AIR INsULATeD swITCHgeAR

>> PIX
up to 24 kV
Air-insulated switchgear with
vacuum circuit-breaker

system configuration

AReVA T&D
Delivery conditions
The General Conditions of Delivery as amended shall apply.

Illustrations
The illustrations are not binding.
>>
Contents

INTRODUCTION
Overview 4

Product description
Technical Description 6
Construction 6
Locks 8

STANDARDS
Regulations, provisions and Standards 10

TECHNICAL DESCRIPTION
Functional unit 12
HVX CB drawout module 13
Spring drive for HVX 14
Equipment 15
CVX drawout contactor module 16
CBX electromagnetic operating mechanisme 17
Equipment 17
UTX drawout disconnecting link module 18
MTX drawout VT‘s module 18
LTRI air switch disconnector 18

Product range
Product range 19
Equipment range 20

DESIGN DATA
PIX 12 23
PIX 17 24
PIX 24 25
Dimensions and layout 26

Cable connections 27

Accessories 28

SHIPPING INFORMATION
Delivery, packaging 29

3
>> Overview

The PIX series switchgear panels Features


tHe systeM WitH tWo sWitCHiNG teCHNoloGies

are air-insulated, type-tested and > Air-insulated, metal-clad


metal-clad. switchgear
AREVA switchgear technology - with three compartments
satisfies the international requi- - compartmentalization class PM
rements for energy distribution in > Loss of service continuity
medium-voltage grids and is espe- category in accordance with
cially suited for application in: IEC 62271-200
> Industry > LSC 2B
> Distributed Power > IAC qualification (optional) in
> Oil & gas accordance with IEC 62271-200/
> Power plants DIN EN 62271-200
> Shipbuilding > Truck-type switching devices
> Infrastructure - for vacuum circuit-breaker
- for SF6 circuit-breaker
The modular PIX switchgear covers > Truck-type design
a wide range of ratings for: - of vacuum contactor
> rated voltages of 12 kV, 17.5 kV, - of metering truck
24 kV - of isolating truck
> rated currents up to 4000 A
> rated short-time currents Operator Safety
Safe operation with the panels and up to 40 kA
doors closed > All operations are performed with
> rated peak withstand currents the front or door closed.
up to 100 kA. > Make-proof earthing switch can
be checked via inspection glass.
Thanks to its modular design, the > Actuation of earthing switch with
truck-type switchgear PIX is an anti-kickback device.
especially compact switchgear > Reliable interlocks
system. By offering a switchgear > Pressure relief directed upwards
technology with highly flexible > Closed metal shutters with the
equipment-fitting options, PIX truck module in disconnected or
provides a comprehensive, eco- outside position
nomical range of functional units > Voltage indicator for each phase
for all switchgear-related require-
ments.

4
Easy operation and
maintenance
> Operation is simple and logical,
with clear status indicators for all
functions.
> Manual or electrical control
> The use of digital control and
protection equipment with self-
testing and monitoring proce-
dures.

Easy installation and access


> PIX was designed to minimize
the space required, with access
to all compartments via the front
panel.
> Can be installed against a wall.
> Connection of the cables via the
front is made easier by removing
the separating plate between the
cable and apparatus compart-
ments. Optionally, the rear panel
can be made removable.
> Rigid, self-supporting construc-
tion.

Environment
PIX system has been conceived
with due consideration of its
impact on the environment:
> In a factory certified to
ISO 14001
> With a construction allowing
maximum recyclable compo-
nents at the end of product life.

