96M00603 FS-N10 Series Quick Start and Cabling

„ Quick Start
Digital Fiber Sensor Fine sensitivity adjustment
Output switch
Press the [MODE] button once, then

FS-N10 Series
Up Down use to select L-on or D-on

Preset function
Instruction Manual Configure easily
with a single press
when receiving light
Setting value Light intensity
Sensitivity setting Power select switch *1

Press once each for workpiece/no workpiece Standard ⇔ MEGA (fixed)

*1 This is a channel switch on 2-output types.


*2 Press and hold the [MODE] button to make advanced settings.

„ Cabling
Note See page 4 for information about connecting to external devices other than the FS-
N11N.

Brown
Failure to follow these instructions may lead to death or seri- DC12-24V
Danger ous injury.
Black
Load
Warning Failure to follow these instructions may lead to injury.
Blue
0V
Failure to follow these instructions may lead to product dam-
Caution age (product malfunction, etc.)
Mounting Unit

Note Provides additional information on proper operations that can be easily mistaken.
„ Mounting on a DIN Rail 3

1 Align the claw at the bottom of the main body with


Note This provides tips about situations in which the feature being described is useful.
the DIN rail, as shown in figure1.
While pushing the main body in the direction of
2
Tip the arrow 1, slant it in the direction of the arrow 2. 1

2 To dismount the sensor, raise the main body in figure1


See "FS-N10 Series User's Manual" for details on the features of the FS-N10 series and the direction of the arrow 3 while pushing the
detailed instructions for configuration. main body in the direction of the arrow 1.

„ Installation on a Wall (Main Unit Only)


Hints on Correct Use
1 Attach the unit to the optional mounting bracket (OP-
73880), mount them together, and secure them with
two M3 screws as shown in figure2.
• This product is used to detect targets. Do not apply the
product to safety circuits for human protection.
• This product is not of explosion-proof construction. Do not
use the products in places with flammable gas, liquid, or OP-73880
Warning dust. figure2
• This product is a sensor of DC power supply type. Do not
apply AC power. The product may explode or burn if an AC
voltage is applied.
Connecting Fiber Unit

• Do not wire the amplifier line along with power lines or high-tension lines, otherwise the sen- 1 Open the dust cover in the direction shown by
sor may malfunction or receive damage due to noise. arrow 1.
1
• When using a commercially available switching regulator, ground the frame ground terminal
and ground terminal.
2 Move down the fiber lock lever in the direction
shown by arrow 2. 4
• Do not use the FS series outdoors, or in a place where extraneous light can enter the light-


receiving surface directly.
Due to the individual dispersion of characteristics and the difference in fiber unit model, the
3 Insert a fiber unit into the fiber insertion holes 2
to a length of the fiber insertion sign (i.e.,
maximum sensing distance or displayed value of all the units are not the same. approximately 14 mm).
• If the sensor is used in S-APC mode for a long time, the LED indicators will be imposed with 3
a heavy load. In that case, the sensor will be automatically set to ACC mode where the cur- 4 Move down the fiber lock lever in the direction
Fiber insertion sign

rent consumption of the sensor for light emission will be constant, and “END APC” will be shown by arrow 4.
displayed. The sensor can be continuously used in this case. Replace the sensor, however, if
highly precise detection is required. Note • If a thin fiber unit is used, an adapter provided with the thin fiber unit will be
required.
„ About UL Certification Unless the correct adapter is connected, the thin fiber unit will not detect
targets correctly (the adapter is supplied with the fiber unit).
The FS-N series is UL and C-UL certified, and is compliant with the UL and CSA standards.
• Applicable standards UL508 Industrial Control Equipment Cable outer dia Adapter Appearance
CAN/CSA C22.2 No.14-M05 Industrial Control Equipment
Adapter A
• UL File No. E301717 φ1.3 (OP-26500)
• UL categories: NRKH, NRKH7
• Enclosure Type 1 (based on UL50 standard) Adapter B
φ1.0
(OP-26501)
„ Notes on UL Certification
• To connect the coaxial reflective type fiber unit to the amplifier, connect the
• The power source used with the FS-N series must be UL Listing certified for Class 2 output single-core fiber to the transmitter side, and connect the multiple-core fiber
as stipulated by US National Electric Code (NEC) NFPA70. to the receiver side.
• Connect the FS-N12 and N14 to the FS-N11 and N13 main units for use.

