APPLICABLE STANDARDS NFPA 20/ UL 1247 NFPA20 & UL1247 Complied Closed

3) ENGINE GROSS POWER VTA 259/271.5HP Noted Noted

4.) ENGINE NET POWER (RATED CONTINOUS OUTPUT) VTA 240HP Noted Closed

5) ENGINE OVERLOAD CAPACITY( OUTPUT) FOR ONE HOUR VTA 256HP Noted Closed

6) ENGINE STARTER MOTOR VTA 24Volt Noted Closed

7)FAULTS LEADING TO AUTOMATIC DIESEL ENGINE SHUTDOWN VTA Comply Complied Closed

8) ENGINE INSTRUMENT PIPE VTA Comply Complied Closed

9)SILENCER WITH EXHAUST REQUIRED Noted With Installation Contractor Scope of Work Complied Closed

10) AIR FILTER 2 STAGE FILTER AND SILENCER Comply Complied Closed

11) DAY TANK FOR 6 Hrs CAPACITY VTA Comply with 8hrs asper NFPA20 Requirement Complied Closed

12) DAY TANK MATERIAL VTA Comply with Carbon Steel Noted Noted

13)MAIN OIL STORAGE TANK TO BE WITH MAGNETIC OIL GAUGE VTA Comply with Fuel Level Indicator vendor to confirm complaince for magnetic oil gauge Vendor to Confirm compliance of Magnetic Oil gauge

14)RADIATOR VTA Comply with Heat Exchanger Type Noted Noted

15) TYPE OF LUBRICATION LUBE OIL Comply Complied Closed

16)LUBRICATION OIL CONSUMPTION(Maximum) VTA 37.5Gallon Consumption per Hour Noted Noted

17)FUEL CONSUMPTION UNDER N.T.P VTA 37.5Gallon Consumption per Hour Noted Noted

18) 100% LOAD VTA 300 Gallon per 8 Hours Noted Noted
DOC. NO: T-25-2018-00-ME-TBE-1064
TECHNICAL BID EVALUATION SHEET REV. NO.: 0

MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C) REQ'N N: T-25-2018-00-ME-REQ-1053

BIDDER BIDDER
DESCRIPTION REQ'N REQUIREMENT CLARIFICATIONS VENDOR TO FILL IN & ATTACH WITH TECHNICAL QUERY - 2
VENDOR TO FILL IN & ATTACH WITH OFFER
OFFER

19) ENGINE SPEED VTA 2900RPM Noted Closed

20)CRITICAL SPEED OF SHAFT VTA 2900RPM Noted Closed

21) METHOD OF ENGINE COOLING JACKET WATER-COOLING (RADIATOR) Comply with Heat Exchanger Type Noted Noted

22)EXHAUST OUTLET DIAMETER VTA Noted With Installation Contractor Scope of Work Noted Noted

23) EXHAUST FLOW ( TOTAL) VTA 8.76KPA Noted Noted

15 meters of exhaust piping (straight length) shall be included


Vendor to confirm 15meters of exhaust piping with supports in their scope
24)EXHAUST STACK HEIGHT m 15 Based on the Site Condition in Vendor’s scope of supply along
of supply
with the supports

noted and 15 meters of exhaust piping (straight length) shall


Vendor to confirm 15meters of exhaust piping with supports in their scope
25) EXHAUST PIPE VTA Min. 6" dia (We considered 10mtr pipe lenth & 3nos 90Deg.Elbow) be included in Vendor’s scope of supply along
of supply
with the supports

26)INSULATION WITH CLADDING VTA Noted With Installation Contractor Scope of Work Noted Complied

27)AIR ASPIRATON VTA Comply with TurboCharged Noted Closed

28)NUMBER OF CYLINDERS VTA 6 Noted Noted

29)EFFICIENCY VTA 62.40% Noted Closed

30)BASE FRAME SKID MOUNTED (PUMP & ENGINE) Will be provide After Fire Pump Assembled Noted Noted

