Operator’s Manual
D I G I T A L C O N T R O L L ER 5 0 0 2 U
CONTENTS
1. TECHNICAL DETAILS
2. SPECIFICATIONS
4. FRONT FASCIA
5. CONNECTIONS DETAIL
6. USER GUIDE
7. MODE OF OPERATION
9. COMMUNICATION PARAMETERS
1. TECHNICAL DETAILS
Provision for zero and span setting is
This is a versatile microprocessor based made to restrict range of usage and
ON/OFF controller with a very high programming. This restricts accidental
performance to price ratio. The features wrong setting of set-point beyond the
offered in this product are better than range of interest. Outside this range the
any other controller available in similar unit will indicate temperature as 'OVER'
price range. for some abnormal condition. This zero
and span setting is used for linear inputs
The instrument is made in 96 x 96 x 180 for setting the range between -1999 to
mm³ size with standard cutout of 92 x 9999 counts.
92 mm². Front is sealed membrane type
to withstand dusty environment. On Also, the unit has an optional provision
back plate, PCB soldered terminals are for isolated linearzed retransmission
used. The programming and calibration signal or isolated serial
of the instrument is done by a 4-button communication using RS-485.
keypad, equipped with two independent Retransmission signal is useful for
displays for set point and process recorder or secondary display. The
variable. Set point display is kept 0.3” to output can be 4-20 mA for the
differentiate it from process variable programmed range or 1 mV/degree (1-
display. Status of control/alarm relays 5V) for thermocouple types so that an
and presently displayed set point are ordinary DPM can be connected to this
displayed by 3 mm red LED. signal for remote indication of
temperature.
The operation of the instrument is
menu- driven with user-friendly
prompts.
• No of Supply :1
• Voltage Rating : 24 V dc @ 20 mA
Isolated output
• Isolation : 500 V dc
• Communication standard:
RS-485
• Communication Protocol:
Modbus RTU
• Distance of Communication:
1200 meter (Twisted pair cable as
per EIA 485 standard)
• Maximum Slaves:
32 without repeaters
• Isolation:
500 V dc
Now, setting correct value of password various types of set-points and effect of
in SV (set value) window and pressing Hysteresis on relay operation.
enter key mode will be displayed.
mode 7.1 SET-POINTS &
HYSTERESIS EFFECTS
By pressing INC/DEC Key, user can view For set-points selection, there are three
operating modes (CALb Or ConF) in different options, which can be selected
for a particular set-point.
PV (Process value) window and by
pressing Enter key unit will enter into
On-Above/On-Below Set-point
that particular operating mode.
If user selects on above set-point option,
Conf the relay will be energized when the
Calb process variable is more than set
variable. In case of on below set-point
After Entering into operating mode operation of relay is reverse.
(CALb Or ConF), first parameter will be
displayed in SV window and by Pressing Control/ Alarm Set-point
select key subsequent parameter will be
displayed. Corresponding parameter In the case of control set-point the
values will be displayed in PV window. Hysteresis effect is different from alarm
By pressing INC/DEC Key, user can type. In case of alarm set-point, the
select desired value and by pressing relay can be acknowledged on pressing
ENTER Key, user can store selected of ENTER key in run mode. So, this
value. After the last parameter is selection should be done carefully
displayed, pressing of SEL key for 3 according to application.
second will bring the instrument in Run
mode. Absolute/ Deviation Set-point
This key will also decrement the selected Deviation option is applicable only for
parameter value by one count in all second and third set-points. In case of
operation modes. deviation set-point, it is added to the
If the key is pressed continuously than first set-point to derive the actual set-
the rate of decrement will be made five point.
times faster. This facility is called dual This set-point selection can be done by
speed decrement facility to allow faster changing the configuration. Refer to
data change for higher values. This key section on reconfiguration elsewhere in
is also used to move onto different mode this manual.
(calibration and configuration).
