This document provides technical specifications for three different power transformers with rated powers of 400 kVA, 1600 kVA, and 2500 kVA. All three transformers have mineral oil insulation, three phases, and Dyn11 vector groups. They also have hermetically sealed tanks, corrugated cooling fins, and accessories that include bushings, tap changers, and monitoring devices. The specifications provide details on voltages, insulation levels, impedance, losses, materials, and performance standards.

Uploaded by

Osama Masood
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views

Data Sheets

This document provides technical specifications for three different power transformers with rated powers of 400 kVA, 1600 kVA, and 2500 kVA. All three transformers have mineral oil insulation, three phases, and Dyn11 vector groups. They also have hermetically sealed tanks, corrugated cooling fins, and accessories that include bushings, tap changers, and monitoring devices. The specifications provide details on voltages, insulation levels, impedance, losses, materials, and performance standards.

Uploaded by

Osama Masood
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

abb

Technical data sheet

1. Characteristic
Rated Power [kVA] 400
Insulation Liquid Mineral oil (IEC60296 I -10)
Primary voltage [V] 6300
Primary taps type / tappings Off load / +2,-2x2.5%
Secondary voltage at no load [V] 415
Primary insulation level [kV] LI60/AC20
Secondary insulation level [kV] LI-/AC3
Frequency [Hz] 50
Number of phases 3
Vector group Dyn11
Max. average temperature rise (Oil/Winding) [K/K] 50/55
Surface treatment Powder coating
Surface color B05
Max. altitude [m] 1000

2. Performance values
Standards IEC
Impedance [%] 4 (TOL-10%,+10%) 5.5
No load losses [W] 930 (TOL≤+15%) 2340
Load losses at 75°C [W] 6000 (TOL≤+15%) 20200

3. Type of design
Tank construction Hermetically Sealed
Radiator type Corrugated cooling fins
Cooling ONAN
Primary winding conductor material Cu
Secondary winding conductor material Cu

4. Accessories Qty.
HV bushings 3
LV bushings 4
Off-load tap changer 1
Oil filling tube 1
Oil drain device 1
Thermometer pocket 1
Pressure release valve 1
Gas relay 1
Oil temperature indicator 1
Terminal box 1
Oil level indicator 1
abb
Technical data sheet

1. Characteristic
Rated Power [kVA] 1600
Insulation Liquid Mineral oil (IEC60296 I -10)
Primary voltage [V] 6300
Primary taps type / tappings Off load / +2,-2x2.5%
Secondary voltage at no load [V] 415
Primary insulation level [kV] LI60/AC20
Secondary insulation level [kV] LI-/AC3
Frequency [Hz] 50
Number of phases 3
Vector group Dyn11
Max. average temperature rise (Oil/Winding) [K/K] 50/55
Surface treatment Powder coating
Surface color B05
Max. altitude [m] 1000

2. Performance values
Standards IEC
Impedance [%] 6 (TOL-10%,+10%) 5.5
No load losses [W] 2600 (TOL≤+15%) 2340
Load losses at 75°C [W] 20000 (TOL≤+15%) 20200

3. Type of design
Tank construction Hermetically Sealed
Radiator type Corrugated cooling fins
Cooling ONAN
Primary winding conductor material Cu
Secondary winding conductor material Cu

4. Accessories Qty.
HV bushings 3
LV bushings 4
Off-load tap changer 1
Oil filling tube 1
Oil drain device 1
Thermometer pocket 1
Pressure release valve 1
Gas relay 1
Oil temperature indicator 1
Terminal box 1
Oil level indicator 1
abb
Technical data sheet

1. Characteristic
Rated Power [kVA] 2500
Insulation Liquid Mineral oil (IEC60296 I -10)
Primary voltage [V] 6300
Primary taps type / tappings Off load / +2,-2x2.5%
Secondary voltage at no load [V] 415
Primary insulation level [kV] LI60/AC20
Secondary insulation level [kV] LI-/AC3
Frequency [Hz] 50
Number of phases 3
Vector group Dyn11
Max. average temperature rise (Oil/Winding) [K/K] 50/55
Surface treatment Powder coating
Surface color B05
Max. altitude [m] 1000

2. Performance values
Standards IEC
Impedance [%] 8 (TOL-10%,+10%) 5.5
No load losses [W] 3500 (TOL≤+15%) 2340
Load losses at 75°C [W] 32000 (TOL≤+15%) 20200

3. Type of design
Tank construction Hermetically Sealed
Radiator type Corrugated cooling fins
Cooling ONAN
Primary winding conductor material Cu
Secondary winding conductor material Cu

4. Accessories Qty.
HV bushings 3
LV bushings 4
Off-load tap changer 1
Oil filling tube 1
Oil drain device 1
Thermometer pocket 1
Pressure release valve 1
Gas relay 1
Oil temperature indicator 1
Terminal box 1
Oil level indicator 1