F. STARTING BATTERY

1)RATED VOLTAGE VTA 24V Noted Noted

2)TYPE OF BATTERY VTA Lead Calcium Battery Noted Noted

3)BATTERY CAPACITY AT 25 ° C VTA 12V Amps Noted Noted

4)NUMBER OF PERMISSIBLE START PER HOUR OF DIESEL ENGINE VTA 24Volts/7HRS Noted Noted

G. BATTERY CHARGER

1)TYPE/DESIGNATION VTA 24 Volts x 45 Amps with belt guard Noted Noted

2)VOLTAGE RATING VTA 220V Noted Noted

H. DIESEL ENGINE AUXILLARIES

1)POWER REQUIRMENTS (APPROX) VTA Comply with 150% Rated power Noted Closed

2)COOLING FAN MOTOR VTA Turbo Charged Noted Noted

3)FUEL OIL TRANSFER PUMP( IF APPLICABLE) VTA Bosch in-line “P” type Noted NOted

4)TOTAL POWER REQUIRMENTS FOR COMPLETE SYSTEM 0 259HP Noted Noted

5)WEIGHT (APPROX) VTA 1000Kg Noted Closed

6)DIMENSION OF COMPLETE DIESEL ENGINE INCLUDING BASE


VTA 1505mm X 1360mm X 1360mm Noted Closed
FRAME (L*W*H)

7)LOCAL CONTROL CUBICLES VTA Noted With Installation Contractor Scope of Work Noted Closed

8)TYPE AND DESIGN VTA internmal Combustion Engine With UL1247 Design Noted Noted

9)QUANTITY VTA 3nos complied Closed

10)MAKE OF CONTROL PANEL AND COMPONENETS VTA TORNATECH-UAE Noted Noted

11)DEGREE OF PROTECTION FOR ENCLOSURE VTA IP23-NEMA2 Enclosure Vendor to provide IP65 Vendor to confirm complaince for IP65

12)DETAILS OF EACH STARTER INDICATING NO. OF START/STOP


VTA 24Volts/7HRS Noted Noted
PER HOUR
DOC. NO: T-25-2018-00-ME-TBE-1064
TECHNICAL BID EVALUATION SHEET REV. NO.: 0

MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C) REQ'N N: T-25-2018-00-ME-REQ-1053

BIDDER BIDDER
DESCRIPTION REQ'N REQUIREMENT CLARIFICATIONS VENDOR TO FILL IN & ATTACH WITH TECHNICAL QUERY - 2
VENDOR TO FILL IN & ATTACH WITH OFFER
OFFER

13)THICKNESS mm VTA

14) DETAILS OF: VTA

(1) CONTROLS VTA


Noted
(2)ANNUCIATIONS VTA Kindly refer the submitted submittal Controller Data Sheets Noted

(3)INDICATIONS VTA

15)TYPE OF VISUAL ANNUNCIATION / INDICATIONS VTA

I. INSPECTION & TESTS

1) SHOP INSPECTION (8.1.1) YES

2) MATERIAL CERTIFICATION YES

3) INSPECTION REQUIRED FOR CONN. WELDS YES

4) HYDROSTATIC TEST WITNESS

Comply & Factory Test Report will be provide on Pump Delivery Time
5) PERFORMANCE TEST (complete unit w/Job Mtr) WITNESS Noted Noted
Period

6) TEST OF TOLERANCE (8.3.3.4) AS PER API 610

7) SOUND LEVEL TEST WITNESS

8) NPSH TEST WITNESS

9) COMPLETE UNIT TEST WITNESS

J. OTHER REQUIREMENTS:

1) INSTRUMENTATION FOR PUMP SKID VTA Will be provide after Assubmbly Noted Noted

2) HAZARDOUS AREA CLASSIFICATION FOR INSTRUMENTS(IF ZONE 2, IIB, T4 Noted With Installation Contractor Scope of work Noted Noted

3) MATERIAL CERTIFICATON 3.1B [CASING, IMPELLER, SHAFT,SEAL , SHAFT SLEEVE, SEAL HOUSING] Kindly refer the submittal Noted Noted

4) NOISE LEVEL AT 1 m DISTANCE FOR MOTOR / PUM dB(A) LESS THAN 85 Comply with 85db Complied Closed

5) SURFACE PREPARATION & PAINTING REQ'T T-25-2018-00-ME-SPC-1077 Compl with RAL3000 Vendor to provide painting as per specification provided Vendor to provide painting as per specification provided

6) SPARE PARTS (1) START UP & COMMISSIONING VTA Comply Complied Closed

(2) TWO(2) YEAR OPERATION PROVIDED BY VENDOR Comply with 1 year. More than 1 year additional Cost Vendor to provide 2 years operation Vendor to provide complaince for 2 years operation with no additional cost.