Included accessories
Transmitter
Single-core fiber
• Instruction Manual 1pc.
Multi-core fiber
• Fiber cutter 1pc. Receiver

1
Downloaded from www.Manualslib.com manuals search engine
Two-point calibration performs detection at a location where there is a workpiece, and
Connecting Multiple Amplifiers another location where there is not, uses the intermediate value as the setting.
If the sensitivity difference does not have enough room, "- - - -" flashes for about two sec-
Up to 16 sub units can be connected to one main unit. onds after the calibration is complete. The set value is stored in memory even in that case.

Mount on DIN rail and install on metal sheeting when connecting to


Warning multiple amplifiers or mounting main units together. Other Calibration Methods

Note • Multiple connections cannot be made to equipment other than the FS-N10 „ Increase Resistance to Dust and Dirt
series.
• Turn the power off before connecting multiple sub units. z Maximum Sensitivity Setting
• Do not touch the expansion connector with your bare hands.
In the state shown below, press and hold the [SET] button for three seconds and stop push-
ing when "5'6" flashes.
1 Remove the protection covers of the main unit and The sensitivity is set slightly higher than the light intensity.
sub unit(s).
Through-beam model : with workpiece set

2 Install the amplifiers one by one on the DIN rail. Workpiece

Press and hold for 3 seconds or more

3 Engage the two claws of the sub unit with the


Reflective model : without workpiece set
recesses on the main unit side until you hear a
click.

4 Attach the end units (option: OP-26751) to the


both ends of the connected amplifiers in the same
way as in step (2). Press and hold for 3 seconds or more

5 Sandwich the amplifiers between the end units.


Tighten the screws at the top (two screws x two
units) with a Phillips screwdriver to fix the end „ Calibrate with Moving Workpiece
units.
z Full Auto Calibration
OP-26751 (a set of two) Press and hold the [SET] button with no workpiece in place, while “5'6” is flashing, pass
through a workpiece. (Continue pressing the [SET] button while the workpiece passes
through.)
Calibration Method
Common to
Through-beam and Reflective Models
„ Detecting Even Small Differences
z Two-point Calibration Press and hold until
"UGV" flashes
Two-point calibration is the basic method for making calibration.
You can set the sensitivity level automatically, simply by pressing the [SET] button twice.
Just press once with the workpiece set up, and once without.

Through-beam model setting method


Press [SET] button once with
no workpiece set
While pressing the [SET] button
pass through a workpiece

Workpiece

Settings complete

Workpiece Press [SET] button once with „ Position Workpiece


workpiece set
z Positioning Calibration
Press the [SET] button with no workpiece set.
Place the workpiece in the location you wish to position it, and press and hold the [SET] but-
ton for at least 3 seconds. Release the button when "5'6" flashes.

Common to
Settings complete Through-beam and Reflective Models

Press [SET] button once with


no workpiece set
Reflective model setting method
Press [SET] button once with
no workpiece set

Press and hold [SET] button with


workpiece set

Press [SET] button once with


workpiece set
Workpiece Press and hold until
"UGV" flashes

Workpiece

Settings complete
Settings complete

2
Downloaded from www.Manualslib.com manuals search engine
Simple, User Friendly Functions „ Set the current value to an adequate value when it is too
large (when saturated).
„ Easily Set up Display z Use the Saturation Recovery Function

z Preset Function Press the [SET] button while pressing the [MODE] button to enable the saturation recovery
function.
With light ON, press the [PRESET] button. The current value is set to "". The light transmission level and light intensity gain are calibrated automatically.

Press [PRESET] button once


with no workpiece set

Green "PST" lights up Press the [SET] button while


pressing the [MODE] button.

Setting is Current value is


"" ""

Pressing the [PRESET] button changes the setting and current value as shown below.
Set the light intensity to
• Presetting with preset disabled: within the range in the table below.
The setting is changed to "". The setting can be changed via the normal calibration
method.
Power mode Light intensity setting range
• Presetting with preset enabled:
HSP, FINE, TURBO 2047 r 350
Only the current value is changed to "", and the setting is not changed.
SUPER 4095 r 500
Note • The preset function cannot be used together with the zero shift func- ULTRA, MEGA 5000 r 600
tion. To use the zero shift function, you must first disable the preset
function.
• This is not suited to transparent workpieces and other cases of detec- z Disable Saturation Recovery
tion with low light shielding. When the saturation recovery function is enabled, press the [SET] button while pressing the
[MODE] button to cancel it.
z Disable the Preset Function
Note Handy Uses for the Saturation Recovery Function
Press and hold the [PRESET] button to disable the preset function.
This function is handy when the fiber unit becomes saturated after installation.
When the preset function is disabled, the ratio of the setting and current values is main-
This eliminates the saturation via a simple operation, by automatically calibrat-
tained as-is. Tip
ing the light transmission level and light intensity gain.

