C264 Enct C30
C264 Enct C30
MiCOM C264/C264C
COMMUNICATIONS
Communications C264/EN CT/C30
CONTENT
2. SCP COMMUNICATION 6
2.1 Communication on Station bus 6
2.1.1 Finality 6
2.1.2 Inputs 6
2.1.3 Supported services 7
2.1.4 Supported data objects 7
3. SCADA COMMUNICATION 8
3.1 Overview 8
3.2 SCADA common functionality 8
3.2.1 Interface to SCADA 8
3.2.2 Behaviour and specific treatments 9
3.2.3 Data sent to SCADA 10
3.2.4 Data sent to MiCOM C264 12
3.3 Slave DNP3 profile 13
3.3.1 DNP3 level 3: IMPLEMENTATION TABLE 16
3.4 Slave IEC 60870-5-101 profile 20
3.4.1 System or device 20
3.4.2 Network configuration 20
3.4.3 Physical layer 21
3.4.4 Link layer 21
3.4.5 Application layer 22
3.4.6 Basic application functions 26
3.4.7 Protocol Requirements 30
3.4.8 Application Functions 30
3.5 Slave IEC 60870-5-104 Server profile 32
3.5.1 System or device 32
3.5.2 Network configuration (Network-specific parameter) 32
3.5.3 Physical layer (Network-specific parameter) 33
3.5.4 Link layer (Network specific parameter) 33
3.5.5 Protocol Requirements 34
3.5.6 Application layer 34
3.5.7 Basic application functions 40
3.6 Slave DNP3 (TCP/IP) profile 43
C264/EN CT/C30 Communications
4. IED COMMUNICATION 53
4.1 Overview 53
4.2 IED Common functionality 53
4.2.1 Interface to IEDs 53
4.2.2 Behaviour 54
4.2.3 Data received from IEDs 58
4.2.4 Data sent to IEDs 58
4.2.5 Tunnelling 59
4.2.6 Limits and Performances 62
4.3 MODBUS communication 62
4.3.1 Finality 62
4.3.2 Interface to IEDs 62
4.3.3 Behaviour 63
4.3.4 Data received from IEDs 63
4.3.5 Data sent to IEDs 64
4.3.6 Error management 64
4.3.7 Limits and Performances 64
4.4 DNP 3.0 Communication 65
4.4.1 Finality 65
4.4.2 Interface to IEDs 65
4.4.3 Behaviour 66
4.4.4 Data received from IEDs 67
4.4.5 Data sent to IEDs 67
4.4.6 Master DNP3.0 Profile 68
4.4.7 DNP.3 Level 3 IMPLEMENTATION TABLE 71
Communications C264/EN CT/C30
BLANK PAGE
Communications C264/EN CT/C30
2. SCP COMMUNICATION
2.1 Communication on Station bus
2.1.1 Finality
This item describes IEC61850-8-1 implementation inside MiCOM C264.
2.1.2 Inputs
2.1.2.1 Information: MiCOM C264 application SCP
The type of information that can be transmitted are:
• Counters
• Controls
• Control acknowledgements
• MiCOM C264 information (Init. report, Operating mode, control mode, Date)
2.1.2.2 Information SCP MiCOM C264 application
The type of information that can be transmitted are:
• Counters
• Controls
• Control acknowledgements
• Database downloading
Communications C264/EN CT/C30
Client Server
Common Class Comment
support support
Status
SPS Single input status YES YES
DPS Double input status YES YES
INS Integer input status YES YES
ACT Protection activation information YES YES
ACD Directional protection activation YES YES
information
Measurements
MV Measurement value YES YES
CMV Complex measurement value YES YES
WYE 3 phase + N measurement YES YES
DELTA Phase to phase measurement YES YES
Counters
BCR Binary counter YES YES
Control
SPC Single point control YES YES
DPC Double control output YES YES
BSC Binary step control YES YES
APC Analogue output YES YES
INC Integer control output YES YES
ISC Integer step control output YES YES
Description
LPL Logical node name plate YES YES
DPL Device name plate YES YES
Report Control Block
URCB Unbuffered report control block YES YES
BRCB Buffered report control block NO YES
C264/EN CT/C30 Communications
3. SCADA COMMUNICATION
3.1 Overview
A MiCOM C264 can be connected to a SCADA through networks using various protocols:
1. DNP3 (serial link)
2. T101 (serial link)
3. T104 (TCP/IP link)
4. DNP3 (TCP/IP link)
5. MODBUS (serial link)
It is possible to have:
• The same protocol on two links (redundant mode). This is actually not supported for
Modbus protocol.