7) SPECIAL TOOLS VTA

8) SUPPLY OF FOUNDATION BOLTS & FURNISHING LOADS VTA

9) PACKING, SHIPPING AND STORAGE VTA

9) PROVISION FOR VIBRATION MEASUREMENT (FLAT SURFAC VTA Will be provide after Assembly Noted Noted

10) DIMENSIONAL GA DRAWING mm REQUIRED

11) OVERALL WEIGHT kg VTA

12) DELIVERY VTA


DOC. NO: T-25-2018-00-ME-TBE-1064
TECHNICAL BID EVALUATION SHEET REV. NO.: 0

MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C) REQ'N N: T-25-2018-00-ME-REQ-1053

BIDDER BIDDER
DESCRIPTION REQ'N REQUIREMENT CLARIFICATIONS VENDOR TO FILL IN & ATTACH WITH TECHNICAL QUERY - 2
VENDOR TO FILL IN & ATTACH WITH OFFER
OFFER

H. DEVIATIONS LIST FROM VENDOR

TECHNICAL ACCEPTANCE

COMMENTS

LEGEND: V : IN ACCORDANCE WITH REQUIREMENT VTA: MFR'S RECOMMENDATION N.S: NOT SPECIFIED IN QUOTATION
TECHNICAL BID EVALUATION SHEET
MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C)

BIDDER
DESCRIPTION REQ'N REQUIREMENT
VENDOR TO FILL IN & ATTACH WITH OFFER

A. GENERAL:

1) PUMP TYPE AXIALLY SPLIT HORIZONTAL CENTRIFUGAL PUMP Comply with Horizontal Split Case Type

Comply & Noted. Sequence of Operation Based on the Pressure Settings


2) NO. REQ'D WORKING 2, STAND-BY 1
& Installation Contrcator Scope of Work

3) MANUFACTURER SIZE / MODEL VTA SFP 2000-29SM-2G

4) DESIGN CODE API 610/ NFPA 20/ UL 1247 ANSI/UL 448

5) TABLE OF COMPLIANCE TO RFQ REQUIRED Comply

6) FILLED IN PUMP DATASHEET REQUIRED Comply

7) LOCATION OF PUMP INDOOR Comply

8) OPERATION INTERMITTENT Comply

9) PERFORMANCE AND TESTING CODE VTA Comply With UL Testing Standards

10) OPERATE IN SERIES OR PARALLEL PARALLEL Comply

THE PUMPS OFFERED ARE SUITABLE TO OPERATE IN


11) YES Comply
PARALLEL THROUGHOUT THE RANGE

B. OPERATING COND. & PERFORMANCE:

1) PUMPED FLUID FIRE WATER (FRESH WATER/SALT WATER) Fresh Water

2) DESIGN TEMPERATURE ℃ 5/82 50 Deg. Ambient Temperature

3) FLUID DENSITY Kg/m3 1000 Comply

4) SUCTION PRESSURE max / min kPa 362.75 / 88.23 Comply with 9 Bar

5) DISCHARGE PRESSURE kPa VTA Comply with 9 Bar

6) DIFF. HEAD. @ DUTY POINT m 120 9 bar (91.80 m head)

7) FLOW RATED m3/hr 454 Comply

8) MIN, CONTINUOUS FLOW m3/hr VTA Comply with 454 m³/hr

9) EFFICIENCY @ RATED POINT % VTA 62.40%

10) BHP @ RATED POINT kW VTA 256HP

11) MAX. POWER @ RATED IMPELLER kW VTA 256HP

Not Clear for EOC with Water Point. Kindly advise for the Exact
12) DRIVER SIZED FOR EOC WITH WATER REQUIRED
Requirement.