5
>> Product description

The PIX metal-clad switchboards Once the withdrawable module has


air iNsulated sWitCHGears

are extensible on both sides and been removed, each shutter can
consist of modular functional units, be padlocked individually.
linked by a busbar, and connected
to the substation earth via an ear- With the interlocking shutters
thing bus. option, the independant opening
of the upper or lower shutter is
The cubicles are subdivided by only possible using a special tool
metal partitions into four separate (optionally supplied).
compartments, including a low vol-
tage compartment for the control > An earthing device for the
and monitoring equipment. removable module, to the IEC
The three Medium Voltage com- standards, ensures earthing
partments; bus bar, equipment continuity during removal, either
& cables, are fitted with an over- through rullers or through an
pressure release system, oriented optional plug.
towards the top of the unit inside
of cubicle volume. An inspection window on the door,
allows the position of the withdra-
The fused switch-disconnectors wable module to be clearly seen
are fixed type in the compartimen- within the compartment.
ted unit.
Operating panel The PIX system also offers,
amongst the range of withdrawable
Main module compartment modules, the functions of discon-
Closed off by a door, this compart- necting link, voltage transformers
ment contains: and busbar earthing switch.
> A withdrawable module, fitted
with a circuit breaker or con- This compartment is fitted with
tactor, which has two positions, mechanical locking devices in
“plugged in” or “disconnected/ accordance with IEC standards,
test”. which are necessary to avoid any
unsafe operations.
All operations of the withdrawable (For details, see the chapter on
module and its associated equip- locks).
ment can be carried out with the
compartment door closed.

For modules fitted with vacuum


circuit breakers, the movement can
be motorised.

Withdrawable modules of the same


type are interchangeable.

The connection between the with-


drawable module, the busbar and
the cable branches is made by
means of withdrawable silver pla-
ted contacts.

A 64-pin plug (Max.) connects the


auxiliary circuits of the withdra-
wable module to the low voltage
compartment.
Main module compartment.
> For personnel safety, there are
metallic shutters (1), installed in
front of the spouts of the fixed
“plug-in” contacts (2), which
prevent access to the primary
circuit, thus ensuring a protection
when the withdrawable module is
either in the “disconnected/test”
position or removed from the
compartment.

6
Cable compartment VDS type voltage indicators Low voltage compartment
Normally closed with a bolted (IEC 612345) can be offered as an This compartment contains all the
panel, accessible from the front option. secondary circuit functions for
panel, and with a removable hori- control, measurement, protection,
zontal panel between the cable & Details of the interlocks are given monitoring, communication and
main module compartment, this in the next chapter. other associated systems.

This independent compartment, is


a separate assembly, supplied fully
assembled and tested.

Cable connection compartment

Busbar compartment
Located in the upper, rear of the
unit, this compartment is accessi-
ble via the top or front panel of the
cubicle, after removing the parti-
tions, which separate it from the Low voltage compartment standard.
HVX compartment without insula-
switchgear compartment.
ting protection plate
The bus bar consists of flat copper
with rounded edges. The rated cur-
design is made for ease of assem- rent will determine the number of
bly and on-site testing of cables bars to be mounted in parallel.
and accessories. The bus bar is linked and suppor-
ted by solid connections to the
As an option, and depending on spouts.
the installation of switchboard cho-
sen, the rear panel can be made
removable, to further improve
access.

This compartment contains:


> The connections to the power
cables, up to 6 x 630 mm2 per
phase, with a choice of bottom
plate (for details, see chapter on
cable connections).
> The cable earthing switch is
operated from the front of the
cubicle by means of a removable
lever.
Its position is visible from the
front panel, through the inspec­
tion window in the cable panel.
> Current transformers, with DIN
dimensions, are fitted at the rear
of the cubicle.
> The voltage transformers, fitted
at the front of the compartment,
are either fixed - with or without
Busbar compartment
fuses, or removable with fuses.
> A metallic cable duct, located on
the right-hand lateral part, guides Optionally, this compartment can
the low voltage conductors into be fitted with:
the control/command compart- > Segregations made of insulating
ment safely. materials, resistant to pressure,
mounted between each cubicle.
At the front, upper section of this > Insulation of the bus bars and
compartment, is the access to the branch connections.
earthing switch controls, along with > Fixed voltage transformers,
its mimic diagram and VPIS type without fuses.
voltage indicators (IEC 61958). > An earthing switch.

