FSN 11 N
FSN 11 N
Quick Start
Digital Fiber Sensor Fine sensitivity adjustment
Output switch
Press the [MODE] button once, then
FS-N10 Series
Up Down use to select L-on or D-on
Preset function
Instruction Manual Configure easily
with a single press
when receiving light
Setting value Light intensity
Sensitivity setting Power select switch *1
Cabling
Note See page 4 for information about connecting to external devices other than the FS-
N11N.
Brown
Failure to follow these instructions may lead to death or seri- DC12-24V
Danger ous injury.
Black
Load
Warning Failure to follow these instructions may lead to injury.
Blue
0V
Failure to follow these instructions may lead to product dam-
Caution age (product malfunction, etc.)
Mounting Unit
Note Provides additional information on proper operations that can be easily mistaken.
Mounting on a DIN Rail 3
• Do not wire the amplifier line along with power lines or high-tension lines, otherwise the sen- 1 Open the dust cover in the direction shown by
sor may malfunction or receive damage due to noise. arrow 1.
1
• When using a commercially available switching regulator, ground the frame ground terminal
and ground terminal.
2 Move down the fiber lock lever in the direction
shown by arrow 2. 4
• Do not use the FS series outdoors, or in a place where extraneous light can enter the light-
•
receiving surface directly.
Due to the individual dispersion of characteristics and the difference in fiber unit model, the
3 Insert a fiber unit into the fiber insertion holes 2
to a length of the fiber insertion sign (i.e.,
maximum sensing distance or displayed value of all the units are not the same. approximately 14 mm).
• If the sensor is used in S-APC mode for a long time, the LED indicators will be imposed with 3
a heavy load. In that case, the sensor will be automatically set to ACC mode where the cur- 4 Move down the fiber lock lever in the direction
Fiber insertion sign
rent consumption of the sensor for light emission will be constant, and “END APC” will be shown by arrow 4.
displayed. The sensor can be continuously used in this case. Replace the sensor, however, if
highly precise detection is required. Note • If a thin fiber unit is used, an adapter provided with the thin fiber unit will be
required.
About UL Certification Unless the correct adapter is connected, the thin fiber unit will not detect
targets correctly (the adapter is supplied with the fiber unit).
The FS-N series is UL and C-UL certified, and is compliant with the UL and CSA standards.
• Applicable standards UL508 Industrial Control Equipment Cable outer dia Adapter Appearance
CAN/CSA C22.2 No.14-M05 Industrial Control Equipment
Adapter A
• UL File No. E301717 φ1.3 (OP-26500)
• UL categories: NRKH, NRKH7
• Enclosure Type 1 (based on UL50 standard) Adapter B
φ1.0
(OP-26501)
Notes on UL Certification
• To connect the coaxial reflective type fiber unit to the amplifier, connect the
• The power source used with the FS-N series must be UL Listing certified for Class 2 output single-core fiber to the transmitter side, and connect the multiple-core fiber
as stipulated by US National Electric Code (NEC) NFPA70. to the receiver side.
• Connect the FS-N12 and N14 to the FS-N11 and N13 main units for use.
Included accessories
Transmitter
Single-core fiber
• Instruction Manual 1pc.
Multi-core fiber
• Fiber cutter 1pc. Receiver
1
Downloaded from www.Manualslib.com manuals search engine
Two-point calibration performs detection at a location where there is a workpiece, and
Connecting Multiple Amplifiers another location where there is not, uses the intermediate value as the setting.
If the sensitivity difference does not have enough room, "- - - -" flashes for about two sec-
Up to 16 sub units can be connected to one main unit. onds after the calibration is complete. The set value is stored in memory even in that case.
Note • Multiple connections cannot be made to equipment other than the FS-N10 Increase Resistance to Dust and Dirt
series.
• Turn the power off before connecting multiple sub units. z Maximum Sensitivity Setting
• Do not touch the expansion connector with your bare hands.
In the state shown below, press and hold the [SET] button for three seconds and stop push-
ing when "5'6" flashes.
1 Remove the protection covers of the main unit and The sensitivity is set slightly higher than the light intensity.
sub unit(s).
Through-beam model : with workpiece set
Workpiece
Settings complete
Common to
Settings complete Through-beam and Reflective Models
Workpiece
Settings complete
Settings complete
2
Downloaded from www.Manualslib.com manuals search engine
Simple, User Friendly Functions Set the current value to an adequate value when it is too
large (when saturated).
