Generator Earthing and Stator Earth Fault Protection - EEP

This document discusses generator earthing and stator earth fault protection. It describes different methods for earthing generators, including low and high impedance earthing. It also discusses various types of earth fault protection that can be used depending on how the generator is connected, including neutral overcurrent protection, sensitive earth fault protection, and restricted earth fault protection. Protection methods discussed include using current transformers, voltage displacement, and third harmonic voltage measurements.

Uploaded by

ABHINAV SAURAV
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
248 views13 pages

Generator Earthing and Stator Earth Fault Protection - EEP

This document discusses generator earthing and stator earth fault protection. It describes different methods for earthing generators, including low and high impedance earthing. It also discusses various types of earth fault protection that can be used depending on how the generator is connected, including neutral overcurrent protection, sensitive earth fault protection, and restricted earth fault protection. Protection methods discussed include using current transformers, voltage displacement, and third harmonic voltage measurements.

Uploaded by

ABHINAV SAURAV
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more!
More Information
Energy and Power / Energy Generation / Protection

Generator earthing and stator earth fault protection


Home / Technical Articles / Generator earthing and stator earth fault protection

Generating unit complexity


Generating unit is a pretty complex system made up of the generator stator winding, its transformer and unit transformer (if
present), the rotor with its field winding and excitation system, and the prime mover with its associated auxiliaries.

Generator earthing and stator earth fault protection (photo credit: Greg Moss)

Many different faults can occur within this generating unit system for which wide range of of electrical and mechanical
protection are required.

As (almost) always, the financial considerations decide the amount of protection that will be applied, taking into account
the value of the machine, and the value of its output to the plant owner.

This technical article deals with generator earthing methods and only the stator earth fault protection.

1. Generator earthing
2. Earth fault protection
1. Direct-Connected Generators
1. Neutral Overcurrent Protection
2. Sensitive Earth Fault Protection
3. Neutral Voltage Displacement Protection
2. Indirectly-Connected Generators
1. High Resistance Earthing – Neutral Overcurrent Protection
2. Distribution Transformer Earthing Using a Current Element
3. Distribution Transformer Earthing Using a Voltage Element
4. Neutral Voltage Displacement Protection
3. Restricted Earth Fault Protection
1. Low-Impedance Biased REF Protection
2. High Impedance REF Protection
4. Earth Fault Protection for the Entire Stator Winding
1. Measurement of Third Harmonic Voltage
2. Use of Low-Frequency Voltage Injection

1. Generator earthing
The neutral point of a generator is usually earthed to facilitate protection of the stator winding and associated system.
Earthing also prevents damaging transient overvoltages in the event of an arcing earth fault or ferroresonance.

For HV generators, impedance is usually inserted in the stator earthing connection to limit the magnitude of earth fault
current.

There is a wide variation in the earth fault current chosen, common values being:

rated current
200A-400A (low impedance earthing)
10A-20A (high impedance earthing)

The main methods of impedance-earthing a generator are shown in Figure 1. Low values of earth fault current may limit the
damage caused from a fault, but they simultaneously make detection of a fault towards the stator winding star point more
difficult.

Except for special applications, such as marine, LV generators are normally solidly earthed to comply with safety
requirements.

Where a step-up transformer is applied, the generator and the lower voltage winding of the transformer can be treated as
an isolated system that is not influenced by the earthing requirements of the power system.
Figure 1 – Methods of generator earthing

An earthing transformer or a series impedance can be used as the impedance. If an earthing transformer is used,
the continuous rating is usually in the range 5-250kVA. The secondary winding is loaded with a resistor of a value
which, when referred through the transformer ratio, will pass the chosen short-time earth-fault current.

This is typically in the range of 5-20 A.

The resistor prevents the production of high transient overvoltages in the event of an arcing earth fault, which it does by
discharging the bound charge in the circuit capacitance. For this reason, the resistive component of fault current should not
be less than the residual capacitance current.

This is the basis of the design, and in practice values of between 3-5 Ico are used.

It is important that the earthing transformer never becomes  saturated. Otherwise a very undesirable condition of  ferroresonance may occur.

The normal rise of the generated voltage above the rated value caused by a sudden loss of load or by field forcing must be
considered, as well as flux doubling in the transformer due to the point-on-wave of voltage application.

It is sufficient that the transformer be designed to  have a primary winding knee-point e.m.f. equal to 1.3 times  the generator rated line voltage.

Go back to contents ↑
2. Earth fault protection
Earth fault protection must be applied where impedance earthing is employed that limits the earth fault current to less than
the pick-up threshold of the overcurrent and/or differential protection for a fault located down to the bottom 5% of the
stator winding from the star-point.

The type of protection required will depend on the method of earthing and connection of the generator to the power
system.

