Tutorial Sheet-2
Tutorial Sheet-2
1. For the system in below figure the rating of the various components are:
Generator : 25 MVA, 12.4 kV, 10% subtransiant reactance
Motor : 20 MVA, 3.8 kV, 15% subtransiant reactance
Transformer T1 : 25 MVA, 11/33 kV, 8% reactance
Transformer T2 : 20 MVA, 33/3.3 kV, 10% reactance
Line : 20 ohms reactance
10. A generator supplies a group of identical motors as shown in Fig. The motors are rated
600V,90% efficiencty at full load unity pf with sum of their output ratings being 5 MW.
The motors are sharing equally a load of 4 MW at rated voltage, 0.8 pf lagging and 90%
efficiency when an LG fault occurse on the low voltage side of the transformer. Specify
completely the sequence networks to simulate the fault so as to include the effect of
the prefault current. The group of motors can be treated as a single equivalent motor.
Find the subtransient line currents in all parts of the system with pre fault current
ignored.
[Iag=0, Ibg=-j2.08 pu, Icg=j2.08 pu, Iam=-j3.51 pu, Ibm=-j1.2 pu, Icm=-j1.2 pu,]
11.
[5,266A]
12