PIX System Configuration en
PIX System Configuration en
>> PIX
up to 24 kV
Air-insulated switchgear with
vacuum circuit-breaker
system configuration
AReVA T&D
Delivery conditions
The General Conditions of Delivery as amended shall apply.
Illustrations
The illustrations are not binding.
>>
Contents
INTRODUCTION
Overview 4
Product description
Technical Description 6
Construction 6
Locks 8
STANDARDS
Regulations, provisions and Standards 10
TECHNICAL DESCRIPTION
Functional unit 12
HVX CB drawout module 13
Spring drive for HVX 14
Equipment 15
CVX drawout contactor module 16
CBX electromagnetic operating mechanisme 17
Equipment 17
UTX drawout disconnecting link module 18
MTX drawout VT‘s module 18
LTRI air switch disconnector 18
Product range
Product range 19
Equipment range 20
DESIGN DATA
PIX 12 23
PIX 17 24
PIX 24 25
Dimensions and layout 26
Cable connections 27
Accessories 28
SHIPPING INFORMATION
Delivery, packaging 29
3
>> Overview
4
Easy operation and
maintenance
> Operation is simple and logical,
with clear status indicators for all
functions.
> Manual or electrical control
> The use of digital control and
protection equipment with self-
testing and monitoring proce-
dures.
Environment
PIX system has been conceived
with due consideration of its
impact on the environment:
> In a factory certified to
ISO 14001
> With a construction allowing
maximum recyclable compo-
nents at the end of product life.
5
>> Product description
are extensible on both sides and been removed, each shutter can
consist of modular functional units, be padlocked individually.
linked by a busbar, and connected
to the substation earth via an ear- With the interlocking shutters
thing bus. option, the independant opening
of the upper or lower shutter is
The cubicles are subdivided by only possible using a special tool
metal partitions into four separate (optionally supplied).
compartments, including a low vol-
tage compartment for the control > An earthing device for the
and monitoring equipment. removable module, to the IEC
The three Medium Voltage com- standards, ensures earthing
partments; bus bar, equipment continuity during removal, either
& cables, are fitted with an over- through rullers or through an
pressure release system, oriented optional plug.
towards the top of the unit inside
of cubicle volume. An inspection window on the door,
allows the position of the withdra-
The fused switch-disconnectors wable module to be clearly seen
are fixed type in the compartimen- within the compartment.
ted unit.
Operating panel The PIX system also offers,
amongst the range of withdrawable
Main module compartment modules, the functions of discon-
Closed off by a door, this compart- necting link, voltage transformers
ment contains: and busbar earthing switch.
> A withdrawable module, fitted
with a circuit breaker or con- This compartment is fitted with
tactor, which has two positions, mechanical locking devices in
“plugged in” or “disconnected/ accordance with IEC standards,
test”. which are necessary to avoid any
unsafe operations.
All operations of the withdrawable (For details, see the chapter on
module and its associated equip- locks).
ment can be carried out with the
compartment door closed.
6
Cable compartment VDS type voltage indicators Low voltage compartment
Normally closed with a bolted (IEC 612345) can be offered as an This compartment contains all the
panel, accessible from the front option. secondary circuit functions for
panel, and with a removable hori- control, measurement, protection,
zontal panel between the cable & Details of the interlocks are given monitoring, communication and
main module compartment, this in the next chapter. other associated systems.
Busbar compartment
Located in the upper, rear of the
unit, this compartment is accessi-
ble via the top or front panel of the
cubicle, after removing the parti-
tions, which separate it from the Low voltage compartment standard.
HVX compartment without insula-
switchgear compartment.
ting protection plate
The bus bar consists of flat copper
with rounded edges. The rated cur-
design is made for ease of assem- rent will determine the number of
bly and on-site testing of cables bars to be mounted in parallel.
and accessories. The bus bar is linked and suppor-
ted by solid connections to the
As an option, and depending on spouts.
the installation of switchboard cho-
sen, the rear panel can be made
removable, to further improve
access.