Go back to contents ↑

2.1 Direct-Connected Generators

A single direct-connected generator operating on an isolated system will normally be directly earthed. However, if
several direct-connected generators are operated in parallel, only one generator is normally earthed at a time.

For the unearthed generators, a simple measurement of the neutral current is not possible, and other methods of protection
must be used.

The following paragraphs describe the methods available:

2.1.1 Neutral Overcurrent Protection

With this form of protection, a current transformer in the neutral-earth connection energizes an overcurrent relay element.
This provides unrestricted earth-fault protection and so it must be graded with feeder protection.

The relay element will therefore have a time-delayed operating characteristic.

Grading (or grading margin) must be carried out in accordance with the following principles:

1. Circuit Breaker Interrupting Time

The circuit breaker interrupting the fault must have completely interrupted the current before the discriminating relay
ceases to be energized. The time taken is dependent on the type of circuit breaker used and the fault current to be
interrupted.

Manufacturers normally provide the fault interrupting time at rated interrupting capacity and this value is invariably used
in the calculation of grading margin.

2. Relay Timing Error

All relays have errors in their timing compared to the ideal characteristic as defined in IEC 60255. For a relay specified to
IEC 60255, a relay error index is quoted that determines the maximum timing error of the relay.

The timing error must be  taken into account when determining the grading margin.

3. Overshoot
When the relay is de-energized, operation may continue for a little longer until any stored energy has been dissipated.

For example, an induction disc relay will have stored kinetic energy in the motion of the disc; static relay circuits may have
energy stored in capacitors. Relay design is directed to minimizing and absorbing these energies, but some allowance is
usually necessary.

The overshoot time is defined as the difference between the  operating time of a relay at a specified value of input current  and the maximum duration of
input current, which when  suddenly reduced below the relay operating level, is insufficient  to cause relay operation.

4. CT Errors

Current transformers have phase and ratio errors due to the exciting current required to magnetize their cores. The result
is that the CT secondary current is not an identical scaled replica of the primary current.

This leads to errors in the operation of relays, especially in the operation time. CT errors are not relevant for independent
definite-time delay overcurrent relays.

5. Final Margin

After allowances have been made for circuit breaker interrupting time, relay timing error, overshoot and CT errors, the
discriminating relay must just fail to complete its operation.

Some extra safety margin is required to ensure that relay operation does not occur.

The setting should not be more than 33% of the maximum earth fault current of the generator, and  a lower setting would be preferable, depending on
grading  considerations.

Go back to contents ↑

2.1.2 Sensitive Earth Fault Protection

This method is used in the following situations:

a. Direct-connected generators operating in parallel.


b. Generators with high-impedance neutral earthing, the earth fault current being limited to a few tens of amps.
c. Installations where the resistance of the ground fault path is very high, due to the nature of the ground.

In these cases, conventional earth fault protection is of little use.

The earth fault (residual) current can be obtained from residual connection of line CTs, a line-connected CBCT, or a CT in
the generator neutral. The latter is not possible if directional protection is used. The polarising voltage is usually the neutral
voltage displacement input to the relay, or the residual of the three phase voltages, so a suitable VT must be used.

For Petersen Coil earthing, a wattmetric technique can also be used.

For direct connected generators operating in parallel, directional sensitive earth fault protection may be necessary. This is
to ensure that a faulted generator will be tripped before there is any possibility of the neutral overcurrent protection tripping
a parallel healthy generator.

When being driven by residually-connected phase CTs, the protection must be stabilised against incorrect tripping with
transient spill current in the event of asymmetric CT saturation when phase fault or magnetising inrush current is being
passed.
Stabilizing techniques include the addition of relay circuit impedance and/or the application of a time delay. Where the
required setting of the protection is very low in comparison to the rated current of the phase CTs, it would be necessary to
employ a single CBCT for the earth fault protection to ensure transient stability.

Since any generator in the paralleled group may be earthed, all  generators will require to be fitted with both neutral overcurrent protection and sensitive
directional earth fault  protection.

The setting of the sensitive directional earth fault protection is chosen to co-ordinate with generator differential protection
and/or neutral voltage displacement protection to ensure that 95% of the stator winding is protected.

Figure 2 illustrates the complete scheme, including optional blocking signals where difficulties in co-ordinating the
generator and downstream feeder earth-fault protection occur.

Figure 2 – Comprehensive earth-fault protection scheme


for direct-connected generators operating in parallel

For cases (b) and (c) above, it is not necessary to use a directional facility. Care must be taken to use the correct Relay
Characteristic Angle (RCA) setting – for instance if the earthing impedance is mainly resistive, this should be 0°.

On insulated or very high impedance earthed systems, an RCA of –90° would be used, as the earth fault current is
predominately capacitive.