7
Locks
The operation of PIX is designed
to be completely safe. All the ope-
rations listed below are carried out
from the front panel, with the door
and panels closed.
> Connect or disconnect the with-
drawable module.
> Re-load the spring mechanism.
> Mechanically close or open the
circuit breaker or switch-discon-
nector.
> Open or close the earthing
switch. Access to the withdra-
wable module compartment
requires the use of a specialised
handle and key.
The interlocks were designed
with this operational ideology in
mind and add to the security of
the system by making it impossi-
ble to make unsafe operations.

Actions Status of elements involved


Basic locking devices Optional locking devices
Plugging in the module - LV socket connected - Module compartment access
- Circuit breaker open door closed
- Earthing switch open
Closing the circuit breaker/contactor - Module completely plugged in, or
plugged out/test position
- Plug-in lever removed
Closing the earthing switch - Module plugged in/out/test posi-
tion or removed
Access to the cable compartment - Earthing switch closed
Opening of the earthing switch - Cable compartment panel closed
Access to the withdrawable module- (Reminder: requires the use of a - Module in disconnected plugged-
compartment specific key and handle) out/test
Partial re-opening of the earthing - Is not possible to put the breaker
switch for cable testing module into the panel again when
the earthing switch is in this
position
Opening of the shutters - By the withdrawable module
action
- With specific tool.

Other safety equipment

Basic locking devices Optional locking devices


Locking device using padlocks - Shutters
- Earthing switch access (in open
or closed position)
- No access to operate the drawout
module
Locking devices (specific) - ON/OFF Buttons - Circuit breaker
Locking device using fixed locks - The door of the withdrawable
module
- Earthing switch, either in open or
closed position
- Module in plugged out position
Locking device by electromagnetic - Earthing switch, in open position
coil - Disconnect link module (UTX)

8
PIX iN Detail

13

2 12
3

11

10

4
9

8
5
7

1 LV compartment standard
2 Circuit breaker
3 Switchgear compartment door
4 Earthing switch operating
mechanism
5 Voltage presence indicator
6 E.S. mimic digram
7 Cable compartment panel
8 Voltage transformer
9 Current transformer
10 Cable connection Earthing switch drive
11 Earthing switch
12 Metal shutter for cable
13 Spouts
14 Metal shutter for busbar
15 Busbar

Operating panel Earthing switch indicator

9
>> Standards
Regulations, provisions and standards

Certified safety
Certified safety due to tests

due to tests

The PIX panels were developed on


the basis of international standards
(IEC) and validated for type tests
which are performed in acknow-
ledged laboratories.

Applied standards

Series PIX switchgear units with


vacuum switching devices are
> metal enclosed;
Loss of service continuity
category in accordance with
IEC 62271-200: LSC 2B-PM
> type-tested
> optional: tested for internal faults
(qualification IAC)
> dimensioned for indoor instal-
lation

PIX switchgear units meet the following standards and regulations:

Designation IEC standard EN standard


IEC 62271-1
Switchgear
IEC 62271-200 EN 62271-200
Circuit-breaker IEC 62271-100 EN 62271-100
Vacuum contactor IEC 60470 EN 60470
Earthing switch IEC 62271-102 EN 62271-102
Isolating truck IEC 62271-102 EN 62271-102
Current transformers IEC 60044-1 EN 60044-1
Voltage transformers IEC 60044-2 EN 60044-2
IEC 61243-5 EN 61 243-5
Voltage Detecting Systems
IEC 61958 EN 61958
Protection against accidental contact, IEC 60529 EN 60529
foreign bodies and water
Erection IEC 61936-1 HD 637 S1
Operation of electrical equipment - EN 50110-1
Switch fuse combination IEC 60265-1 EN 60265-1

10
Operating conditions

Operating conditions for interior use, in accordance with IEC 60694


Ambient temperature - + 40°C
- maxi + 55°C with corresponding under-rating current
- + 35°C on average over a 24 hour period
- - 5°C minimum
Ambient air - No impurities due to dust, flammable/corrosive gases & vapours, smoke
or salt.
Humidity - Average relative humidity over a 24 hour period: 95%
- Average steam pressure over a 24 hour period: Max. 2.2 kPa
- Average relative humidity over a 1 month period: 90%
- Average steam pressure over a 1 month period: Max. 1.8 kPa
Altitude - Up to 1,000 m above sea level, corresponding to atmospheric
conditions of: 1013 hPa, + 20 °C, 11g/m3 water.
- Above 1,000 m, a derating factor is applied, please contact us for details.
Vibration - Negligible
- For particular conditions, please contact us.

