Distance Protection Setting Calculation PDF
Distance Protection Setting Calculation PDF
Setting Calculations
Distance Protection
In Fig. the impedance measured at the relay point A is Zin , where x is the
distance to the fault (short circuit), and R and X are transmission line
parameters in per unit length. The line length is l in the fig.
Operating characteristics of distance protection elements are usually
represented using R-X diagrams.
Required information for Protective Setting
Line Parameters:
• Line length, voltage level, conductor size and conductor type used
for local as well as remote substations.
• This information is used to calculate the parameters (positive and
zero sequence resistance, reactance) for each section.
• Maximum load current or apparent power (MVA) corresponding to
the emergency line which can be obtained from the table of standard
conductor rating (available in each utility).
• The number of conductors in a bundle has to be taken into
consideration.
• Conductor Specifications if not available, refer to CEA manual
‘Annexure-V, Table 1(a), Line parameters’
…required information for Protective Setting
Transformer Parameters:
• The manufacturer's positive and zero sequence impedance test
values have to be obtained.
• The transformer nameplate normally provides the
manufacturer's positive sequence impedance values.
• Voltage ratio, MVA rating, %Impedance value
CT & PT Ratios :
• Obtain the CT & PT ratios as indicated on the protection
diagrams.
• For existing circuits, it is possible to verify the ratios indicated
on the diagrams by measuring the load currents on site and
comparing with a known ratio.
Arc & Tower footing resistance:
• Used in resistive reach calculation.
Various operating Characteristics
Region of
Line Q non-operation
120%
B outside the circle
80%
Zone 2
Line P
Z RS
Load
Region of region
operation
Zone 1
A R
1. Mostly used
2. Resistive and reactive reach can be set independently
Zone protection
* Generally zones Z1, Z2, Z3 are taken as forward direction and Z4 is
taken as reverse direction with time settings as T1, T2, T3 and T4
respectively.
* Settings adopted depends on their respective Regional Power Committees
and CBIP recommendation or guidelines.
Adopted Philosophy for Transmission Line Protection
Why 80% ?
The under-reach setting is set to avoid overreaching into the next
protected line & to avoid unwanted tripping.
Zone 2:
* Set to cover (120% of the protected line) Or (Protected line
impedance + 50% of adjacent shortest line impedance)
or (Protected line + 50% transformer impedance).
* 150% of the protected line (for Double circuit )
* Time delay- 300-500 milli seconds.
* Provides Backup protection for a part of the adjacent line.
* Should be set in such a way that Zone-2 setting should not encroach
into LV side of the transformer as this leads to unwanted tripping of
HV side for a fault in LV side.
* Trip the faulty line instantaneously using carrier aided tripping
(POTT).
Consideration for time delay:
• Downstream Co-ordination (100ms)
• Circuit Breaker Operation(100ms)
• Safety margin(100ms)
Adopted Philosophy for Transmission Line Protection
Zone 3:
* Set to cover (120% of the protected line + adjacent longest line) or
(Protected line impedance + 100% of adjacent longest line
impedance + 25% of second adjacent longest line) or (Protected line
+ 100% transformer impedance).
* Time delay- 800-1200milli seconds .
* Provides Backup protection for a the next adjacent line.
* Should be set in such a way that Zone-3 setting should not encroach
into LV side of the transformer as this leads to unwanted tripping of
HV side for a fault in LV side..
Zone-4:
* Reverse Zone
* Provides backup protection for station faults. (Acts as Busbar zone
backup)
* Time delay is normally 1-1.3sec if Bus bar protection available
else 450-500ms.
Conversion of primary values into secondary values
* Distance relays are fed from the secondary's of line CT’s & Bus
PT’s /Line CVT’s.
* The line parameters are to be converted into secondary values
Zsec = Zpri / (Impedance ratio)
Where Impedance ratio = PT ratio / CT ratio.
* The CT and PT ratios are inter related. Hence any changes in CT
ratio has to be effected along with revision of relay settings only.
What to do?
* Define the load regions in the impedance plane and block operation
of distance elements if the impedance in either of the load region.
Resistive reach:
* This setting is used for setting the resistive coverage.
* Separate resistive settings are kept for Phase-Phase faults &
Phase-Earth faults.
* Arc resistance & tower footing resistance are required to calculate
resistive reach settings.
…Resistive reach:
In general , reach is calculated ..
Notation:
* R1PH-R1G ( MiCOM)
* R(Z)-RE(Z) (SIEMENS)
* RFPP-RFPE (ABB)
Power swing
* It can cause major power outages, even power blackout or severe damage to
the machine.