Note Handy Uses for the Preset Function


This function is mainly useful when performing simple detection using a Output Switch
through-beam model fiber unit (e.g. complete dark detection, such as when all
Tip
light axes of the fiber unit are shielded with opaque workpieces).
Either light-ON (L-on) mode or dark-ON (D-on) mode can be selected.
When you are using multiple FS-N10 series units simultaneously, this function
is an easy way to make all the displays uniform. 1 While the current value is displayed, press the [MODE] button once.

„ Set Current Value to "0"


z The Zero Shift Function
This function is mainly used with reflective models.
Press the [PRESET] button and [ ] button at the same time.
The current value is set to "0".
2 Use to switch the output (.QP/&QP), then press the [MODE] button again.
The output switch completes, and the display returns to the current value.

Names of Each Part of the Main Unit

Fiber lock lever


Green "PST" lights up
SET button (SET)
Operation status indicators
PST indicator Setting value
Current value is "" DTM indicator (Displayed in green)
Digital monitor Current value
Manual button (Displayed in red)
Note The zero shift and preset function cannot be used together. To use ( )
the preset function, you must first disable the zero shift function.

Expansion
z Disable the Zero Shift Function protective cover
Press and hold the [PRESET] button to disable the zero shift function. Expansion connector
MODE button (MODE)
Note Handy Uses for the Zero Shift Function Preset button (PRESET)
This function is mainly used to set the current value to "0" on a reflective
model fiber unit. Cable*2 Power select switch*1
Tip
Dust cover
When a reflective model is first installed, the light intensity is sometimes not
set to "0".
If this happens, using the zero shift function to set the value to "0" when there
is no workpiece allows for easier understanding of the difference in light inten- *1 Setting to "M" locks the power mode to MEGA mode. The two output type is a channel
sity. switch.
*2 On the FS-N10Cx, this is an M8 connector rather than a cable. On the FS-N10Ex, this is an
e-CON connector.

3
Downloaded from www.Manualslib.com manuals search engine
Connecting to External Devices Initializing the Settings

„ FS-N11N/N12N/N11MN/N13N/N14N „ Initializing Method


Output Circuit Diagram Input Circuit Diagram (FS-N13N/N14N only)
DC3.3 V
1 Press and hold the [SET] and [PRESET] buttons simultaneously for three seconds.
DC12−24 V
Sensor main circuit Brown*1

Sensor main circuit


Monitor output(1−5V)*2 Device with input

Protection
Pink

circuit
impedance
Orange 10 Ω or more
Overcurrent
protection
Load PLC, etc.
DC5−30 V
circuit

Black*3 (Short-circuit current


(Control output) 1 mA or less) Blue
0V
0V
Blue*1

*1 FS-N11N/N11MN/N13N only
*2 FS-N11MN only Press and hold for 3 seconds or more
*3 The FS-N13N/N14N has a white cable as separate output 2.
2 Use the to select "456", then press the [MODE] button.
„ FS-N11P/N12P/N13P/N14P/N13CP/N14CP 3 Use the to select "K0K6", then press the [MODE] button.
Output Circuit Diagram Input Circuit Diagram (FS-N13P/N14P only) After initialization is complete, the display returns to the current value.
DC12−24 V

z
Brown
Brown 1*1
DC12−24 V
Initial Settings
Sensor main circuit

Sensor main circuit


protection circuit

PLC, etc.
Overcurrent

Black 4*2
Load
Setting Initial Value
(Control output)
Pink
Blue 3*1 (Short-circuit
current 2 mA
Power mode FINE
0V or less)
Detection mode Normal
2 4
Setting value 50
M8 connector Pin layout 1 3

Output switch L-on


*1 FS-N11P/N13P/N13CP only
*2 The FS-N13P/N14P has a white cable as separate output 2.
The FS-N13CP/N14CP has the pin2 as separate output2. Using a Fiber Cutter and Cautions for Use
„ FS-N11CN/N12CN/N11EN/N12EN
Output Circuit Diagram Input Circuit Diagram
„ Using a Fiber Cutter
1*
DC12−24 V
DC3.3 V 1 Inset the fiber into the cutter hole.