Protection degree

Standard degree of protection of the Meaning for the protection Meaning for the protection
external enclosure: IP 3X of equipment ofpeople
Optionally, there is the possibility of
various IP, ratings in accordance with
the table below.
Elements of code IP 1st element 2nd element Additional element

Protection against water ingress with 2 > = 12.5 mm Not used element covered
harmful effects 3 > = 2.5 mm by 1st element
4 > = 1 mm
X Not defined
0 Not protected
1 Vertical dripping
water
2 Dripping water with
15° inclination
X Not defined
Protection against access to the dangerous parts by means of tools C D = 2.5 mm
L = 100 mm
D D = 1 mm
L = 100 mm
X Not defined

11
>> Technical data
Functional unit
TECHNIcal INFORMATIONs

Designation PIX 12 PIX 17 PIX 24


Reference standards IEC 60298 IEC 60298 IEC 60298
Rated voltage kV rms 12 17.5 24
Power frequency withstand voltage 50 Hz 1 min
to earth and between phases kV rms 28 38 50
on the isolating distance kV rms 32 45 60
Impulse withstand voltage 1,2 / 50 micro sec
to earth and between phases kV peak 75 95 125
on the isolating distance kV peak 85 110 145
Rated frequency Hz 50 / 60 50 / 60 50 / 60
Short time current
1 sec withstand (2) kA rms 25 / 31.5 / 40 25 / 31.5 /40 16 / 25 / 31.5
3 sec withstand (2) (1) kA rms 25/ 31.5 / 40 25 / 31.5 / 40 16 /25 / 31.5
Peak withstand kA rms 63 / 80 / 100 63 / 80 / 100 40 / 63 / 80
Rated current
Busbar with natural ventilation A Up to 3150 Up to 3150 Up to 2500
Busbar with forced ventilation A Up to 4000 Up to 4000
Functions Disconnect link A Up to 3150 Up to 3150 Up to 2500
Functions CB with natural ventilation A rms Up to 3150 Up to 3150 Up to 2500
Functions CB with forced ventilation A rms Up to 4000 Up to 4000
Functions SWD A rms 630 630 630
Functions Air SWD + fuses A rms 400 400 400
Functions Contactor A rms 200-400
Internal arc withstand kA Up to 40 kA - 1 sec Up to 40 kA - 1sec Up to 31.5 kA - 1sec
Earthing switch making capacity (2) kA peak 63 / 80 / 100 63 / 80 / 100 40 / 63 / 80
Earthing switch endurance
number of making operation 2 2 2
mechanical (C/O) 1000 1000 1000
Degree of protection
external enclosure standard IP 3X IP 3X IP 3X
open door without withdrawable module IP 2X IP 2X IP 2X
Approximate heat dissipation
Functions CB Ir = 800A W 650 650 650
Force on floor (without cubicle weight)
Functions CB daN 750 750 750
(1)
Earthing switch limited 40 kA - 1sec
(2)
For SWD and SWD + fuses functions
Short time current
1 sec withstand kA rms 16 / 25 16 / 25 16 / 25
peak withstand kA peak 40 / 63 40 / 63 40 / 63
Earthing switch making capacity kA peak 40 / 63 40 / 63 40 / 63

For 50 kA, 5000 A, please refer to PIX-H documentation or contact us.