Easily Set up Display z Use the Saturation Recovery Function
z Preset Function Press the [SET] button while pressing the [MODE] button to enable the saturation recovery
function.
With light ON, press the [PRESET] button. The current value is set to "". The light transmission level and light intensity gain are calibrated automatically.
Pressing the [PRESET] button changes the setting and current value as shown below.
Set the light intensity to
• Presetting with preset disabled: within the range in the table below.
The setting is changed to "". The setting can be changed via the normal calibration
method.
Power mode Light intensity setting range
• Presetting with preset enabled:
HSP, FINE, TURBO 2047 r 350
Only the current value is changed to "", and the setting is not changed.
SUPER 4095 r 500
Note • The preset function cannot be used together with the zero shift func- ULTRA, MEGA 5000 r 600
tion. To use the zero shift function, you must first disable the preset
function.
• This is not suited to transparent workpieces and other cases of detec- z Disable Saturation Recovery
tion with low light shielding. When the saturation recovery function is enabled, press the [SET] button while pressing the
[MODE] button to cancel it.
z Disable the Preset Function
Note Handy Uses for the Saturation Recovery Function
Press and hold the [PRESET] button to disable the preset function.
This function is handy when the fiber unit becomes saturated after installation.
When the preset function is disabled, the ratio of the setting and current values is main-
This eliminates the saturation via a simple operation, by automatically calibrat-
tained as-is. Tip
ing the light transmission level and light intensity gain.
Expansion
z Disable the Zero Shift Function protective cover
Press and hold the [PRESET] button to disable the zero shift function. Expansion connector
MODE button (MODE)
Note Handy Uses for the Zero Shift Function Preset button (PRESET)
This function is mainly used to set the current value to "0" on a reflective
model fiber unit. Cable*2 Power select switch*1
Tip
Dust cover
When a reflective model is first installed, the light intensity is sometimes not
set to "0".
If this happens, using the zero shift function to set the value to "0" when there
is no workpiece allows for easier understanding of the difference in light inten- *1 Setting to "M" locks the power mode to MEGA mode. The two output type is a channel
sity. switch.
*2 On the FS-N10Cx, this is an M8 connector rather than a cable. On the FS-N10Ex, this is an
e-CON connector.
3
Downloaded from www.Manualslib.com manuals search engine
Connecting to External Devices Initializing the Settings
Protection
Pink
circuit
impedance
Orange 10 Ω or more
Overcurrent
protection
Load PLC, etc.
DC5−30 V
circuit
*1 FS-N11N/N11MN/N13N only
*2 FS-N11MN only Press and hold for 3 seconds or more
*3 The FS-N13N/N14N has a white cable as separate output 2.
2 Use the to select "456", then press the [MODE] button.
FS-N11P/N12P/N13P/N14P/N13CP/N14CP 3 Use the to select "K0K6", then press the [MODE] button.
Output Circuit Diagram Input Circuit Diagram (FS-N13P/N14P only) After initialization is complete, the display returns to the current value.
DC12−24 V
z
Brown
Brown 1*1
DC12−24 V
Initial Settings
Sensor main circuit
PLC, etc.
Overcurrent
Black 4*2
Load
Setting Initial Value
(Control output)
Pink
Blue 3*1 (Short-circuit
current 2 mA
Power mode FINE
0V or less)
Detection mode Normal
2 4
Setting value 50
M8 connector Pin layout 1 3
2
Sensor main circuit
4
Load DC5−30 V
1 Bring down the blade in a single,
Overcurrent
2 4
1
M8 connector Pin layout 1 3 e-CON connector Pin layout Always insert fiber from the end with writing
*FS-N11CN/N11EN only
Cautions for Using a Fiber Cutter
FS-N11CP/N12CP
Failure to heed the cautions below could reduce the detection range.
Output Circuit Diagram Input Circuit Diagram
1* DC12−24 V
DC12−24 V 1*
• When cutting a fiber unit to be attached to the FS-N10 series, be sure to use a gray fiber cut-
Sensor main circuit
ter (OP-87098)
PLC, etc.
• Stopping the blade midway could cause a bad cut plane, reducing the detection range.
Overcurrent
Function Configuration
2 4
OP-73864 Connected
pin No.
Core wire
cover color
6WT$ Turbo mode
(Cable length: 2 m)
3
4 2
1
1 Brown 5W24 Super mode
7.64
OP-73865 2 White
(Cable length: 10 m) Ultra mode
3 Blue
4 Black /')# MEGA mode
Error Displays and Corrective Actions 5'6 5VF Normal sensitivity setting method
MODE
5'6 5'V2 Percentage Calibration*1
5V) 5;5
detection is required.