* Direction of current flow will remain same during the power swing
event. Only voltages change with respect to one another.
* Traditional Method
• We can distinguish a Power Swing condition or OSS condition by the difference in the
rate of change of the positive-sequence impedance vector.
• This detection method is based on the fact that it takes a certain time for the rotor
angle to advance because of system inertias.
• Practical implementation of measuring the rate of change of the impedance is
normally performed through the use of two impedance measurement elements
together with a timing device.
• If the measured impedance stays between the settings of the two impedance
measurement elements for a predetermined time, the relay declares a power swing
condition and issues a blocking signal to block the distance relay element operation.
*Advanced Method
• The advent of digital technology has given relay design engineers the
ability to develop and realize new methods for detecting power
swings.
• Some of these new methods determine a power swing condition
based on a continuous impedance calculation.
• For example, an impedance calculation is performed for each 5ms
step, and compared with the previous 5ms’ result. Thus two
continuous deviations can be predicted as traveling impedance
because of power swing.
• Synchro phasor-based Out-of-Step Relaying measurement has also
been used to detect and take action for power swings.
• Many utilities are currently evaluating the use and application of
synchronized phasor measurement systems.
Auto Reclose Element
Types of faults:
* 1.Transient faults 2. Semi permanent faults 3. Permanent faults
Transient faults:
* Disappear after Short dead time
Various Transient Faults
• Lightning strokes resulting in flashovers
• Conductor swinging due to high winds
• Bird fault
• Temporary contact with foreign objects like tree etc.
* 80%-90% of faults on any overhead line network are transient in
nature. The remaining 20%-10% of faults are either semi-
permanent or permanent.
…Auto reclose :
Advantages:
* Decreases outage time
* Improves reliability
* Improves system stability
* Reduces maintenance time.
Dead time:
The time between the auto reclosing scheme being energised and the operation of the
contacts which energise the circuit breaker closing circuit.
Range: 0.3- 1.2 sec ; 1 Sec (NRPC & CBIP-274 for both 220 kV and 400kV)
Reclaim time:
The time between 1st and 2nd Auto reclosure.
Range: 10-30 sec ; 25 Sec (NRPC)
* Line is switched on to a close by fault (say after line clear with earth
switch closed, accidental energization), the voltage at the relaying
point will be zero.
* Voltage applied to the relay will be low.
* SOTF relay will trip instantaneously.
* SOTF feature will be effective only for about 200 ms after the line is
charged and if fault is presents the relay will operate as a simple O/C
relay and its isolate the healthy section from faulty detection.
* This function is very useful in a case when maintenance of any
machinery is done in a switchyard and the line to be energised.
* Faults occurring after this time will be measured in normal way.
* Setting:
I2/I1 ≥ 0.2 ; Time delay 3-5secs. (NRPC)
Data Required
*Positive Sequence Line Impedance = R1+jX1
*Zero Sequence Line Impedance = R0+jX0
*CT Ratio
*PT Ratio
*Protected line length (PLL)
*Adjacent shortest line length (ASLL)
*Adjacent longest line length (ALLL)
*Second adjacent long line length (SALLL)
*MVA, %Impedance of Transformer, No. of Transformers connected
*Maximum load on the Feeder (Refer from CEA Tr. Lines Guidelines)
*Phase-Phase fault resistance (Arc resistance)
*Phase-Earth fault resistance (Arc resistance + Tower footing
resistance)
.....setting calculations for ABB REL-521
Calculations
1.Protected Line (P.L)