12
HVX drawout circuit breaker module - Characteristics

For the cubicles PIX 12 PIX 17 PIX 24


Designation HVX 12 HVX 17 HVX 24
Reference standards IEC IEC IEC
Rated voltage kV 12 17.5 24
Rated current A rms Up to 3150 Up to 3150 Up to 2500
Rated breaking capacity
short circuit current kA rms 16/25/31.5/40 25/31.5/40 16/25/31.5
cable charging current A 25 31.5 31.5
line charging current A 10 10
single capacitor bank A 400 400
no load transformer A 10 10
Rated making capacity kA peak 40/63/80/100 63/80/100 40/63/80
Rated operating time
opening ms 40-47 40-47 40-47
breaking ms 55-62 55-62 55-62
arcing ms 2-15 2-15 2-15
closing ms 50-58 50-58 50-58
Rated operating sequence O-3min-CO-3min-CO O-3min-CO-3min-CO O-3min-CO-3min-CO
CO-15s-CO CO-15s-CO CO-15s-CO
O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO
Endurance
mechanical (C/O) for
30 000 30 000 30 000
switching chamber
mechanical (C/O) for
10 000 10 000 10 000
mechanism
electrical (C/O at In up to
10 000 10 000 10 000
3150 A)

13
HVX spring operating mechanism

Designation FH2-01 (hand) / FK2-01 (motor)


Reference standards IEC IEC
DC AC
Rated supply voltage (1) V 24-48-60-110-125-220 120-230
Rated frequency Hz 50/60
Reset motor
Voltage variation range % of Un 85 to 110 85 to 110
Power consumption (maxi) W / VA 100 100
Starting current A
Reset time s 8-12 8-12
Shunt opening coil
Voltage variation range % of Un 70 to 110 70 to 110
Power consumption (maxi) W / VA ≤ 250 ≤ 250
Minimum impulse duration ms 50 50
Under voltage opening coil
Voltage range for closing % of Un >85 >85
Voltage range for tripping % of Un 35 to 0 35 to 0
Power consumption (maxi) W/VA 10 10
Shunt closing coil
Rated current % of Un 85 to 110 85 to 110
Power consumption maxi W/VA ≤250 ≤250
Auxiliary contacts
Rated current A 15 15
Breaking capacity 48V (L/R 10ms) A 10 -
Breaking capacity 125V (L/R 10ms) A 4 -
Breaking capacity 220V (L/R 10ms) A 2 -
Breaking capacity 120 or 230 Vdc A - 10
(1)
No 125 Vdc for reset motor - No 220 Vdc and 120 Vac for under voltage opening coil.

14
Equipment

FH2-01 (hand) FK2-01 (motor)


Basic Optional Basic Optional
Manual opening and closing • •
CB Position indicators • •
Spring charging motor •
Spring position indicator • •
Shunt trip coil • •
Second shunt trip coil • •
CT operated release • •
Undervoltage shunt tripping coil • •
Closing coil •
Operation counter • •
Anti-pumping relay • •
Free auxiliary contacts
CB position 2NO / 2NC • •
3NO / 4 NC • •
Spring charged position 2NO / 1NC • •
For more information refer to HVX documentation t&d bprob/hvxb-24 kv/uke/pdb/04.01/ger/2854




HVX up to 2000 A HVX > 2000 A

15
CVX drawout contactor module - Characteristics

For the cubicles PIX 12 PIX 12


Designation CVX 07 CVX 12
Contactor designation CBX CBX
Reference standards IEC IEC
Category AC3 - AC4 AC3 - AC4
Rated voltage kV 7.2 12
Rated current A rms 400 400
Maximum motor rated current A 320 320
Rated breaking capacity
short circuit current with fuses kA rms 40 40
short circuit current without fuses kA rms 6 4
single capacitor bank A 280 280
Rated making capacity with fuses kA peak 100 100
Rated making capacity without fuses kA peak 15 10
Rated operating time
opening with d.c. magnetic holding control ms 60 to 100 60 to 100
opening with a.c. magnetic holding control ms 90 to 120 90 to 120
opening with mechanical latch control ms 20 to 30 20 to 30
closing ms 60 to 100 60 to 100
Rated operating sequence number per hour 1200 1200
Endurance
mechanical with magnetic holding (C/O) 3 000 000 3 000 000
electrical with mechanical latch (C/O) 200 000 200 000
electrical (C/O at 400 A) 500 000 500 000
electrical (C/O at 250 A) 1 000 000 1 000 000
electrical (breaking at Icc 3.2 kA) 25 25
electrical (making at Icc 4 kA) 100 100