• For protocols running on TCP/IP link, there is only one Ethernet port. So redundancy
is not available for those protocols, and they all are physically running on the same
network (including IEC61850 protocol).
• In T104 protocol the C264 (server) can manage two clients. These two clients have
separate configurations but may have same data. On the SCADA port, up to four front
ends can be defined, corresponding to one active port and three backup ports. So, up
to four IP addresses will be defined during the configuration of each T104 client. If
both clients are communicating with the computer, they must manage thein own
redundancy for doing controls with coherency.
Common features to all SCADA communication and all protocols are specified below.
Specific features to each protocol are specified in subsequent paragraphs.
3.2 SCADA common functionality
3.2.1 Interface to SCADA
This paragraph describes the exchange of data between the “SCADA communication”
function and the Master SCADA. It is split into two sub-paragraphs:
3.2.1.2 Output
• At a given time, only one SCADA can send controls to the substation (the one which
has the control).
− Reset the “Taking Control Binary input” of the SCADA which had previously the
control
− Set the “Taking Control Binary input” of the SCADA which asks the control
If the take control command is set for a SCADA, MiCOM C264 should refuse all commands
from other SCADAs.
3.2.2.7 SBMC mode
This mode is used to test a substation while it is in Remote mode. As this mode is a test
mode, MiCOM C264 won’t send all changes of state to SCADA.
When bay turns to SBMC mode, MiCOM C264 will send to SCADA all concerned data
(configured Bay Based in the SCE) at specific states defined in the SCE for the management
of SBMC.
For those data, change of state won’t be transmitted, but will be memorised by MiCOM C264
while the Bay is in SBMC mode.
When the Bay returns to Non SBMC mode, MiCOM C264 will send the current state of any
data that has changed whilst the Bay has been in SBMC mode.
3.2.2.8 Redundancy
Serial links can be configured as redundant. In this case, SCADA can send requests on both
serial links: “main link “or “redundant link”.
MiCOM C264 always responds on the link used by SCADA for requesting the slave
3.2.2.9 Automatic synchrocheck
SCADA can send control to synchronised circuit breakers with a facility to bypass the
synchrocheck.
3.2.3 Data sent to SCADA
After the initialisation sequence, MiCOM C264 Slave sends the state of all of its data to the
SCADA. The current state of data is sent as state or as change of state messages,
depending on the protocol.
The data, which can be sent to SCADA, is detailed in the paragraphs below.
Communications C264/EN CT/C30
− The percentage of filling from which the MiCOM C264 will try to transmit the SOE
file
• When the SOE is full, the oldest Event is deleted and the new one is added
• Once a SOE file has been successfully up-loaded, all Event sent are deleted from
SOE
3.2.3.7 Synchronisation status
MiCOM C264 can inform the controlling station about its synchronisation status.
According to the protocol, this may be done by a specific message or by a binary input.
3.2.4 Data sent to MiCOM C264
SCADA can send data to MiCOM C264. The type of data is described in subsequent
paragraphs.
3.2.4.1 Digital Controls or setpoints
A control is transmitted to the handling of control sequences function.
At the end of the control sequence an acknowledgement is sent to SCADA if protocol allows
it.
3.2.4.2 Counter commands
The commands allowed on counters are:
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events
Specific variation requested: When no specific variation requested:
Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable to send both, one or the other Configurable (attach explanation)
(explanation below)
User option to have all Binary Input
Change Events returned as either:
• time-tagged OR
• non-time-tagged
Communications C264/EN CT/C30
User option to return all static counters in User option to select roll over:
One of the following variations: • 32 bit counters roll over at 2^32.
• 32-Bit Binary Counter • 16 bit counters roll over at 2^16
• 32-Bit Binary Counter Without Flag
• 16-Bit Binary Counter
• 16-Bit Binary Counter Without Flag
Send Multi-Fragment Responses: Yes No
Binary Input (BI) double management:
For a BI double, two binary inputs are configured, with a point address for the open contact and the
address + 1 for the close contact. All the BI double are transmitted this way.