2
Sensor main circuit

Sensor main circuit


protection circuit

4
Load DC5−30 V
1 Bring down the blade in a single,
Overcurrent

swift motion to cut the fiber. 2


PLC, etc.
(Short-circuit current
1 mA or less) 3*
3* 0V Fiber
0V Fiber cutter
(OP-87098)

2 4
1
M8 connector Pin layout 1 3 e-CON connector Pin layout Always insert fiber from the end with writing

*FS-N11CN/N11EN only
„ Cautions for Using a Fiber Cutter
„ FS-N11CP/N12CP
Failure to heed the cautions below could reduce the detection range.
Output Circuit Diagram Input Circuit Diagram
1* DC12−24 V
DC12−24 V 1*
• When cutting a fiber unit to be attached to the FS-N10 series, be sure to use a gray fiber cut-
Sensor main circuit

Sensor main circuit


protection circuit

ter (OP-87098)
PLC, etc.
• Stopping the blade midway could cause a bad cut plane, reducing the detection range.
Overcurrent

• Do not use the same hole twice.


4
Load 2
(Short-circuit
0V current 2 mA
or less)
3*

Function Configuration
2 4

M8 connector Pin layout 1 3 e-CON connector Pin layout


„ Basic Setting
*FS-N11CP only MODE
Press and hold for 3 seconds or more

„ Socket Cable (Sold Separately)


For FS-N11CN/N11CP/N12CN/N12CP/N13CP/N14CP J52  High Speed mode

Pin - Pin and wire color table


MODE
(KPG  Fine mode

OP-73864 Connected
pin No.
Core wire
cover color
6WT$  Turbo mode
(Cable length: 2 m)
3
4 2
1
1 Brown 5W24  Super mode

7.64 
OP-73865 2 White
(Cable length: 10 m) Ultra mode
3 Blue
4 Black /')#  MEGA mode

Error Displays and Corrective Actions 5'6 5VF Normal sensitivity setting method
MODE
5'6 5'V2 Percentage Calibration*1

Error display Cause Solution 5'6 15'V Zero-shift calibration

ErC Overcurrent in the control output.


Check the load and return the current
within the rated value. '0& MODE
Settings complete

ErE Failed to write/load the internal data. Perform initialization (p.4).


MODE
5V) (W0E Go to detection setup mode

End APC Large load on the light source.


Replace the sensor if highly precise 5V) &K52 Go to display setup mode

5V) 5;5
detection is required.
Go to system setup mode

Return to normal display

MODE
*1 You can press the button to set between the range of 2 to 2.

4
Downloaded from www.Manualslib.com manuals search engine
„ Detection Settings „ System Settings
5V) (W0E MODE
5V) 5;5 MODE

6Q((  Timer OFF #2% Q(( Disable APC

Q((&  #2% QP
MODE MODE
Off-delay timer *1 Enable APC

Q0&  On-delay timer * 1

'EQ Q(( Do not use eco feature


5JQ6  One-shot timer *1
'EQ QP
MODE
Enable eco feature

&'VE 5VF Normal (light intensity)


detection mode 'EQ (W.. Reduce power consumption
(response time 4 times slower)

&'VE &V/
MODE
DATUM1 mode *2

&'VE &V/ DATUM2 mode *2 )#KP 5VF Standard current value display

)CKP (W..
MODE
Maximum current value display
&'VE #4'# Area detection mode (4 times hysteresis)

&'VE Rising Edge Detection Mode


KPV( 56& Normal operation

&'VE Falling Edge Detection Mode MODE


KPV( &Q$.
Twice number of
interference-prevention units as 56&
(response time 2 times slower)
*6 KP Q(( Do not use external input
*1 .KP- Q(( Disable common key operations
KP 5'V
MODE
External calibration input
.KP- QP
MODE
Enable common key operations
KP 245V Preset input

KP 5J(V Zero shift input '0& Settings complete

KP 45V 5V) (W0E


MODE
Reset input Go to detection setup mode

KP .Q(( Transmission OFF input 5V) &KU2 Go to original display setup mode

KP 2#75 Pause mode transition input *3 5V) 5;5 Return to system setup mode

KP 5.'2 Sleep mode transition input


Return to normal display

MODE
#66  Light emission power selection *4 *1 Main unit only.

