Setting Calculation of Oc and Ef Realy

This document outlines the calculation of over current relay settings for low and high settings. It details the pickup settings, plug setting multipliers, operating times, and total grading times to determine the appropriate settings and operating times for protection of a feeder.

Uploaded by

ManishPandya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
13K views1 page

Setting Calculation of Oc and Ef Realy

This document outlines the calculation of over current relay settings for low and high settings. It details the pickup settings, plug setting multipliers, operating times, and total grading times to determine the appropriate settings and operating times for protection of a feeder.

Uploaded by

ManishPandya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

Calculation of Over Current Relay Setting:

(1) Low over Current Setting: (I>)


 Over Load Current (In) = Feeder Load Current X Relay setting = 384 X 125% =480 Amp
 Required Over Load Relay Plug Setting= Over Load Current (In) / CT Primary Current
 Required Over Load Relay Plug Setting = 480 / 600 = 0.8
 Pick up Setting of Over Current Relay (PMS) (I>)= CT Secondary Current X Relay Plug Setting
 Pick up Setting of Over Current Relay (PMS) (I>)= 1 X 0.8 = 0.8 Amp
 Plug Setting Multiplier (PSM) = Min. Feeder Fault Current / (PMS X (CT Pri. Current / CT Sec. Current))
 Plug Setting Multiplier (PSM) = 11000 / (0.8 X (600 / 1)) = 22.92
 Operation Time of Relay as per it’s Curve
 Operating Time of Relay for Very Inverse Curve (t) =13.5 / ((PSM)-1).
 Operating Time of Relay for Extreme Inverse Curve (t) =80/ ((PSM)2 -1).
 Operating Time of Relay for Long Time Inverse Curve (t) =120 / ((PSM) -1).
 Operating Time of Relay for Normal Inverse Curve (t) =0.14 / ((PSM) 0.02 -1).
 Operating Time of Relay for Normal Inverse Curve (t)=0.14 / ( (22.92)0.02-1) = 2.17 Amp
 Here Time Delay of Relay (TMS) is 0.125 Sec so
 Actual operating Time of Relay (t>) = Operating Time of Relay X TMS =2.17 X 0.125 =0.271 Sec
 Grading Time of Relay = [((2XRelay Error)+CT Error)XTMS]+ Over shoot+ CB Interrupting Time+
Safety
 Total Grading Time of Relay=[((2X7.5)+10)X0.125]+0.05+0.17+0.33 = 0.58 Sec
 Operating Time of Previous upstream Relay = Actual operating Time of Relay+ Total Grading
Time Operating Time of Previous up Stream Relay = 0.271 + 0.58 = 0.85 Sec
(2) High over Current Setting: (I>>)
 Pick up Setting of Over Current Relay (PMS) (I>>)= CT Secondary Current X Relay Plug Setting
 Pick up Setting of Over Current Relay (PMS) (I>)= 1 X 2.5 = 2.5 Amp
 Plug Setting Multiplier (PSM) = Min. Feeder Fault Current / (PMS X (CT Pri. Current / CT Sec. Current))
 Plug Setting Multiplier (PSM) = 11000 / (2.5 X (600 / 1)) = 7.33
 Operation Time of Relay as per it’s Curve
 Operating Time of Relay for Very Inverse Curve (t) =13.5 / ((PSM)-1).
 Operating Time of Relay for Extreme Inverse Curve (t) =80/ ((PSM)2 -1).
 Operating Time of Relay for Long Time Inverse Curve (t) =120 / ((PSM) -1).
 Operating Time of Relay for Normal Inverse Curve (t) =0.14 / ((PSM) 0.02 -1).
 Operating Time of Relay for Normal Inverse Curve (t)=0.14 / ( (7.33)0.02-1) = 3.44 Amp
 Here Time Delay of Relay (TMS) is 0.100 Sec so
 Actual operating Time of Relay (t>) = Operating Time of Relay X TMS =3.44 X 0.100 =0.34 Sec
 Grading Time of Relay = [((2XRelay Error)+CT Error)XTMS]+ Over shoot+ CB Interrupting Time+
Safety
 Total Grading Time of Relay=[((2X7.5)+10)X0.100]+0.05+0.17+0.33 = 0.58 Sec
 Operating Time of Previous upstream Relay = Actual operating Time of Relay+ Total Grading Time.
 Operating Time of Previous up Stream Relay = 0.34 + 0.58 = 0.85 Sec
Conclusion of Calculation:
 Pickup Setting of over current Relay (PMS) (I>) should be satisfied following Two Condition.
 (1) Pickup Setting of over current Relay (PMS)(I>) >= Over Load Current (In) / CT Primary Current
 (2) TMS <= Minimum Fault Current / CT Primary Current
 For Condition (1) 0.8 > =(480/600) = 0.8 >= 0.8, Which found OK
 For Condition (2) 0.125 <= 11000/600 = 0.125 <= 18.33, Which found OK
 Here Condition (1) and (2) are satisfied so
 Pickup Setting of Over Current Relay = OK
 Low Over Current Relay Setting: (I>) = 0.8A X In Amp
 Actual operating Time of Relay (t>) = 0.271 Sec
 High Over Current Relay Setting: (I>>) = 2.5A X In Amp
 Actual operating Time of Relay (t>>) = 0.34 Sec