Now, let us see an example to illustrate
the effect of Hysteresis setting on relay
operation. For control set-point and
7. MODE OF alarm set-point the effect of Hysteresis
is little different so we will consider each
OPERATION case separately.
There are five modes of operations. Suppose you have selected a set-point
• Run mode of 200 and Hysteresis of 5. Also the
• Password mode setting is for control type and on below
• Program mode set-point. So in this case the Hysteresis
• Configuration mode effect is applicable while turning ON the
• Calibration mode relay. The relay will turn off exactly at
200 after being turned on. But it will not
Before looking into various modes of turn on once again until temperature
operations, it will be better to falls below 200 - 5 = 195. This provides
understand some fundamentals for a band of 5 around the set-point. In
case of on above set-point type, the If either of the key is kept pressed
operation will be reverse. continuously for more than 10 counts
change in setting, it will start
Now suppose you have kept same set- incrementing or decrementing the data
point of 200 and Hysteresis of 5. Set- at a five time faster rate. Bring the set-
point type is alarm and on below set- point at a desired value and press enter
point. In this case the Hysteresis effect key for storing the value permanently.
will be applicable while turning OFF the On pressing of enter key the display
relay. The relay will turn ON when the shows the parameter prompt. On
process value goes below 200. But it will pressing of select key other parameter
not turn OFF until the temperature goes in sequence are selected and changed
beyond 200 + 5 = 205. This provides a by the same procedure.
band of 5 around the set-point. In case
of on above set-point type, the The parameters in sequence are:
operation will be reverse.
Sp1 Setpoint1
Band Set-point
Hys1 Hysteresis for first set-point
In case of band set point main set point Sp2 Setpoint2
is taken as a reference and band set Hys2 Hysteresis for second set-point
point is distributed both side of main set Sp3 Setpoint3
point equally.
Hys3 Hysteresis for Third set-point
First we will see the meaning of various N-tc input -200 to 1300.
prompts displayed.
G-tc input 0 to 2320.
Inpt Input type C-tc input 0 to 2320.
zerO Zero setting Rtd input 0.1 deg. Resolution
SpaN Span setting -199.9 to 850.0.
NOSP Number of set-point
4-20 mA input -1999 to 9999.
Tsp1 Type of first set-point
0-20 mA input -1999 to 9999.
Tsp2 Type of second set-point
1-5V input -1999 to 9999.
Tsp3 Type of third set-point
0-5V input -1999 to 9999.
D SP Default Display set-point
0-100 mV input -1999 to 9999.
dp Decimal point position
0-2V input 0 to 2000.
OPSE Open sensor For changing of input type, no internal
PASS Password hardware changes are required.
init Initialization When an input type is selected its
corresponding zero and span range is
SLOt Slot configuration
automatically adjusted as per its table.
Byps Bypass selection[used to However if user wants to change zero
bypass 3rd Relay and and span as required he can move to the
RL3 LED Indication in zero or span prompt and can change .
front]
srNo Serial No With this facility if the same input is
selected (i.e. ENTER key is pressed on
baud Baud Rate
the same input), its zero and span range
rt-Z RX zero setting [ Applicable is kept as it is. For setting the range as
for 0-2V input and Retransmission Option ] per the table one has to change the
rt-S RX span setting [ Applicable input type only. Refer corresponding
for 0-2V input and Retransmission Option ] range as per the inputs.
Type of input is displayed as code for These settings are for specifying
input type. The type of inputs available minimum and maximum range of
is E, J, K, T, B, R, S, N, G ,C, RTD, 4-20 operation. Although full sensor input
mA DC, 0-20 mA DC and 0-5 Volt DC, 1- range is supported, user can select his
5 Volt DC, 0-100 mV DC, 0-2 Volt DC range of operation. The set-point cannot
with display prompt shown below. be set below zero setting and above the
Input type can be selected by INC key or span setting. The reading will display
DEC key. Input type and each type of over when the input is below zero
input are displayed by prompt as setting by 5% or above span setting by
follows. 5%. This 5% is calculated for the
Inpt difference of zero and span settings.