Go to system setup mode
MODE
*1 You can press the button to set between the range of 2 to 2.
4
Downloaded from www.Manualslib.com manuals search engine
Detection Settings System Settings
5V) (W0E MODE
5V) 5;5 MODE
Q((& #2% QP
MODE MODE
Off-delay timer *1 Enable APC
&'VE &V/
MODE
DATUM1 mode *2
&'VE &V/ DATUM2 mode *2 )#KP 5VF Standard current value display
)CKP (W..
MODE
Maximum current value display
&'VE #4'# Area detection mode (4 times hysteresis)
KP .Q(( Transmission OFF input 5V) &KU2 Go to original display setup mode
KP 2#75 Pause mode transition input *3 5V) 5;5 Return to system setup mode
MODE
#66 Light emission power selection *4 *1 Main unit only.
Two Output *2
*7 #P.) Analog scaling *5
MODE
EJ 5VF Light intensity detection mode
EJ #.TV
Return to normal display
Warning output mode
MODE
*1 Press the button to set between the range of and (ms).
6Q((
MODE
*2 Press the button to set the retouch sensitivity to a range of between .'W and .'W Timer OFF
and set the warning output level to a range of between 12 and 2.
Q((& Off-delay timer *1
MODE
MODE
*3 Press the button to toggle between Q((/Q0/-''2.
*4 Can be set between the range of and . Q0& On-delay timer *1
*5 Can be set between the range of and .
*6 Only external input types (FS-N11CN/N11CP/N11EN/N12EN/N13N/N13P/N14N/N14P).
5JQ6 One-shot timer *1
5W$56&'
MODE
Extension display
24* QP
Enable the saturation of the
Preset function *2
24* Q((
MODE Disable the saturation of the
Preset function
5
Downloaded from www.Manualslib.com manuals search engine
Specifications
Type Monitor
Standard 1 output High functionality 2 output
output
Main unit/sub unit Sub unit Sub unit Sub unit Sub unit Sub unit
Main unit (with output Main unit (with output Main unit (with output Main unit Main unit (with output Main unit (with output
cable) cable) cable) cable) cable)
Model NPN FS-N11N FS-N12N FS-N11CN FS-N12CN FS-N11EN FS-N12EN FS-N11MN FS-N13N FS-N14N - -
Control output 1 output 1 output 1 output 1 output 1 output 1 output 1 output 2 output 2 output 2 output 2 output
Control NPN output NPN open collector 30 V; 1 output max: 100 mA or less; 2 output total:
output 100 mA or less (used stand-alone)/20 mA or less (multiple connections); residual voltage 1 V or less
PNP output PNP open collector 30 V; 1 output max: 100 mA or less; 2 output total:
100 mA or less (used stand-alone)/20 mA or less (multiple connections); residual voltage 1 V or less
Monitor output 1 to 5 V voltage output; load resistance 10 k: or more; repeat precision r 0.5% of F.S.; responsiveness 1 ms (FS-N11MN only)
Number of interference
0 for HSP; 4 for FINE; 8 for TURBO/SUPER/ULTRA/MEGA (When set to double, the number of interference-prevention units will be doubled.)
prevention units
Environme Operating
ntal ambient Incandescent lamp: 20,000 lx or less; Sunlight: 30,000 lx or less
resistance luminance
Operating
ambient -10 to +55 q
C (no freezing)*3
temperature
Operating
ambient 35 to 85% RH (no condensation)
humidity
Vibration
10 to 55 Hz Compound amplitude 1.5 mm, 2 hours for each of X,Y,Z axis
resistance
Shock
500 m/s2 3 times for each of X,Y,Z axis
resistance
Weight Approx 75g Approx 45g Approx 22g Approx 22g Approx 22g Approx 22g Approx 75g Approx 80g Approx 70g Approx 22g Approx 22g
*1 Use a cable length of 30m or less for M8 connector and e-CON connector types.
*2 Increases 100 mW (4.0 mA) for High Speed mode
*3 One or two more units connected: -10 to +55 q C; 3 to 10 more units connected: -10 to +50q C; 11 to 16 more units connected: -10 to +45q
C. When using 2-outputs, one unit is counted as two units.
All temperature regulations are for when the unit is mounted on a DIN rail and installed on metal sheeting.