13) SPEED rpm VTA 2900 rpm

14) SUCTION SPECIFIC SPEED LIMIT rpm VTA 2900 rpm

15) NPSH (1) NPSH available m 8.72 Noted

(2) NPSH required m VTA NPSH Required for Propose Pump 4.2mtr

16) NPSHav - NPSHre m >1 Comply

17) NPSH @ EOC/150% flow < NPSH available m VTA Comply with 4.2mtr

18) RATED IMPELLER DIA. mm VTA 279 mm

19) MAX. / MIN. IMPELLER DIA. mm VTA 300/240 mm

20) MAX. HEAD @ RATED IMPELLER m VTA 11.24 bar @ 300mm dia

21) HEAD OF MAX. IMPELLER DIA. @ RATED FLOW m VTA 11.24 bar @ 300mm dia @ 2000GPM
TECHNICAL BID EVALUATION SHEET
MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C)

BIDDER
DESCRIPTION REQ'N REQUIREMENT
VENDOR TO FILL IN & ATTACH WITH OFFER

22) HEAD RISE TO SHUTOFF / SHUT OFF PRESSURE % VTA 9.35 bar

23) CAPACITY AT THE END OF CURVE m3/hr VTA 4400 GPM

24) RATED FLOW AS PERCENTAGE OF B.E.P FLOW % VTA 239.52 HP

25) MAXIMUM ALLOWABLE WORKING PRESSURE kPa VTA 250PSI

26) EQUIPMENT SUITABLE FOR BLACK BULB TEMP. VTA Proposed Pump 50Deg. Ambient Temperature

27) TEMPERATURE OF LIQUID ℃ 15 / 40 / 50 50Deg. Ambient Temperature

28) SHUT OF HEAD VTA 9.35Bar

29) SPECIFIC GRAVITY OF LIQUID @ 15℃ 0.992 Comply

30) TYPE OF SUCTION DOUBLE SUCTION TYPE Comply

31) PUMP BHP VTA 256HP

32) RATED HEAD mWC VTA 9 bar

33) POSITION OF DISCHARGE VALVE AT PUMP STARTING OPEN ( STANDBY PUMP IS IN PARALLEL POSITION) Comply

34) NPSH REQUIRED AT RUNOUT CONDITION mWC VTA 4.5mtr

35) PUMP SHAFT INPUT POWER AT RATED FLOW kw VTA 239.52 HP

C. CONSTRUCTION:

1) CASING (1) TYPE AXIALLY SPLIT Comply

(2) MOUNTING FOOT MOUNTED Comply

2) SUCTION NOZZLE (1) SIZE VTA Comply with 8 Inch Dia

(2) RATING : VTA ANSI B16.1 Class 250

(3) POSITION SIDE SUCTION Comply

3) DISCHARGE NOZZLE (1) SIZE : VTA Comply with 6 inch Dia

(2) RATING : VTA ANSI B16.1 Class 250

(3) POSITION SIDE DISCHARGE Comply

4) CASING DRAIN SIZE & RATING VTA 3/4inch dia

5) CASING VENT SELF VENTING Comply

6) SEAL TYPE GLAND PACKING Comply

7) BEARING TYPE (1) RADIAL BEARING VTA Comply with Roller Bearing

(2) THRUST BEARING VTA Comply with Roller Bearing

8) COUPLING (1) TYPE FLEXIBLE METALLIC DISC SPACER COUPLING Comply

(2) MFR. VTA Comply with Rigid Flexible Coupling

(3) SERVICE FACTOR 1.5 1.15

9) BASE PLATE SLOPING DRIP PAN Comply

10) TYPE OF IMPELLER ENCLOSED IMPELLER (CAST IN ONE PIECE) Closed impellar Type

11) DRIVE TYPE DIESEL ENGINE Comply

12) FLANGE DRILLING (SUCTION & DISCHARGE) ASME B 16.5 ANSI B 16.1
TECHNICAL BID EVALUATION SHEET
MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C)