CVX drawout contactor module CVX drawout contactor module on


truck

16
CBX electromagnetic operating mechanisms

Designation
Reference standards IEC IEC
DC AC
Rated supply voltage V 24-48-60-110-125-220 120-230
Rated frequency Hz 50/60
Magnetic holding control circuit
Voltage range for closing % of Un > 85 > 85
Voltage range for opening % of Un 75 to 10 75 to 10
Power consumption on closing W / VA 615 615
Power consumption on holding W / VA 150 150
Mechanical latch control circuit
Voltage variation range % of Un 70 to 110 85 to 110
Power consumption on closing W / VA 615 615
Power consumption on opening W 240 240
Minimum impulse duration ms 20 20
Auxiliary contacts:
Rated current A 15 15
Breaking capacity 48 Vdc (L/R 10 ms)
Breaking capacity 220Vdc (L/R 20 ms)

Equipment

Operating mechanism Magnetic holding Mechanical latch


Manual opening •
Contactor Position indicators • •
Magnetic holding coil •
Shunt trip coil •
Closing coil •
Operation counter • •
Anti-pumping relay • •
Free auxiliary contacts
Contactor position 3 NO / 3 NC • •
Fuse position 1 O/C • •
For more information refer to CBX documentation

17
UTX drawout disconnecting link module

Disconnect link 12 kV Disconnect link 24 kV

Auxiliary contacts for withdrawable module

Position HVX - UTX - MTX CVX


Basic Optional Basic Optional
Plugged in and test/unplugged
1 O/C (reverse) •
4 O/C (reverse) •
Plugged in
1 N/C •
1 N/C + 1 N/O •
2 N/C •
Unplugged/test
1 NC •
1 N/C + 1 N/O •
2 N/C •

Auxiliary contacts for earthing switch

Position Basic Optional


Close/Open 1 O/C (reverse) •
Closed 3 N/C •
Opened 3 N/C •

MTX drawout LTRI air switch-


VT’s module disconnector

MTX drawout VT‘s moduls LTRI Air Switch-Disconnector

18
>> Range of equipment

Product range

Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Outgoing with Contactor outgoing Switch disconnector


with circuit breaker with circuit breaker with circuit breaker disconnect link and fuses outgoing
+ fixed VT’s withdrawable cable
VT’s with removable
fuses

Bus section with Bus riser with Direct incoming Busbar voltage Busbar voltage Busbar current
circuit breaker transformers metering with metering metering
earthing switch

Busbar with voltage Busbar with earthing


transformer on switch on the top
the top

19
Equipment range

> Incoming or outgoing unit with


circuit breaker up to 2000 A.

On request:
- VT’s with fuses
- Withdrawable cable VT’s
with removable fuses
- Fixed VT’s without fuses (1)
- Surge arresters

(1)

> Incoming or outgoing unit with


circuit breaker 2500 to 3150 A.

On request:
- VT’s with fuses
- Withdrawable cable VT’s
with removable fuses
- Fixed VT’s without fuses (1)
- Surge arresters

(1)

> Outgoing unit with contactor and


fuses 200, 400 A.

On request:
- Surge arresters

20
> Bus section unit with circuit
breaker up to 2000 A

On request:
- Busbar earthing switch (1)

(1)

> Bus section unit circuit breaker


2500 to 3150 A

On request:
- Busbar earthing switch (1)

(1)

> Bus riser unit up to 2000 A.

On request:
- Withdrawable VT’s module with
fuses (1).
- Current transformers (2)
(1)

(2)

> Bus riser unit 2500 A to 3150 A.