Directional sensitive earth-fault protection can also be used for detecting winding earth faults. In this case, the relay
element is applied to the terminals of the generator and is set to respond to faults only within the machine windings.

Hence earth faults on the external system do not result in relay operation. However, current flowing from the system into
a winding earth-fault causes relay operation. It will not operate on the earthed machine, so that other types of earth-
fault protection must also be applied.

All generators must be so fitted, since any can be operated as the earthed machine.
Go back to contents ↑

2.1.3 Neutral Voltage Displacement Protection

In a balanced network, the addition of the three phase-earth voltages produces a nominally zero residual voltage,
since there would be little zero sequence voltage present.

Any earth fault will set up a zero sequence system voltage, which will give rise to a non-zero residual voltage.

This can be measured by a suitable relay element. The voltage signal must be derived from a VT that is suitable – i.e. it
must be capable of transforming zero-sequence voltage, so 3-limb types and those without a primary earth connection are
not suitable.

This unbalance voltage provides a means of detecting earth faults.

The relay element must be insensitive to third harmonic voltages that may be present in the system voltage waveforms, as
these will sum residually.

As the protection is still unrestricted, the voltage setting of the relay must be greater than the effective setting of
any downstream earth fault protection. It must also be time-delayed to co-ordinate with such protection.

Sometimes, a second high-set element with short time delay is used to provide fast-acting protection against major winding
earth faults.

Figure 3 illustrates the possible connections that may be used.

Figure 3 – Neutral voltage displacement protection

Go back to contents ↑

2.2 Indirectly-Connected Generators

As noted at the beginning of this article, a directly-earthed generator-transformer unit cannot interchange zero-sequence
current with the remainder of the network, and hence an earth fault protection grading problem does not exist.
The following paragraphs detail the protection methods for the various forms of impedance earthing of generators:

Go back to contents ↑

2.2.1 High Resistance Earthing – Neutral Overcurrent Protection

A current transformer mounted on the neutral-earth conductor can drive an instantaneous and/or time delayed
overcurrent relay element, as shown in Figure 4 below.

It is impossible to provide protection for the whole of the winding, and Figure 4 also details how the percentage of winding
covered can be calculated. For a relay element with an instantaneous setting, protection is typically limited to 90% of the
winding.

This is to ensure that the protection will not maloperate with zero sequence current during operation of a primary fuse for
a VT earth fault or with any transient surge currents that could flow through the interwinding capacitance of the step-
up transformer for an HV system earth fault.

A time-delayed relay is more secure in this respect, and it may have a setting to cover 95% of the stator winding.

Figure 4 – Earth fault protection of high-resistance


earthed generator stator winding using a current
element

Since the generating units under consideration are usually large, instantaneous and time delayed relay elements are
often applied, with settings of 10% and 5% of maximum earth fault current respectively. This is the optimum compromise
in performance.

The portion of the winding left unprotected for an earth fault is at the neutral end. Since the voltage to earth at this end of
the winding is low, the probability of an earth fault occurring is also low.

Hence additional protection is often not applied.

Go back to contents ↑

2.2.2 Distribution Transformer Earthing Using a Current Element

In this arrangement, shown in Figure 5(a), the generator is earthed via the primary winding of a distribution transformer. The
secondary winding is fitted with a loading resistor to limit the earth fault current.
An overcurrent relay element energized from a current transformer connected in the resistor circuit is used to measure
secondary earth fault current. The relay should have an effective setting equivalent to 5% of the maximum earth fault
current at rated generator voltage, in order to protect 95% of the stator winding.

The relay element response to third harmonic current should be limited to prevent incorrect operation when a sensitive
setting is applied.

Figure 5 – Generator winding earth-fault


protection: distribution transformer
earthing
– Protection using a current element

As discussed in above section ”High Resistance Earthing – Neutral Overcurrent Protection”, the protection should be
time delayed when a sensitive setting is applied, in order to prevent mal-operation under transient conditions.

It also must grade with generator VT primary protection (for a VT primary earth fault). An operation time in the range 0.5s-
3s is usual.

Less  sensitive instantaneous protection can also be applied to  provide fast tripping for a heavier earth fault condition.

Go back to contents ↑

2.2.3 Distribution Transformer Earthing Using a Voltage Element

Earth fault protection can also be provided using a voltage-measuring element in the secondary circuit instead. The setting
considerations would be similar to those for the current operated protection, but transposed to voltage.

The circuit diagram is shown in Figure 6.


Figure 6 – Generator winding earth-fault
protection: distribution transformer
earthing
– Protection using a voltage element

Application of both voltage and current operated elements to a generator with distribution transformer earthing provides
some advantages. The current operated function will continue to operate in the event of a short-circuited loading resistor
and the voltage protection still functions in the event of an open-circuited resistor.