„ Two Output *2
*7 #P.)  Analog scaling *5
MODE
EJ 5VF Light intensity detection mode

'0& MODE Settings complete


MODE
EJ .K/V Limit setting output mode

5V) &K52 Go to display setup mode MODE

5V) 5;5 Go to system setup mode


T5V 75'4 User reset

5V) (W0E Return to original


detection setup mode T5V #WVQ Auto reset

EJ #.TV
Return to normal display
Warning output mode
MODE
*1 Press the button to set between the range of  and (ms).
6Q(( 
MODE
*2 Press the button to set the retouch sensitivity to a range of between .'W and .'W Timer OFF
and set the warning output level to a range of between 12 and 2.
Q((&  Off-delay timer *1
MODE
MODE
*3 Press the button to toggle between Q((/Q0/-''2.
*4 Can be set between the range of  and . Q0&  On-delay timer *1
*5 Can be set between the range of  and .
*6 Only external input types (FS-N11CN/N11CP/N11EN/N12EN/N13N/N13P/N14N/N14P).
5JQ6  One-shot timer *1

*7 Only monitor output types (FS-N11MN).

„ Display Settings '0& Settings complete


MODE

5V) &K52 MODE


Return to normal display
MODE
button to set between the range of  and (ms).
4'W Q((
*1 Press the
Normal display method
*2 Only 2 output types (FS-N13N/N13P/N14N/N14P/N13CP/N14CP).
4'W QP
MODE
Reverse display

5W$ Q(( Do not set up sub-display

5W$56&'
MODE
Extension display

5W$ $#4 Bar display

5W$ 2'4 Excess gain display

5W$ *.& Light intensity hold display *1

5W$*.&2 Excess gain hold display *1

5W$.FQP L-on / D-on display

24* QP
Enable the saturation of the
Preset function *2

24* Q((
MODE Disable the saturation of the
Preset function

'0& Settings complete


MODE
5V) 5;5 Go to system setup mode

5V) (W0E Go to detection setup mode

5V) &K52 Return to original display setup mode

Return to normal display


MODE
*1 Press the button to toggle between 5VF/2`2A/D`DA/2AD`/2`DA
MODE
*2 Press the button to set between the range of 2 and 2.

5
Downloaded from www.Manualslib.com manuals search engine
Specifications

Type Monitor
Standard 1 output High functionality 2 output
output

Cable/M8 connector Cable M8 connector*1 e-CON connector*1 Cable Cable M8 connector*1

Main unit/sub unit Sub unit Sub unit Sub unit Sub unit Sub unit
Main unit (with output Main unit (with output Main unit (with output Main unit Main unit (with output Main unit (with output
cable) cable) cable) cable) cable)

Model NPN FS-N11N FS-N12N FS-N11CN FS-N12CN FS-N11EN FS-N12EN FS-N11MN FS-N13N FS-N14N - -

PNP FS-N11P FS-N12P FS-N11CP FS-N12CP - - - FS-N13P FS-N14P FS-N13CP FS-N14CP

Control output 1 output 1 output 1 output 1 output 1 output 1 output 1 output 2 output 2 output 2 output 2 output

Monitor output (1-5 V) - - - - - - 1 output - - - -

External input - - 1 input 1 input 1 input 1 input - 1 input 1 input - -

Response time 50 Ǵs (HIGH SPEED)/250 Ǵs (FINE)/500 Ǵs (TURBO)/1 ms (SUPER)/4 ms (ULTRA)/16 ms (MEGA)

Control NPN output NPN open collector 30 V; 1 output max: 100 mA or less; 2 output total:
output 100 mA or less (used stand-alone)/20 mA or less (multiple connections); residual voltage 1 V or less

PNP output PNP open collector 30 V; 1 output max: 100 mA or less; 2 output total:
100 mA or less (used stand-alone)/20 mA or less (multiple connections); residual voltage 1 V or less

Monitor output 1 to 5 V voltage output; load resistance 10 k: or more; repeat precision r 0.5% of F.S.; responsiveness 1 ms (FS-N11MN only)

External input input time 2 ms (ON)/20 ms (OFF) or more

Multiple connections to sub


Up to 16 units can be connected total, but two-output type is treated as two units
units

Number of interference
0 for HSP; 4 for FINE; 8 for TURBO/SUPER/ULTRA/MEGA (When set to double, the number of interference-prevention units will be doubled.)
prevention units

Rating Power voltage 12 - 24 V DC r 10% ripple (P-P) 10% or less

NPN Normal:900 mW or less (36 mA max. at 24 V, 48 mA max. at 12 V)*2


Eco on mode:800 mW or less (32 mA max. at 24 V, 39 mA max. at 12 V)*2
Eco Full mode:470 mW or less (19 mA max. at 24 V, 23 mA max. at 12 V)

