Minimum Requirements
Minimum Requirements
1000 x 2100 (h) 1 hour fire- 1000 x 2100 (h) 1 hour fire- 1000 x 2100 (h) 1 hour fire-
Side Door/
rated mild steel doorc/w closer rated mild steel doorc/w closer rated mild steel doorc/w closer
Escape Door
and rubber skirting and rubber skirting and rubber skirting
Signage All doors shall have Latch & Hasp
Floor Hardener + Epoxy Paint Floor Hardener + Epoxy Paint Anti-acid homogeneous floor
Floor Finish
Nippon EA-4 Evergreen 1461 Nippon EA-4 Evergreen 1461 tiles
2100mm high allround Rim 2100mm high allround Rim 2100mm high allround anti-
Wall Finish Grey (10397) Gloss Paint, ICI or Grey (10397) Gloss Paint, ICI or acid homogeneous wall tiles &
(Internal) equivalent & above 2100mm equivalent & above 2100mm white emulsion paint above
white emulsion paint white emulsion paint 2100mm
Rim G
Wall Finish
TNB Corporate Stripe above 2800mm from FFL - 1
(External)
Selection of colours should be harmonized with t
Ceiling
John Lysaght "Klip Lok Hi Ten" 0.48mm thick metal deck c/w galvanised chicken netting, double sided aluminium
Roofing Roof truss - lightweight steel
Roof slab - Reinforced concrete slab with approved water proofing membrane with five (5) years warranty certi
Gutter Reinforced concrete gutter with a
2 x 23W ceiling mounted LED 2 x 23W ceiling mounted LED
2 x 23W ceiling mounted LED
T8 bare channel c/w angle T8 bare channel c/w angle
T8 bare channel anti-corrosive
reflector (min. 1000 away from reflector (min. 1000 away from
type (min. 1000 away from slot)
slot) slot)
Electrical Fittings 2400 (h) 2 x 23W wall 2400 (h) 2 x 23W wall
Switches for lamp and exhaust
(Lighting) mounted LED T8 bare channel mounted LED T8 bare channel
fan located outside of the room
c/w angle reflector c/w angle reflector
Electrical Fittings
1500 (h) 13 Amp power point - tagging to follow schematic; test for each electrical socket using ELCB & So
(Switches)
ROOM SWITCHGEAR CONTROL BATTERY
Location of cylind
Approved Clean
Halocarbons or
Gas Agent
Earthing System 6 x 50mm copper tape - ring 6 x 50mm copper tape - ring 6 x 50mm copper tape - ring
to Achieve Earth system system system
Resistance < 3 3 nos earth point at 11kV slot 2 nos earth point at 11kV slot 1 no earth bar at cable opening
ohm 4 nos earth point at 33kV slot 2 nos earth point at 33kV slot Cadweld/Brazed joints
TNB Care
Compound
Danger sign,
Signage
No entry sign
Safety E
M REQUIREMENTS FOR PPU 33/11KV BUILDING CONSTRUCTION
TRANSFORMER
CABLE CELLAR LT
2 X 30MVA
1800 x 2100 (h) double leaf 900 x 2100 (h) 1 hour fire- 900 x 2100 (h) 1 hour fire-
solid mild steel doorc/w closer rated mild steel door(next to rated mild steel door(next to
and rubber skirting roller shutter) roller shutter)
have Latch & Hasp c/w lock protector, Danger signage, No Entry signage and Room signage
6mm thick reinforced chequered plates with lifting holes and handles
TRANSFORMER
CABLE CELLAR LT
2 X 30MVA
N/A 4200 x 2000 x 150 1000 x 1800 x 150
2
10kN/m 60 ton 5 ton
Attached Floor Hardener Attached Floor Hardener
Floor Hardener + Epoxy Paint Standalone 150mm layer Standalone 150mm layer
Nippon EA-4 Evergreen 1461 thickness 25mm - 38mm Ø thickness 25mm - 38mm Ø
granite chipping granite chipping
RC roof slab
e sided aluminium sisalation foil, 50mm thick fibreglass wool insulation including flashing, capping
Min. 9 kg port. ABC 2 nos of 9kg ABC portable fire 1 nos of 9kg ABC portable fire
extinguishers c/w labeling / extinguisher c/w weatherproof extinguisher c/w weatherproof