*Positive Sequence Resistance of P.L (Primary) = R1 (Ω/Km)
*Total Positive sequence resistance of P.L (Primary) = R1x PLL
*Total Positive Sequence resistance wrt secondary (R1 Sec) = R1 x PLL x (CT/PT ratio)
Loadablity
*Max Load current
*Max apparent power Smax= 1.732 x 1.2 x V L-L x Max load current
*As per “Reliability Standard PRC-023” for 0.85per unit voltage and max current
is
Zloadmin (Pri.)=(0.8*V L-L* V L-L)/(Smax)
Zloadmin (Sec.) = Zload max (Pri.) * (CT/PT ratio)
Phase-Earth
*X1PE=X1PP
*R1PE=R1PP
*RFPE = Min[ (Ph-Ph fault resistance in Sec),(4.5 times of Zone 1 reach) &
(0.8*Zloadmin*(cos 30-(2*R1PP+R0PE/2*X1PP+X0PE)*Sin 30))]
Zero Sequence
*X0PE = 80% of PLL (X0)
*R0PE = 80% of PLL (R0)
Phase-Earth
*X1PE=X1PP
*R1PE=R1PP
*RFPE = Min[ (Ph-Ph fault resistance in Sec),(4.5 times of Zone 2 reach) &
(0.8*Zloadmin*(cos 30-(2*R1PP+R0PE/2*X1PP+X0PE)*Sin 30))]
Zero Sequence
*X0PE = Min[Max { (PLL+0.5*ASLL),(1.2*PLL)} & (PLL+0.5 Trans. Impedance)]
*R0PE = Min[Max { (PLL+0.5*ASLL),(1.2*PLL)} & (PLL+0.5 Trans. Impedance)]
Phase-Earth
*X1PE=X1PP
*R1PE=R1PP
*RFPE = Min[ (Ph-Ph fault resistance in Sec),(4.5 times of Zone 3 reach) &
(0.8*Zloadmin*(cos 30-(2*R1PP+R0PE/2*X1PP+X0PE)*Sin 30))]
Zero Sequence
*X0PE = Min[ (1.2*PLL+ALLL),(PLL+ALL+0.25*SALL)} & (PLL+Trans. Impedance)]
*R0PE = Min[ (1.2*PLL+ALLL),(PLL+ALL+0.25*SALL)} & (PLL+Trans. Impedance)]
Phase-Earth
*X1PE=X1PP
*R1PE=R1PP
*RFPE = Min[ (Ph-Ph fault resistance in Sec),(4.5 times of Zone 4 reach) &
(0.8*Zloadmin*(cos 30-(2*R1PP+R0PE/2*X1PP+X0PE)*Sin 30))]
Zero Sequence
*X0PE = 0.25 * Zone 1 Impedance
*R0PE = 0.25 * Zone 1 Impedance
Data Required
*Positive Sequence Line Impedance = R1+jX1
*Zero Sequence Line Impedance = R0+jX0
*CT Ratio
*PT Ratio
*Protected line length (PLL)
*Adjacent shortest line length (ASLL)
*Adjacent longest line length (ALLL)
*Second adjacent long line length (SALLL)
*MVA, %Impedance of Transformer, No. of Transformers connected
*Maximum load on the Feeder (Refer from CEA Tr. Lines Guidelines)
*Phase-Phase fault resistance (Arc resistance)
*Phase-Earth fault resistance (Arc resistance + Tower footing
resistance)
.....setting calculations for Siemens 7SAXXX
Calculations
1.Protected Line (P.L)
*Positive Sequence Impedance of P.L (Primary) Z = √ (R12+X12 ) (Ω/Km)
*Total Positive sequence Impedance of P.L ( Primary) = Z x PLL
*Total Positive Sequence Impedance wrt secondary (PL .Z Sec) = Z x PLL
x (CT/PT ratio)
Calculations
3.Adjacent Longest Line (A.L.L)
*Positive Sequence Impedance of A.L.L (Primary) Z = √ (R12+X12 )
(Ω/Km)
*Total Positive sequence Impedance of A.L.L ( Primary) = Z x ALLL
*Total Positive Sequence Impedance wrt secondary (ALL.Z Sec) = Z x
ALLL x (CT/PT ratio)
Loadablity
*Max Load current
*Max apparent power Smax= 1.732 x 1.2 x V L-L x Max load current
*As per “Reliability Standard PRC-023” for 0.85per unit voltage and max current
is
Zmax (Pri.)=(0.8*V L-L* V L-L)/(Smax)
Zmax (Sec.) = Zload max (Pri.) * (CT/PT ratio)
Calculations
Loadablity
* The Resistance reach & Reactance reach corresponding to
Zmax w.r.t Secondary is
R = Zmax *Cos (30) & X= Zmax *Sin (30)
*The New impedance for Parallel line drawn parallel to the
Line impedance passing through Zmax to the point at which
the parallel line cuts
*The Resistance axis is Znew= X(at Zmax) /Sin(Line angle)
*The New Resistance from known Reactance
Rnew = Znew* Cos (Line angle)
*Resistancereach of Relay Characteristics obtained
from maximum loadability condition
Resistive Reach R=(R correspond to Zmax – Rnew)
.....setting calculations for Siemens 7SAXXX
Zone Settings
Zone 1
*Zone 1 Impedance Z1= 80% x P.L.Z Sec
*Zone 1 Resistance R1= Z1 x Cos(Line angle)
*Zone 1 Reactance X1= Z1 x Sin(Line angle)
*Phase to phase resistive reach R(Z1) = R1+Arc Resistance/2
*Phase to earth resistive reach RE(Z1)=R1+Arc Resistance +Tower footing
resistance