However, neither scheme will operate in the event of a flashover on the primary terminals of the transformer or of the
neutral cable between the generator and the transformer during an earth fault.

A CT could be added in the neutral connection close to the generator, to energize a high-set overcurrent element to detect
such a fault, but the fault current would probably be high enough to operate the phase differential protection.

Go back to contents ↑

2.2.4 Neutral Voltage Displacement Protection

This can be applied in the same manner as for direct-connected generators. The only difference is that there are no
grading problems as the protection is inherently restricted.

A sensitive setting can therefore be used, enabling cover of up to 95% of the stator winding to be achieved.

Go back to contents ↑

2.3 Restricted Earth Fault Protection

This technique can be used on small generators not fitted with differential protection to provide fast acting earth
fault protection within a defined zone that encompasses the generator.

It is cheaper than full differential protection, but only provides protection against earth faults. The principle is that used for
transformer REF protection.

However, in contrast to transformer REF protection, both biased low-impedance and high-impedance techniques can be
used.

Go back to contents ↑

2.3.1 Low-Impedance Biased REF Protection


This is shown in Figure 7. The main advantage is that the neutral CT can also be used in a modern relay to
provide conventional earth-fault protection and no external resistors are used.

Relay bias is required, but the formula for calculating the bias is slightly different and also shown in Figure 7.

Figure 7 – Low impedance biased REF protection of a generator

The initial bias slope is commonly set to 0% to provide maximum sensitivity, and applied up to the rated current of
the generator. It may be increased to counter the effects of CT mismatch. The bias slope above generator rated current
is typically set to 150% of rated value.

The initial current setting is typically 5% of the minimum earth fault current for a fault at the machine terminals.

Go back to contents ↑

2.3.2 High Impedance REF Protection

The same technique as of high impedance differential protection can be used for earth-fault protection of a generator,
using three residually connected phase CTs balanced against a similar single CT in the neutral connection.

Settings of the order of 5% of maximum earth fault current at the generator terminals are typical.

The usual requirements in respect of stabilizing resistor and non-linear resistor to guard against excessive voltage across
the relay must be taken, where necessary.

Go back to contents ↑

2.4 Earth Fault Protection for the Entire Stator Winding

All of the methods for earth fault protection detailed so far leave part of the winding unprotected. In most cases, this is
of no consequence as the probability of a fault occurring in the 5% of the winding nearest the neutral connection is very
low, due to the reduced phase to earth voltage.
However, a fault can occur anywhere along the stator windings in the event of insulation failure due to localized heating
from a core fault.

In  cases where protection for the entire winding is required,  perhaps for alarm only, there are various methods available:

Go back to contents ↑

2.4.1 Measurement of Third Harmonic Voltage

One method is to measure the internally generated third harmonic voltage that appears across the earthing impedance due
to the flow of third harmonic currents through the shunt capacitance of the stator windings etc.

When a fault occurs in the part of the stator winding nearest the neutral end, the third harmonic voltage drops to near zero,
and hence a relay element that responds to third harmonic voltage can be used to detect the condition. As the fault
location moves progressively away from the neutral end, the drop in third harmonic voltage from healthy conditions
becomes less, so that at around 20-30% of the winding distance, it no longer becomes possible to discriminate between a
healthy and a faulty winding.

Hence, a conventional earth-fault scheme should be used in conjunction with a third harmonic scheme, to provide
overlapping cover of the entire stator winding.

The measurement of third harmonic voltage can be taken either from a star-point VT or the generator line VT. In the latter
case, the VT must be capable of carrying residual flux, and this prevents the use of 3-limb types.

If the third harmonic voltage is measured at the generator star point, an undervoltage characteristic is used.

An overvoltage characteristic is used if the measurement is taken from the generator line VT. For effective application of
this form of protection, there should be at least 1% third harmonic voltage across the generator neutral earthing impedance
under all operating conditions.

A problem encountered is that the level of third harmonic voltage generated is related to the output of the generator. The
voltage is low when generator output is low.

In order to avoid maloperation when operating at low power output, the relay element can be inhibited using an overcurrent
or power elements (kW, kVAr or kVA) and internal programmable logic.

Go back to contents ↑

2.4.2 Use of Low-Frequency Voltage Injection

Another method for protecting the entire stator winding of a generator is to deploy signal injection equipment to inject a
low frequency voltage between the stator star point and earth.

An earth fault at any winding location will result in the flow of a measurable injection current to cause protection
operation. This form of protection can provide earth fault protection when the generator is at standstill, prior to run-up.

It is also an appropriate method to apply to variable speed synchronous machines. Such machines may be employed for
variable speed motoring in pumped-storage generation schemes or for starting a large gas turbine prime mover.