tag, BOMBA certificates and compartment compartment
demarcation line
- wall (50mm red stripe on
white background)
- floor (100mm yellow stripe
with 200mm spacing diagonals
at 45°)
N/A Attached Discharge nozzles (1000mm away from plinth)
Smoke detector Attached Smoke & Heat detector
nel (MFAP) (outside) c/w pictogram/mimic diagram and name tag of installer contractor (SGP)
Gas cylinders c/w demarcation line
Location of cylinders: Not behind opening slot, easy access from exit door
Halocarbons or Inert Gas Manufacturer with Sijil Guna Pakai TNB only
6 x 50mm copper tape - ring 2 nos earth points 1 nos earth points
system + riser to upper floor + 6 x 50 x 300 (l) copper tape 6 x 50 x 300 (l) copper tape
perimeter + earth points 2 nos earthing chamber 1 nos earthing chamber
est point run through 25mm x 3mm copper tape drop to 4 nos earth points/chamber at 4 building corners
at 2.1m height shall be connected with main grid 25mm x 3mm copper strip concealed in concrete
mmØ stainless steel removable handrail, Staircase c/w anti-slip nosing tiles, Finish floor level shall be lower than internal floor level by 50m
r Run*) Catered for double axle trucks carrying 60 tons transformer c/w method statement (as per sample)
TRANSFORMER
CABLE CELLAR LT
2 X 30MVA
(Premix/Reinforced Concrete) road
a) In front of transformer bay - 8000mm (w) and shall be catered for double axle trucks carrying 60
statement
with anticlimb anticut (mesh size: 12.5 x 75 x 4mm Ø) double leaf swing gate c/w cross bar support with min. 4 nos heavy duty roller
nised iron, anticlimb anticut (mesh size: 12.5 x 75 x 4mm Ø) c/w 600mm high razor blade concertina wire
50mmØ stone chipping (1000mm inward and 1000mm outward) at the base 150 mm depth
verts & sump (standalone PPU)** c/w Heavy Duty FRP Grating at all crossings
vidual)** Culverts & sump (standalone PPU)** c/w Heavy Duty FRP Grating at all crossings
(Domestic connection/ Rain water harvesting system/Tube well)**
(Premix/Crusher run*)
8 nos 4000mm (h), 150W HPSV galvanised pole c/w timer and photocell
- Sub DB (external lighting) shall be located at guard house
ete earthing chamber, 50mm x 6mm copper tape with copper connection (crossby clip/cadweld/clamp)
service engineer with proof of calibrated testing equipment (min. every 3 years). The testing method shall comply with IEEE STANDARD 8
Main signboard
TNB Careline, Location: at PPU wall facing the main road
Danger sign, Location: at all four (4) sides of perimeter fencing
No entry sign, Location: at all four (4) sides of perimeter fencing
Safety Excellence Management System (SEMS) symbol
CB NER
4800 4800
Attached 2000 x 3000 (h) Solid Attached 2000 x 3000 (h) Solid
G.I auto/manual roller shutter G.I auto/manual roller shutter
door linked with firefighting door linked with firefighting
system with closing time less system with closing time less
than 30 seconds than 30 seconds
900 x 2100 (h) 1 hour fire- 900 x 2100 (h) 1 hour fire-
rated mild steel door(next to rated mild steel door(next to
roller shutter) roller shutter)
(11326)
ctures.
therproof switches
Amps power point
20 Amps power point
CB NER
Natural ventilation
tilation linked to firefighting system
1 nos of 9kg ABC portable fire 1 nos of 9kg ABC portable fire
extinguisher c/w weatherproof extinguisher c/w weatherproof
compartment compartment
corners
sample)
CB NER
ered for double axle trucks carrying 60 tons transformer c/w method
amp)
od shall comply with IEEE STANDARD 81