Extreme limits for thermocouple and
E-tc input -200 to 1000. RTD types for the setting are sensor
limits.
J-tc input -200 to 1200
zerO
K-tc input –200 To 1372.
T-tc input -200 to 400
spaN
B-tc input 450 to 1820. Zero and span setting are used for
R-tc input 0 to 1768 selecting range for all inputs. This
S-tc input 0 to 1768 allows selecting any value between
-1999 to 9999 for the range of the all.
Number of Set-points
Type of Set-point
1. Set the input resistance at 100.0 at output. Now Press ENTER key
ohm, get CALZ Prompt on the to calibrate O/P for 4 mA.
display and set it to 00.0 °C by 3. Now on pressing SET key SV
“INC” or “DEC” keys and press window will display rtrS
ENTER key to calibrate ZERO. (calibrate span) and PV will
2. Now set the input resistance at display “20.000.” and “2. .”
375.61 ohm. Get CALS Prompt on (20 mA). With help of “INC” or
the display and set 800.0 by “INC” “DEC” keys set this mA value
or “DEC” keys and press ENTER key exactly same as on Ampere-
to calibrate SPAN. meter reading connected at
output. Press ENT key to
Now check the linearity for the whole calibrate O/P for 20 mA.
range
Note: For input type 0-2V: rt-Z
[C] For Linear type parameter must be set to 0 and rt-S
parameter must be set to 2000 to
1. Set the input at 4.000 mA, get calibrate the unit for analog output.
CALZ Prompt on the display and After calibration user can set rt-Z
set it to Actual ZERO by “INC” or and rt-S parameter as per
“DEC” keys and press ENTER key to requirement.
calibrate ZERO.
2. Now set the input at 20.000 mA. • Now check the linearity for the
Get CALS Prompt on the display whole range.
and set it to Actual SPAN by “INC”
or “DEC” keys and press ENTER key
to calibrate SPAN. 7.7 SPECIAL NOTE
• Now check the linearity for the This controller is storing all data
programmed by user and calibration in
whole range.
EEPROM. There are lots of software and
hardware protections added for
ISOLATED RETRANSMISSION safeguarding against data corruptions.
SIGNAL There can be a very rare possibility of
data getting disturbed. The controller is
This is an optional feature. This output having unique algorithm to store data at
can be either 4-20 mA or voltage output multiple places. So, even if the data in
up to 5 volts. This output is proportional one place gets disturbed, it is
to the zero and span setting for input automatically over-ridden by other
type. For example, if you set zero and correct data values. It is also having
span at 0 deg. and 1200 deg. for K type software protections against accidental
thermocouple input, it will output 4 mA writing to EEPROM also.
for 0 deg. and 20 mA for 1200 Deg.
Even after all this, if the data gets
Calibration procedure for ANALOG corrupted by heavy transients on power
OUTPUT . line or noise on power line (for which
protections are already given in
1. Enter into calibration mode as hardware), the unit will display ‘dAtA
explained in the above
paragraph.
Err’ message on the display and will
2. Now SV window will display stop control action, keeping all relays in
OFF condition as safety. In this event,
rtrZ and PV window will programming mode will still continue
display 4.000 (4 mA). With working. User can go to program mode
help of “INC” or “DEC” keys set and check the data, which has changed.
this mA value exactly same as at Re-program the data if it is changed and
Ampere-meter reading connected still it shows data error message, select
8. MODBUS DETAIL
8.1 INTRODUCTION
When a message is sent from a master CRC to the message. The receiving
to a slave device the function code field device recalculates a CRC during receipt
tells the slave what kind of action to of the message, and compares the
perform. calculated value to the actual value it
received in the CRC field. If the two
In Digital controller 5002u the functions values are not equal, an error is
implemented are encountered.