On request:
- Withdrawable VT’s module with
fuses (1).
- Current transformers (2)
(1)

(2)

21
> Direct incoming unit up
to 3150 A.

On request:
- Surge arresters
- Fixed VT’s with fuses
- Fixed VT’s without fuses
- VT’s removable fuses.

> Busbar voltage metering

On request:
- Busbar earthing switch (1)

(1)

> Outgoing unit with switch


disconnector and fuses

On request:
- Current transformers

> Busbar voltage transformers


without fuses on the top

> Busbar earthing switch on the top

22
>> Design data

pix 12

Width 650 - 800 mm


B = 185 - 210
35
B 35
Min. 100 C 1500 Min.
C1

A1

Door 2500
Min. 3130
B1 B1
= =

75.5
A2 4
A

C
3

440
2

75.5
75.5
ø 12.5
B

200
492

383
74

126
1000

40
50

28.5 28.5

Functions PIX 12 up to 40 kA 4000A Width 1000 mm


B1 = 254
Icc B
(kA) ≤ 31.5 40 35 35

In Approximate C1

(A) B (width) weight (kg)

Incoming or outgoing
B1 B1
= =
CB ≤ 1250 650 800 720
Disconnect link 650 (1)
C

3
440

Bus section 1600 800 800 770 2

1
75.5

2000 1000 1000 770


75.5

≥ 2500 1000 1000 820 ø 12.5


200
492

383
74

Direct incoming ≤ 1250 650 800 650


126

650 (1)
40

1600 800 800 700 50

2000 800 800 750 28.5 28.5

≥ 2500 1000 1000 750


Bus riser 1250 650 650 600
Bus riser disconnect link 1600 800 800 650
2000 800 800 700
A: 2130 2230 2330
≥ 2500 1000 1000 700
A1: 530 630 730
Busbar voltage metering 650 650 600
A2: 2730*
Switch disconnector
650 - 600
and fuses outgoing C: 1405/1605 (1) (2)
Contactor 650 650 700 C1: 100/300

Dimensions in mm - (1) Depth 1605 for internal arc withstand 40 kA * Height with forced cooling or
with width 650 mm duct for gas evacuation.
- (2) Depth 1605 for 2 CT/phase
For seismic and arrangement on skid please contact us.

23
pix 17

Width 750 mm
B = 210
35
B 35
Mini 100 C 1500 Mini
C1

A1

Door 2500
Mini 3200
B1
=
B1
=

75.5
A2 4
A

C
3

440
2

75.5
75.5
B
ø 12.5

200
540

435
74

126
1000

40
50

28.5 28.5

Functions PIX 17 up to 40 kA 4000A Width 1000 mm


B1 = 254
Icc B
(kA) ≤ 25 31.5-40 35 35

C1
In Approximate
(A) B (width) weight (kg)

Incoming or outgoing
B1
=
B1
=
CB ≤ 1600 750 750 (1) 850
Disconnect link 2000 750 750 (1) 850

C
3

440
Bus section ≥ 2500 1000 1000 850 2

Direct incoming (1)


75.5

≤ 1600 750 750 730


75.5

2000 750 750 (1) 780 ø 12.5

200
540

435
≥ 2500 1000 1000 780
74

126
Bus riser
40

Bus riser disconnect link 1600 750 750 680 50

2000 750 750 730 28.5 28.5

≥ 2500 1000 1000 730


Busbar voltage metering 750 750 650 A: 2200 2300 2400
Switch disconnector A1: 600 700 800
and fuses outgoing 750 - 650
A2: 2800*
Dimensions in mm - (1) Depth 1605 for internal arc withstand 40 kA
- (2) Depth 1605 for 2 CT/phase
C: 1505/1605 (1) (2)
For seismic and arrangement on skid please contact us. C1: 100/200
* Up to 2800 with forced cooling or duct
for gas evacuation.