C264/EN CT/C30 Communications
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes (2)
(dec) (hex)
(dec) (hex)
1 0 Binary Input – All Variations 1 00,01,06,17,28
1 1 Binary Input 1 00,01,06, 17,28 129 00,17,28
1 2 Binary Input with Status 1 00,01,06,17,28 129 00,17,28
2 0 Binary Input Change - All Variations 1 06,07,08 129,130 17
2 1 Binary Input Change without Time 1
2 2 Binary Input Change with Time 1 06,07,08 129,130 17
2 3 Binary Input Change with Relative Time 1
10 0 Binary Output - All Variations 1
10 1 Binary Output
10 2 Binary Output Status 1
12 0 Control Block - All Variations (1)
12 1 Control Relay Output Block (1) 3,4,5,6 17,28 129 Request
echo
12 2 Pattern Control Block
12 3 Pattern Mask
20 0 Binary Counter - All Variations 1,7,8,9,10 00,01,06,17,28
20 1 32-Bit Binary Counter 1 00,01,06,17,28 129 00,17,28
20 2 16-Bit Binary Counter 1 00,01,06,17,28 129 00,17,28
20 3 32-Bit Delta Counter
20 4 16-Bit Delta Counter
20 5 32-Bit Binary Counter without Flag 1 00,01,06,17,28 129 00,17,28
20 6 16-Bit Binary Counter without Flag 1 00,01,06,17,28 129 00,17,28
20 7 32-Bit Delta Counter without Flag
20 8 16-Bit Delta Counter without Flag
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes (2)
(dec) (hex)
(dec) (hex)
21 0 Frozen Counter - All Variations 1 00,01,06,17,28
21 1 32-Bit Frozen Counter 1 00,01,06,17,28 129 00,17,28
21 2 16-Bit Frozen Counter 1 00,01,06,17,28 129 00,17,28
21 3 32-Bit Frozen Delta Counter
21 4 16-Bit Frozen Delta Counter
21 5 32-Bit Frozen Counter with Time of
Freeze
21 6 16-Bit Frozen Counter with Time of
Freeze
21 7 32-Bit Frozen Delta Counter with Time
of Freeze
21 8 16-Bit Frozen Delta Counter with Time
of Freeze
21 9 32-Bit Frozen Counter without Flag 1 00,01,06,17,28 129 00,17,28
21 10 16-Bit Frozen Counter without Flag 1 00,01,06,17,28 129 00,17,28
21 11 32-Bit Frozen Delta Counter without
Flag
21 12 16-Bit Frozen Delta Counter without
Flag
22 0 Counter Change Event - All Variations 1 06,07,08
22 1 32-Bit Counter Change Event without
Time
22 2 16-Bit Counter Change Event without
Time
22 3 32-Bit Delta Counter Change Event
without Time
22 4 16-Bit Delta Counter Change Event
without Time
22 5 32-Bit Counter Change Event with Time 1 06,07,08 129,130 17
22 6 16-Bit Counter Change Event with Time 1 06,07,08 129,130 17
22 7 32-Bit Delta Counter Change Event with
Time
22 8 16-Bit Delta Counter Change Event with
Time
23 0 Frozen Counter Event - All Variations 1 06,07,08
23 1 32-Bit Frozen Counter Event without
Time
23 2 16-Bit Frozen Counter Event without
Time
23 3 32-Bit Frozen Delta Counter Event
without Time
23 4 16-Bit Frozen Delta Counter Event
without Time
23 5 32-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17
23 6 16-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17
23 7 32-Bit Frozen Delta Counter Event with
Time
23 8 16-Bit Frozen Delta Counter Event with
Time
C264/EN CT/C30 Communications
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes (2)
(dec) (hex)
(dec) (hex)