7
Locks
The operation of PIX is designed
to be completely safe. All the ope-
rations listed below are carried out
from the front panel, with the door
and panels closed.
> Connect or disconnect the with-
drawable module.
> Re-load the spring mechanism.
> Mechanically close or open the
circuit breaker or switch-discon-
nector.
> Open or close the earthing
switch. Access to the withdra-
wable module compartment
requires the use of a specialised
handle and key.
The interlocks were designed
with this operational ideology in
mind and add to the security of
the system by making it impossi-
ble to make unsafe operations.
8
PIX iN Detail
13
2 12
3
11
10
4
9
8
5
7
1 LV compartment standard
2 Circuit breaker
3 Switchgear compartment door
4 Earthing switch operating
mechanism
5 Voltage presence indicator
6 E.S. mimic digram
7 Cable compartment panel
8 Voltage transformer
9 Current transformer
10 Cable connection Earthing switch drive
11 Earthing switch
12 Metal shutter for cable
13 Spouts
14 Metal shutter for busbar
15 Busbar
9
>> Standards
Regulations, provisions and standards
Certified safety
Certified safety due to tests
due to tests
Applied standards
10
Operating conditions
Protection degree
Standard degree of protection of the Meaning for the protection Meaning for the protection
external enclosure: IP 3X of equipment ofpeople
Optionally, there is the possibility of
various IP, ratings in accordance with
the table below.
Elements of code IP 1st element 2nd element Additional element
Protection against water ingress with 2 > = 12.5 mm Not used element covered
harmful effects 3 > = 2.5 mm by 1st element
4 > = 1 mm
X Not defined
0 Not protected
1 Vertical dripping
water
2 Dripping water with
15° inclination
X Not defined
Protection against access to the dangerous parts by means of tools C D = 2.5 mm
L = 100 mm
D D = 1 mm
L = 100 mm
X Not defined
11
>> Technical data
Functional unit
TECHNIcal INFORMATIONs
12
HVX drawout circuit breaker module - Characteristics
13
HVX spring operating mechanism
14
Equipment
15
CVX drawout contactor module - Characteristics
16
CBX electromagnetic operating mechanisms
Designation
Reference standards IEC IEC
DC AC
Rated supply voltage V 24-48-60-110-125-220 120-230
Rated frequency Hz 50/60
Magnetic holding control circuit
Voltage range for closing % of Un > 85 > 85
Voltage range for opening % of Un 75 to 10 75 to 10
Power consumption on closing W / VA 615 615
Power consumption on holding W / VA 150 150
Mechanical latch control circuit
Voltage variation range % of Un 70 to 110 85 to 110
Power consumption on closing W / VA 615 615
Power consumption on opening W 240 240
Minimum impulse duration ms 20 20
Auxiliary contacts:
Rated current A 15 15
Breaking capacity 48 Vdc (L/R 10 ms)
Breaking capacity 220Vdc (L/R 20 ms)
Equipment
17
UTX drawout disconnecting link module
18
>> Range of equipment
Product range
Bus section with Bus riser with Direct incoming Busbar voltage Busbar voltage Busbar current
circuit breaker transformers metering with metering metering
earthing switch
19
Equipment range
On request:
- VT’s with fuses
- Withdrawable cable VT’s
with removable fuses
- Fixed VT’s without fuses (1)
- Surge arresters
(1)
On request:
- VT’s with fuses
- Withdrawable cable VT’s
with removable fuses
- Fixed VT’s without fuses (1)
- Surge arresters
(1)
On request:
- Surge arresters
20
> Bus section unit with circuit
breaker up to 2000 A
On request:
- Busbar earthing switch (1)
(1)
On request:
- Busbar earthing switch (1)
(1)
On request:
- Withdrawable VT’s module with
fuses (1).
- Current transformers (2)
(1)
(2)
On request:
- Withdrawable VT’s module with
fuses (1).