24
pix 24

Width 800 mm
B = 210
35
B 35
Mini 100 C 1500 Mini
C1

A1

Door 2500
Mini 3330
B1
=
B1
=

75.5
4
A

C
3

440
2

75.5
75.5
B

ø 12.5

200
542

433
74

126
1000

40
50

28.5 28.5

Functions PIX 24 up to 31.5 kA 2500A Width 1000 mm


B1 = 254
Icc B
(kA) ≤ 25 31.5-40 35 35

C1
In Approximate
(A) B (Width) weight (kg)

Incoming or outgoing
B1
=
B1
=
CB ≤ 1600 800 800 820
75.5

Disconnect link 2000 1000 1000 870 4

C
3

440
Bus section ≥ 2500 1000 1000 870 2

Direct incoming
75.5

≤ 1600 800 800 750


75.5

2000 800 800 800 ø 12.5


200
542

433

2500 1000 1000 800


74

126

Bus riser
40

Bus riser disconnect link ≤ 1600 800 800 700 50

2000 1000 800 750 28.5 28.5

2500 1000 1000 750


Busbar voltage metering 800 800 700 A: 2330 2430 2530*
Switch disconnector
800 - 700 A1: 530 630 730
and fuses outgoing
A2: 1605
Dimensions in mm
For seismic and arrangement on skid please contact us. C: 100

*
Height:
= 2730 with duct for gas evacuation.
= 2890 with deflectors for internal arc
withstanding.

25
Floor Plan

ground ground
bus bus

6 mm max.
2 mm max.

Cubicles

2 mm/m max. and


6 mm/total length of switchboard

1m

Detail A

PIX 12 PIX 17 PIX 24

100 100 100

Cubicle Cubicle Cubicle


770

820

870
670

720

770

Front Front Front

26
>> Cable connections

The manufacturer’s instructions


for the ends of the cables must be
followed.

L (cable end)
L1 maxi

L2 maxi
X

Adjustment 50 mm +5
-5

Cable glands in upper position Cable glands in lower position


L (cable end)

L4 maxi
L3 maxi
X

108

12

Assembly with DIN clamps Assembly with DIN clamps


Cable 95 mm2. Cables 300 - 630 mm2.

PIX 12 PIX 17 PIX 24


X 430 460 555
L1 390 420 515
L2 440 470 565
L3 290 320 415
L4 410 440 495

27
>> Accessories

Designation Illustration

Handle for opening and closing the front door

Double-bit key for the front door

Double-bit key for the low-voltage compartment

Crank to charge the circuit-breaker‘s energy-storing device

Operating rod to switch the circuit-breaker on and off

Designation To be used for: Rated value Connector Illustration


design

Short circuit current square


≤ 31.5 kA square
Cable feeder
Short circuit current
Operating lever hexagonal
40 kA
for earthing
switch Short circuit current
square
≤ 31.5 kA
Busbar
Short circuit current
hexagonal
40 kA
Truck Rated current
hexagonal
HVX/UTX/MTX Ir < 2500 A
Crank for truck Truck Rated current
square
HVX/UTX Ir ≥ 2500 A
Motor drive - -

28
>> Shipping instructions

Delivery Packaging
> For transportation by lorry:
Delivery The product is fixed to a wooden
The cubicles, which make up the pallet and protected by plastic
switchboard are delivered individu- cover.
ally, ready for assembly. The front panel is protected by
The connection should be carried polystyrene panels.
out on-site.
> For transportation by sea:
The product is covered with a
plastic heat welded cover, with
desiccant materials, then instal-
led into a wooden case.

> For transportation by air:


The product is covered with a
plastic heat welded cover, with
desiccant materials, then instal-
led into a wooden case.

29
Notes:

30
AREVA Energietechnik GmbH, Sachsenwerk Mittelspannung
Rathenaustraße 2 · D-93055 Regensburg · P.O.B. 10 01 55 · D-93001 Regensburg
Phone +49 (0)9 41/46 20-0 · Fax +49 (0)9 41/46 20-4 18
www.areva-td.com
Tel.: +44 (0) 1785 250 070