BIDDER
DESCRIPTION REQ'N REQUIREMENT
VENDOR TO FILL IN & ATTACH WITH OFFER

13) BEARING LIFE VTA 5 years

14) SIZE OF BASE PLATE VTA Will be provide After Fire Pump Assembled

15) PERFORMANCE / FAMILY CURVE ENCLOSED YES Comply

STUFFING BOX ( MECHANICAL SEAL) DESIGN OF GLAN


16) ASSEMBLY SHALL BE SUITABLE FOR MENTIONED RAW VTA Comply with Packing Gland
WATER QUALITY

17) GASKET VTA Comply

D. MATERIAL:

1) CASING CAST IRON Cast Iron

2) IMPELLER SS Bronze

3) SHAFT SS Alloy Steel

4) SHAFT SLEEVE VTA Comply with SS304

5) WEAR RING 1) CASING VTA Brass

2) IMPELLER VTA Bronze

6) COUPLING GUARD REQUIRED Comply

7) SHAFT DIAMETER VTA Comply with 3" dia

8) BASE PLATE SS 316 Comply with Mild Steel

E.DIESEL ENGINE

1) MAKE VTA BLACK STALLION-UAE

2)APPLICABLE STANDARDS NFPA 20/ UL 1247 NFPA20 & UL1247

3) ENGINE GROSS POWER VTA 259/271.5HP

4.) ENGINE NET POWER (RATED CONTINOUS OUTPUT) VTA 240HP

5) ENGINE OVERLOAD CAPACITY( OUTPUT) FOR ONE HOUR VTA 256HP

6) ENGINE STARTER MOTOR VTA 24Volt

7)FAULTS LEADING TO AUTOMATIC DIESEL ENGINE SHUTDOWN VTA Comply

8) ENGINE INSTRUMENT PIPE VTA Comply

9)SILENCER WITH EXHAUST REQUIRED Noted With Installation Contractor Scope of Work

10) AIR FILTER 2 STAGE FILTER AND SILENCER Comply

11) DAY TANK FOR 6 Hrs CAPACITY VTA Comply with 8hrs asper NFPA20 Requirement

12) DAY TANK MATERIAL VTA Comply with Carbon Steel

13)MAIN OIL STORAGE TANK TO BE WITH MAGNETIC OIL GAUGE VTA Comply with Fuel Level Indicator

14)RADIATOR VTA Comply with Heat Exchanger Type

15) TYPE OF LUBRICATION LUBE OIL Comply

16)LUBRICATION OIL CONSUMPTION(Maximum) VTA 37.5Gallon Consumption per Hour

17)FUEL CONSUMPTION UNDER N.T.P VTA 37.5Gallon Consumption per Hour

18) 100% LOAD VTA 300 Gallon per 8 Hours


TECHNICAL BID EVALUATION SHEET
MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C)

BIDDER
DESCRIPTION REQ'N REQUIREMENT
VENDOR TO FILL IN & ATTACH WITH OFFER

19) ENGINE SPEED VTA 2900RPM

20)CRITICAL SPEED OF SHAFT VTA 2900RPM

21) METHOD OF ENGINE COOLING JACKET WATER-COOLING (RADIATOR) Comply with Heat Exchanger Type

22)EXHAUST OUTLET DIAMETER VTA Noted With Installation Contractor Scope of Work

23) EXHAUST FLOW ( TOTAL) VTA 8.76KPA

24)EXHAUST STACK HEIGHT m 15 Based on the Site Condition

25) EXHAUST PIPE VTA Min. 6" dia (We considered 10mtr pipe lenth & 3nos 90Deg.Elbow)

26)INSULATION WITH CLADDING VTA Noted With Installation Contractor Scope of Work

27)AIR ASPIRATON VTA Comply with TurboCharged

28)NUMBER OF CYLINDERS VTA 6

29)EFFICIENCY VTA 62.40%

30)BASE FRAME SKID MOUNTED (PUMP & ENGINE) Will be provide After Fire Pump Assembled