- Current transformers (2)
(1)
(2)
21
> Direct incoming unit up
to 3150 A.
On request:
- Surge arresters
- Fixed VT’s with fuses
- Fixed VT’s without fuses
- VT’s removable fuses.
On request:
- Busbar earthing switch (1)
(1)
On request:
- Current transformers
22
>> Design data
pix 12
A1
Door 2500
Min. 3130
B1 B1
= =
75.5
A2 4
A
C
3
440
2
75.5
75.5
ø 12.5
B
200
492
383
74
126
1000
40
50
28.5 28.5
In Approximate C1
Incoming or outgoing
B1 B1
= =
CB ≤ 1250 650 800 720
Disconnect link 650 (1)
C
3
440
1
75.5
383
74
650 (1)
40
Dimensions in mm - (1) Depth 1605 for internal arc withstand 40 kA * Height with forced cooling or
with width 650 mm duct for gas evacuation.
- (2) Depth 1605 for 2 CT/phase
For seismic and arrangement on skid please contact us.
23
pix 17
Width 750 mm
B = 210
35
B 35
Mini 100 C 1500 Mini
C1
A1
Door 2500
Mini 3200
B1
=
B1
=
75.5
A2 4
A
C
3
440
2
75.5
75.5
B
ø 12.5
200
540
435
74
126
1000
40
50
28.5 28.5
C1
In Approximate
(A) B (width) weight (kg)
Incoming or outgoing
B1
=
B1
=
CB ≤ 1600 750 750 (1) 850
Disconnect link 2000 750 750 (1) 850
C
3
440
Bus section ≥ 2500 1000 1000 850 2
200
540
435
≥ 2500 1000 1000 780
74
126
Bus riser
40
24
pix 24
Width 800 mm
B = 210
35
B 35
Mini 100 C 1500 Mini
C1
A1
Door 2500
Mini 3330
B1
=
B1
=
75.5
4
A
C
3
440
2
75.5
75.5
B
ø 12.5
200
542
433
74
126
1000
40
50
28.5 28.5
C1
In Approximate
(A) B (Width) weight (kg)
Incoming or outgoing
B1
=
B1
=
CB ≤ 1600 800 800 820
75.5
C
3
440
Bus section ≥ 2500 1000 1000 870 2
Direct incoming
75.5
433
126
Bus riser
40
*
Height:
= 2730 with duct for gas evacuation.
= 2890 with deflectors for internal arc
withstanding.
25
Floor Plan
ground ground
bus bus
6 mm max.
2 mm max.
Cubicles
1m
Detail A
820
870
670
720
770
26
>> Cable connections
L (cable end)
L1 maxi
L2 maxi
X
Adjustment 50 mm +5
-5
L4 maxi
L3 maxi
X
108
12
27
>> Accessories
Designation Illustration
28
>> Shipping instructions
Delivery Packaging
> For transportation by lorry:
Delivery The product is fixed to a wooden
The cubicles, which make up the pallet and protected by plastic
switchboard are delivered individu- cover.
ally, ready for assembly. The front panel is protected by
The connection should be carried polystyrene panels.
out on-site.
> For transportation by sea:
The product is covered with a
plastic heat welded cover, with
desiccant materials, then instal-
led into a wooden case.
29
Notes:
30
AREVA Energietechnik GmbH, Sachsenwerk Mittelspannung
Rathenaustraße 2 · D-93055 Regensburg · P.O.B. 10 01 55 · D-93001 Regensburg
Phone +49 (0)9 41/46 20-0 · Fax +49 (0)9 41/46 20-4 18
www.areva-td.com
Tel.: +44 (0) 1785 250 070
AREVA T&D Worldwide Contact Centre:
http://www.areva-td.com/contactcentre/
AREVA Energietechnik GmbH - Sachsenwerk Mittelspannung - AGSIEXXXX-01-1008 - © - AREVA - 2008. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA