Computer Simulation of Transients Due To Disconnector Switching in Air-Insulated Substations
Computer Simulation of Transients Due To Disconnector Switching in Air-Insulated Substations
Abstract—Switching overvoltages due to disconnector voltage collapse, ∆U, Fig. 1., applied to the circuit gives
switching in air-insulated substations (AIS) are presented. rise to a voltage and current damped oscillating wave.
Analysis of shape and levels of switching overvoltages by
means of experimental and computing investigations on 220
kV switchyards of Thermo Power Plant (TPP) Kakanj are
presented. Computer simulations by means of EMTP-ATP
[1] are performed.
I. INTRODUCTION
As generator stations and substations have become
more complex their required standards of reliability and
stability have become more demanding. These demands
have been met by the widespread use of high-speed and
low-power electronic systems. This progress in the
technology has reduced the level of energy required to
switch between logic states, increased the efficiency with
which these levels of energy can be transferred by Fig. 1. The voltages due to the disconnector switching
unintended coupling path, and lowered the levels of a) Simple pattern of substation, b) Wave shape on disconnector’s
contacts
energy which the components can survive.
Electromagnetic interference problems can manifest
themselves as errors or failures after the equipment has The maximum value of voltages and the maximum
entered service. Every incident of interference involves a value of the slope of the wave front increasing will take
source of disturbances, a coupling mechanisms and path, place at the maximum distance between contacts. For the
and susceptible piece of equipment [2]. Switching purpose of the investigation of the insulation strength and
operation of disconnector in power stations and induction of electromagnetic interferences (EMI), the
substations causes high level of high frequency most important are the first few strikes during the closing
overvoltages that can be coupled with low voltage operation or the last few strikes during the opening
secondary circuits and electronic equipment unless they operation.
are suitably protected. The purpose of this paper is to
suggest computer models of circuits for representative of The function of high-voltage air-break disconnectors is
simulations transients due to disconnector switching in to provide electrical isolation of one part of the
air-insulated substations. switchgear. Disconnector’s standards define a negligible
current interrupting capability (≤ 0.5 A) or a voltage
II. OUTLINE PROBLEM between the contacts if it is not significantly changed.
These values of currents include the capacitive charging
Switching operation of disconnector in power stations currents of bushings, busbars, connectors, very short
and substations give rise to electromagnetic interferences lengths of cables and the current of voltage instrument
because they generate abrupt voltage collapses, ∆U, across transformers. Disconnector’s contacts in air-insulated
the contacts of the switching equipment [3]. The collapse substations (AIS) are moving slowly causing numerous
time, ∆t, is dependent on the distance between the contacts strikes and restrikes between contacts. Strikes and
(several tens or some hundreds of nanoseconds) of restrikes occur as soon as the dielectric strength of the air
equipment in air-insulated substations (AIS) [2]. The between contacts is exceeded by overvoltage. The
2052
network
220 kV DISCONNECTOR Current
L busbars busbars transformer
arc
U
Lv Lv
Capacitive
voltage
transformer Rd Rd
busbars
C1 C1
Ccb
busbars
C2 C2
busbars Cdc
TABLE I.
COMPARISON OF MEASURED AND CALCULATED SURGE OVERVOLTAGES
LOAD SIDE
Difference, ∆
Parameter Measured Calculated
(%)
Overvoltage factor k
1.55 1.62 4.52
(p.u.)
Frequency f (kHz) 390 400 2.56
2053
Comparison of measured and calculated surge Comparison of measured and calculated surge
overvoltages and frequencies are given in Table II. overvoltages and frequencies are given in Table III.
Difference, ∆
Parameter Measured Calculated Parameter Measured Calculated Difference, ∆ (%)
(%)
REFERENCES
[1] EMTP_ATP, European EMTP-ATP Users Group e.V.
[2] Guide on EMC in Power Plants and Substations, CIGRE WG
36.04, Dec. 1997
[3] R.Cortina, A.Porrino, P.C.T. Van Der Laan, A.P.J. Van Deursen,
‘Analysis of EMC problems on auxiliary equipment in electrical
a) Trapped charge ( ___ measured, ___ calculated) installations due to lightning and switching operations’, CIGRE
1992, paper 36-302
[4] H.Remde, H.Schwarz, ‘Transient overvoltages in CT and VT
secondary circuits in high-voltage substations’, ABB Review 1/91
[5] ‘Overvoltages in primary and secondary circuits in RP Kakanj
due to disconnector switching’, Faculty of Electrical Engineering,
Report No.L1410020, Sarajevo, 2005
[6] S.Carsimamovic, R.Gacanovic, Z.Bajramovic, M.Veledar,
M.Ljevak, P.Osmokrovic, ‘Switching Overvoltages in Air-
Insulated Substations (AIS) due to Disconnector and Circuit
Breaker Switching’, CIGRE 2006, paper C4-301
2054