PNP Normal : 1050 mW or less(42 mA max. at 24 V,


56 mA max. at 12 V)*2
Normal : 950 mW or less (39 mA max. at 24 V, 52 mA max. at 12 V)*2
Eco on mode : 950 mW or less(38 mA max. at 24 V,
Eco on mode : 850 mW or less (35 mA max. at 24 V, 44 mA max. at 12 V)*2 -
47 mA max. at 12 V)*2
Eco Full mode : 520 mW or less (21 mA max. at 24 V, 26 mA max. at 12 V)
Eco Full mode : 600 mW or less(24 mA max. at 24 V,
29 mA max. at 12 V)

Environme Operating
ntal ambient Incandescent lamp: 20,000 lx or less; Sunlight: 30,000 lx or less
resistance luminance

Operating
ambient -10 to +55 q
C (no freezing)*3
temperature

Operating
ambient 35 to 85% RH (no condensation)
humidity

Vibration
10 to 55 Hz Compound amplitude 1.5 mm, 2 hours for each of X,Y,Z axis
resistance

Shock
500 m/s2 3 times for each of X,Y,Z axis
resistance

Case material Both main unit and housing material: Polycarbonate

Weight Approx 75g Approx 45g Approx 22g Approx 22g Approx 22g Approx 22g Approx 75g Approx 80g Approx 70g Approx 22g Approx 22g

*1 Use a cable length of 30m or less for M8 connector and e-CON connector types.
*2 Increases 100 mW (4.0 mA) for High Speed mode
*3 One or two more units connected: -10 to +55 q C; 3 to 10 more units connected: -10 to +50q C; 11 to 16 more units connected: -10 to +45q
C. When using 2-outputs, one unit is counted as two units.
All temperature regulations are for when the unit is mounted on a DIN rail and installed on metal sheeting.

Warranties and Disclaimers


KEYENCE CORPORATION
1-3-14, Higashi-Nakajima, Higashi-Yodogawa-ku,
KEYENCE, at its sole option, will refund, repair or replace at no charge any defective Products
Osaka, 533-8555, Japan
within 1 year from the date of shipment. Unless stated otherwise herein, the Products should
not be used internally in humans, for human transportation, as safety devices or fail-safe sys- PHONE: +81-6-6379-2211 www.keyence.com
tems. EXCEPT FOR THE FOREGOING, ALL EXPRESS, IMPLIED AND STATUTORY WAR-
AUSTRIA HUNGARY SINGAPORE
RANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY, FITNESS FOR A
Phone: +43-2236-378266-0 Phone: +36 14 748 313 Phone: +65-6392-1011
PARTICULAR PURPOSE AND NONINFRINGEMENT OF PROPRIETARY RIGHTS, ARE
EXPRESSLY DISCLAIMED. KEYENCE SHALL NOT BE LIABLE FOR ANY DIRECT, INDI- BELGIUM ITALY SLOVAKIA
RECT, INCIDENTAL, CONSEQUENTIAL OR OTHER DAMAGES, EVEN IF DAMAGES
Phone: +32 2 716 40 63 Phone: +39-2-6688220 Phone: +421 2 5939 6461
RESULT FROM THE USE OF THE PRODUCTS IN ACCORDANCE WITH ANY SUGGES- CANADA JAPAN SWITZERLAND
TIONS OR INFORMATION PROVIDED BY KEYENCE. In some jurisdictions, some of the fore- Phone: +1-905-696-9970 Phone: +81-6-6379-2211 Phone: +41 43 455 77 30
going warranty disclaimers or damage limitations may not apply. CHINA KOREA TAIWAN
Phone: +86-21-68757500 Phone: +82-31-642-1270 Phone: +886-2-2718-8700
CZECH REPUBLIC MALAYSIA THAILAND
Phone: +420 222 191 483 Phone: +60-3-2092-2211 Phone: +66-2-369-2777
FRANCE MEXICO UK & IRELAND
Phone: +33 1 56 37 78 00 Phone: +52-81-8220-7900 Phone: +44-1908-696900
GERMANY NETHERLANDS USA
Phone: +49-6102-36 89-0 Phone: +31 40 20 66 100 Phone: +1-201-930-0100
HONG KONG POLAND
Phone: +852-3104-1010 Phone: +48 71 36861 60
Specifications are subject to change without notice. A6WW1-MAN-0059

Copyright (c) 2009 KEYENCE CORPORATION. All rights reserved.


00603E 0079-1 96M00603 Printed in Japan