30 0 Analog Input - All Variations 1 00,01,06,17,28
30 1 32-Bit Analog Input 1 00,01,06,17,28 129 00, 17,28
30 2 16-Bit Analog Input 1 00,01,06,17,28 129 00,17,28
30 3 32-Bit Analog Input without Flag 1 00,01,06,17,28 129 00,17,28
30 4 16-Bit Analog Input without Flag 1 00,01,06,17,28 129 00,17,28
31 0 Frozen Analog Input - All Variations
31 1 32-Bit Frozen Analog Input
31 2 16-Bit Frozen Analog Input
31 3 32-Bit Frozen Analog Input with Time of
Freeze
31 4 16-Bit Frozen Analog Input with Time of
Freeze
31 5 32-Bit Frozen Analog Input without Flag
31 6 16-Bit Frozen Analog Input without Flag
32 0 Analog Change Event - All Variations 1 06,07,08
32 1 32-Bit Analog Change Event without 1 06,07,08 129,130 17
Time
32 2 16-Bit Analog Change Event without 1 06,07,08 129,130 17
Time
32 3 32-Bit Analog Change Event with Time 1 06,07,08 129,130 17
32 4 16-Bit Analog Change Event with Time 1 06,07,08 129,130 17
33 0 0 Frozen Analog Event - All Variations
33 1 32-Bit Frozen Analog Event without
Time
33 2 16-Bit Frozen Analog Event without
Time
33 3 32-Bit Frozen Analog Event with Time
33 4 16-Bit Frozen Analog Event with Time
40 0 Analog Output Status - All Variations
40 1 32-Bit Analog Output Status
40 2 16-Bit Analog Output Status
41 0 Analog Output Block - All Variations
41 1 32-Bit Analog Output Block 3,4,5,6 17,28 129 Request
echo
41 2 16-Bit Analog Output Block 3,4,5,6 17,28 129 Request
echo
50 0 Time and Date - All Variations
50 1 Time and Date 1,2 07 (quantity=1)
50 2 Time and Date with Interval
51 0 Time and Date CTO - All Variations
51 1 Time and Date CTO
51 2 Unsynchronized Time and Date CTO
52 0 Time Delay - All Variations
52 1 Time Delay Coarse
52 2 Time Delay Fine
Communications C264/EN CT/C30
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes (2)
(dec) (hex)
(dec) (hex)
60 0
60 1 Class 0 Data 1 06,07,08
60 2 Class 1 Data 1 06,07,08
20,21 06
60 3 Class 2 Data 1 06,07,08
20,21 06
60 4 Class 3 Data 1 06,07,08
20,21 06
70 0 File management – All variations
70 2 Authentication Object 29 5b 129 5b
70 3 File Command Object 25,27 5b 129 5b
70 4 File Command Status Object 26,30 5b 129 5b
70 5 File Transfert Object 1,2 5b 129 5b
70 7 File Description 28 5b 129 5b
80 1 Internal Indications
81 1 Storage Object
82 1 Device Profile
83 1 Private Registration Object
83 2 Private Registration Object Descriptor
90 1 Application Identifier
100 1 Short Floating Point
100 2 Long Floating Point
100 3 Extended Floating Point
101 1 Small Packed Binary-Coded Decimal
101 2 Medium Packed Binary-Coded Decimal
101 3 Large Packed Binary-Coded Decimal
No Object (Cold Restart)
No Object (Warm Restart)
No Object (Delay Measurement
C264/EN CT/C30 Communications
The possible selection (blank, X, R or B) is specified for each specific clause or parameter.
NOTE: In addition, the full specification of a system may require individual selection of
certain parameters for certain parts of the system, such as the individual selection
of scaling factors for individually addressable measured values.
