Generator Protection Setting List
Generator Protection Setting List
xls Page 1 of 10
Rev B Updated the generated output ratings & reactance values, Relay Settings
Explanations:
Protection functions
I2 = Negative sequence current in primary value
I2perm= Permissible negative sequence current in primary value
Ibn= Nominal boundary current, thermal overload, primary value
IN= Rated generator current in primary value
IN_MACH = Generator nominal current in primary value
INprim = Primary nominal current, current transformer
Irg = Rated primary generator current
K= Asymmetrical factor (generator constant) at I2/IN = 1
Kprim= Asymmetrical factor (generator constant) at I2/IN = 1in primary value
Ksec= Asymmetrical factor (generator constant) at I2/IN = 1in secondary value
Pbn= Nominal boundary power, thermal overload, primary value
PMach= Generator reverse power corresponding to setting value
Preverse= Generator reverse power, primary value
Psec= Generator secondary power corresponding to setting value
SN= Generator Nominal apparent power , primary value
SNsec= Generator secondary nominal power
SN_tr= Step-up transformer nominal power
Srg= Generator rated power
Tcool-down= Time required by the generator to cool down under admissible unbalanced load I2>
to the initial value.
Ue= Generator neutral point displacement voltage in Siprotec relay
Uk= Step-up transformer short circuit impedance
UN_MACH = Generator nominal line voltage in primary value
UNprim= Primary Nominal Voltage, voltage transformer
UN_tr= Primary or secondary Nominal Voltage, step-up transformer
Urg= Rated primary generator line voltage
Xdsec= Generator synchronous direct reactance in secondary value
DIGSI NO:
Digsi is the software in which parameter values for relay protection are programmed.
The digsi file is loaded to relay protection, Siprotec 7UM6211 (sub 1 &2).
With the help of the digsi no., it is easier to enter the parameter values in digsi software.
GENERATOR
Digsi No. Manufacturer: Siemens
Rated Voltage, U rg 0251 11,5 kV ± 5 % GeneratorType 1DS2093-7AF02-Z B
Rated apparent power, S rg 0252 65,7 MVA Digsi No.
Rated current, I rg N/A 3298 A Exciter Type 1JG3804-7HU06-Z
Rated Frequency, f rg 0270 50 Hz ± 2 % Exciter Output (Main exciter) N/A 160 kVA
Power Factor (PF) over excited N/A 0,85 Excitation Voltage (Aux AC exciter) N/A 67,2 VDC
Power Factor (PF) under excited N/A 0,95 Excitation Current (Aux AC exciter) N/A 14,3 ADC
Rated Speed, n N/A 1500 rpm
Reactance Xd direct axis reactance N/A 195 % (unsat) B 174,3 % (sat) Time constants
Reactance X 'd direct axis transient reactance N/A 39,3 % (unsat) B 25,4 % (sat) Td' - direct axis SC transient N/A 0,637 s B
Reactance X '' d direct axis subtransient reactance N/A 22,0 % (unsat) B 15,2 % (sat) Td'' - direct axis SC subtransient N/A 0,015 s B
Reactance X0 zero sequence reactance N/A 7,3 % (sat) Td' 0 - direct axis OC transient N/A 4,29 s B
Reactance X2 negative sequence reactance N/A 15,1 % (sat) Ta - armature short-circuit N/A 0,311 s B
Ambient Temp
Max. cont. negative sequence current I 2 N/A 8,0% % (°C) Output (kW) Ibn Current (A) Comments (Implemented in GT Control System)
2 B In the technical specification a graph shows output
Fault condition capability (I 2 /I n) xt N/A 20,0 s -10 58500 3455
power at PF 0,85 versus temperature. From this
0 58500 3455 B
graph five values are picked. The current values are
B used for the thermal protection.
Siemens CT data side1 (line side) & Note:
side 2 (neutral side): Type 5P30 10 58500 3455 Thermal Overload protection (ANSI 49) is
implemented in Simatic Control System
Snct 10 VA 30 55250 3263 B
P bn ( MW ) ≥ 1000
40 49500 2924 B I bn <
U ( kV ) ≥ 3 ≥ 0 ,85
Ipct>0,75xIrg= 0,82 Ipct 0202 / 0211 4000 A 45 46500 2746 B
Thermal
Time Constant
Heating/
CT Ratio= NCTR 4000 Is ct 0203 / 0212 1 A Cooling 25 min
ALF 30
Correction
Angle 0204 0 Degree
CT ratio
prim / sec - Iee1 0205 1
CT ratio
prim / sec - Iee2 0213 1 CH1
CT ratio
prim / sec - Iee2 0213 1 CH2
Unbalanced load K secondary 1705 T cool-down = 3125 s Time for cooling down
Tcool _ down <
I2>, t=f(I2) ∋I 2 perm I N (2 primary
primary/
1706 I 2 >> = 59,4% % I 2>>: Definite time trip level
95% Stator earth Setting: 5% of the full displacement voltage. secondary 5002 U o ≥ 0,05xU delta = 5,50 V B
primary/ Setting value given in secondary
fault or secondary 5005 T S/E/F time delay = 0,5 s value. Connected to the broken delta
Neutral Voltage winding of the voltage transformers on
UN> the stator terminal side of the
(59N) generator.
P bn ( MW ) ≥ 1000
Thermal
<
Time Constant
I bn Heating/
U ( kV ) ≥ 3 ≥ 0 ,85 Cooling 25 min
External Trips
Relay function Setting formula Step,type Values Digsi No Settings Remark
50ARC Arc Protection HIGS External trip 1 BI3 Trip GCB.FCB & GT
primary/
secondary 8602 Ext. Trip1 Time delay 0,00 s