F. STARTING BATTERY

1)RATED VOLTAGE VTA 24V

2)TYPE OF BATTERY VTA Lead Calcium Battery

3)BATTERY CAPACITY AT 25 ° C VTA 12V Amps

4)NUMBER OF PERMISSIBLE START PER HOUR OF DIESEL ENGINE VTA 24Volts/7HRS

G. BATTERY CHARGER

1)TYPE/DESIGNATION VTA 24 Volts x 45 Amps with belt guard

2)VOLTAGE RATING VTA 220V

H. DIESEL ENGINE AUXILLARIES

1)POWER REQUIRMENTS (APPROX) VTA Comply with 150% Rated power

2)COOLING FAN MOTOR VTA Turbo Charged

3)FUEL OIL TRANSFER PUMP( IF APPLICABLE) VTA Bosch in-line “P” type

4)TOTAL POWER REQUIRMENTS FOR COMPLETE SYSTEM 0 259HP

5)WEIGHT (APPROX) VTA 1000Kg

6)DIMENSION OF COMPLETE DIESEL ENGINE INCLUDING BASE


VTA 1505mm X 1360mm X 1360mm
FRAME (L*W*H)

7)LOCAL CONTROL CUBICLES VTA Noted With Installation Contractor Scope of Work

8)TYPE AND DESIGN VTA internmal Combustion Engine With UL1247 Design

9)QUANTITY VTA 3nos

10)MAKE OF CONTROL PANEL AND COMPONENETS VTA TORNATECH-UAE

11)DEGREE OF PROTECTION FOR ENCLOSURE VTA IP23-NEMA2 Enclosure

12)DETAILS OF EACH STARTER INDICATING NO. OF START/STOP


VTA 24Volts/7HRS
PER HOUR
TECHNICAL BID EVALUATION SHEET
MAIN FIRE WATER PUMPS( DIESEL ENGINE DRIVEN PUMP) (P-7003A/7003B/7003C)

BIDDER
DESCRIPTION REQ'N REQUIREMENT
VENDOR TO FILL IN & ATTACH WITH OFFER

13)THICKNESS mm VTA

14) DETAILS OF: VTA

(1) CONTROLS VTA

(2)ANNUCIATIONS VTA Kindly refer the submitted submittal Controller Data Sheets

(3)INDICATIONS VTA

15)TYPE OF VISUAL ANNUNCIATION / INDICATIONS VTA

I. INSPECTION & TESTS

1) SHOP INSPECTION (8.1.1) YES

2) MATERIAL CERTIFICATION YES

3) INSPECTION REQUIRED FOR CONN. WELDS YES

4) HYDROSTATIC TEST WITNESS

Comply & Factory Test Report will be provide on Pump Delivery Time
5) PERFORMANCE TEST (complete unit w/Job Mtr) WITNESS
Period

6) TEST OF TOLERANCE (8.3.3.4) AS PER API 610

7) SOUND LEVEL TEST WITNESS

8) NPSH TEST WITNESS

9) COMPLETE UNIT TEST WITNESS

J. OTHER REQUIREMENTS:

1) INSTRUMENTATION FOR PUMP SKID VTA Will be provide after Assubmbly

2) HAZARDOUS AREA CLASSIFICATION FOR INSTRUMENTS(IF ZONE 2, IIB, T4 Noted With Installation Contractor Scope of work

3) MATERIAL CERTIFICATON 3.1B [CASING, IMPELLER, SHAFT,SEAL , SHAFT SLEEVE, SEAL HOUSING] Kindly refer the submittal

4) NOISE LEVEL AT 1 m DISTANCE FOR MOTOR / PUM dB(A) LESS THAN 85 Comply with 85db

5) SURFACE PREPARATION & PAINTING REQ'T T-25-2018-00-ME-SPC-1077 Compl with RAL3000

6) SPARE PARTS (1) START UP & COMMISSIONING VTA Comply

(2) TWO(2) YEAR OPERATION PROVIDED BY VENDOR Comply with 1 year. More than 1 year additional Cost

7) SPECIAL TOOLS VTA

8) SUPPLY OF FOUNDATION BOLTS & FURNISHING LOADS VTA

9) PACKING, SHIPPING AND STORAGE VTA

9) PROVISION FOR VIBRATION MEASUREMENT (FLAT SURFAC VTA Will be provide after Assembly

10) DIMENSIONAL GA DRAWING mm REQUIRED

11) OVERALL WEIGHT kg VTA

12) DELIVERY VTA