3.4.1 System or device
(system specific parameter, indicates the definition of a system or a device by marking one
of the following with ‘X’)
System definition
Unbalanced interchange
CIRCUIT V24/V28 Balanced interchange
Recommended if Circuit X24/X27
Standard
> 1200 bits/s
100 bits/s ⌧ 2400 bits/s ⌧ 2400 bits/s 56000 bits/s
Unbalanced interchange
Circuit V24/V28 Balanced interchange
Recommended if Circuit X24/X27
Standard
> 1200 bits/s
100 bits/s ⌧ 2400 bits/s ⌧ 2400 bits/s 56000 bits/s
200 bits/s ⌧ 4800 bits/s ⌧ 4800 bits/s 64000 bits/s
⌧ Two octets
Structured
⌧ Unstructured
⌧ Three octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked ‘X’)
⌧ <14> := Measured value, short floating point value with time tag M_ME_TC_1
⌧ <18> := Packed start events of protection equipment with time tag M_EP_TB_1
⌧ <19> := Packed output circuit transmission of protection equipment with time tag M_EP_TC_1
⌧ <36> := Measured value, short floating point number with time tag CP56Time2a M_ME_TF_1
⌧ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
⌧ <40> := Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1
File transfer
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ <122> := Call directory, select file, call file, call section F_SC_NA_1
<3> M_DP_NA_1 X X X X
<4> M_DP_TA_1 X X
<5> M_ST_NA_1 X X X X
<6> M_ST_TA_1 X X
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1 X
<11> M_ME_NB_1 X X X X
<12> M_ME_TB_1 X
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1 X
<15> M_IT_NA_1 X X
<16> M_IT_TA_1 X X
<17> M_EP_TA_1
<18> M_EP_TB_1 X
<19> M_EP_TC_1 X
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X
<31> M_DP_TB_1 X X
<32> M_ST_TB_1 X X
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1 X
<40> M_EP_TF_1 X
<45> C_SC_NA_1 X X X X X X X X
C264/EN CT/C30 Communications
<111> P_ME_NB_1 X
<112> P_ME_NC_1 X
<113> P_AC_NA_1 X
<120> F_FR_NA_1 X X X X
<121> F_SR_NA_1 X X X X
<122> F_SC_NA_1 X X X X
<123> F_LS_NA_1 X X X X
<124> F_AF_NA_1 X X X X
<125> F_SG_NA_1 X X X X
<126> F_DR_TA_1 X X
<136> M_DB_NA_1 X
<137> C_RC_NB_1 X X X X X X X X
Remote initialisation
Read procedure
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
Read procedure
Communications C264/EN CT/C30
Spontaneous transmission
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Spontaneous transmission
General interrogation
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ global
⌧ group 6 ⌧ group 12
⌧ global
⌧ group 4
Clock synchronisation
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Clock synchronisation
Notes: – The controlled station does not report the change of hour by
sending a clock synchronisation message (ASDU 103) to the
controlling station.
– When the controlling station send to controlled station a clock
synchronisation and if the system (includes controlled station), isn’t
synchronized by an other source: the clock synchronisation
response is positive.
– When the controlling station send to controlled station a clock
synchronisation and if the system (includes controlled station), is
synchronized by an other source: the clock synchronisation
response is negative.
C264/EN CT/C30 Communications
Command transmission
(object -specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ No additional definition
Persistent output
Parameter loading
(object-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
Threshold value
Smoothing factor
Parameter activation
(object-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
Test procedure
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Test procedure
File transfer
(station-specific parameter), mark ‘X’ if function is used)
File transfert in monitor direction
⌧ Transparent file
Transparent file
Background scan
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Background scan
Class 2 data
The following types of information must be configured at the controlled station to be Class 2:
Command transmission
All control commands shall be Select before Execute, or Direct Execute.
For only the control commands: Activation termination is returned to the controlling station to
signal the end of a control sequence.
The QU field of the Qualifier of Command shall be set to zero (0), no additional definition.
Test procedure
A test command may be issued by the controlling station to ensure the availability of the
communications link and the commands subsystem.
Test commands are received at the controlled station on the active link. The controlled
station mirrors the test command, on the link from which it was received, with a cause of
transmission indicating activation confirmation.
An error response should be sent if the command is incorrect, with a cause of transmission
indicating negative activation confirmation.
3.5 Slave IEC 60870-5-104 Server profile
This companion standard presents sets of parameters and alternatives from which subsets
have to be selected to implement particular telecontrol systems. Certain parameter values,
such as the choice of “structured” or “unstructured” fields of the INFORMATION OBJECT
ADDRESS of ASDU represent mutually exclusive alternatives. This means that only one value
of the defined parameters is admitted per system. Other parameters, such as the listed set of
different process information in command and in monitor direction allow the specification of
the complete set or subsets, as appropriate for given applications. This clause summarises
the parameters of the previous clauses to facilitate a suitable selection for a specific
application. If a system is composed of equipment stemming from different manufacturers it
is necessary that all partners agree on the selected parameters.
Paragraph in grey are those which are not applicable for the IEC 60870-5-104 profile.
The selected parameters should be filled up ( ).
NOTE: In addition, the full specification of a system may require individual selection of
certain parameters for certain parts of the system, such as the individual selection
of scaling factors for individually addressable measured values.
To simplify the PID , we use the following conventions:
Not supported
Supported
3.5.1 System or device
System definition
Controlling station definition (Master)
Controlled station definition (Slave)
3.5.2 Network configuration (Network-specific parameter)
Point-to-point Multipoint-party line
Multiple point-to-point Multipoint-star
Communications C264/EN CT/C30
Structured
Unstructured
Frame length
_255_ Maximum length L (number of bytes)
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
C264/EN CT/C30 Communications
Cause of transmission
(System-specific parameter)
Length of APDU
(System-specific parameter)
The maximum length of APDU is 253 (default) The maximum length may be reduced by the
system.
File transfer
(station specific parameter)
<1> M_SP_NA_1 X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1 X X X X
<4> M_DP_TA_1 .
<5> M_ST_NA_1 X X X X
<6> M_ST_TA_1 .
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1
<11> M_ME_NB_1 X X X X
<12> M_ME_TB_1
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X
<31> M_DP_TB_1 X X
<32> M_ST_TB_1 X X
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1 X
<40> M_EP_TF_1 X
<45> C_SC_NA_1 X X X X X X X X
<46> C_DC_NA_1 X X X X X X X X
<47> C_RC_NA_1 X X X X X X X X
<48> C_SE_NA_1 X X X X X X X X
<49> C_SE_NB_1 X X X X X X X X
<50> C_SE_NC_1 X X X X X X X X
Communications C264/EN CT/C30
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X X X X
<59> C_DC_TA_1 X X X X X X X X
<60> C_RC_TA_1 X X X X X X X X
<61> C_SE_TA_1 X X X X X X X X
<62> C_SE_TB_1 X X X X X X X X
<63> C_SE_TC_1 X X X X X X X X
<64> C_BO_TA_1
<70> M_EI_NA_1 X
<100> C_IC_NA_1 X X X X X X X X
<101> C_CI_NA_1 X X X X X X
<102> C_RD_NA_1
<103> C_CS_NA_1 X X X X X
<104> C_TS_NA_1
<105> C_RP_NA_1
<106> C_CD_NA_1
<107> C_TS_TA_1 X X X
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1 X X
<121> F_SR_NA_1 X X
<122> F_SC_NA_1 X X X
<123> F_LS_NA_1 X X
<124> F_AF_NA_1 X X
<125> F_SG_NA_1 X X
<126> F_DR_TA_1 X X
<136> M_DB_NA_1
<137> C_RC_NB_1 X X X X X X X X
<138> C_RC_TB_1 X X X X X X X X
Remote initialisation
Read procedure
Spontaneous transmission
(Station-specific parameter)
Spontaneous transmission
General interrogation
(System or station-specific parameter)
Global
Group 1 Group 7 Group 13
Group 2 Group 8 Group 14
Group 3 Group 9 Group 15
Group 4 Group 10 Group 16
Group 5 Group 11
Group 6 Group 12 Information Object Addresses
assigned to each group must be
shown in a separate table
Global
Group 1 Group 3
Group 2 Group 4
Clock synchronisation
(Station specific parameter)
Clock synchronisation
Command transmission
(Object specific parameter)
No additional definition
Short pulse duration (duration determined by a system parameter in the outstation)
Long pulse duration (duration determined by a system parameter in the outstation)
Persistent output
Parameter loading
(Object-specific parameter)
Threshold value
Smoothing factor
Low limit for transmission of measured value
High limit for transmission of measured value
Parameter activation
(Object-specific parameter)
Test procedure
(Station-specific parameter)
Test procedure
File transfer
(Station-specific parameter)
File transfer in monitor direction
Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Transmission of sequences of recorded analogue values
Transparent file
Background scan
(Station-specific parameter)
Background scan
Ethernet 802.3
Serial X.21 interface
Other selection from RFC 2200
• If the slave device receives the query without communication error, and can handle
the query normally, it returns a normal response.
• If the slave does not receive the query due to a communication error, no response is
returned. The master program will process a timeout condition for query.
• If the slave receives the query, but detect a communication error [ bad CRC or framing
error for example ], no response is returned. The master program will process a
timeout condition for query.
• If the slave device receives the query without communication error, but cannot handle
it, the salve will return an exception response informing the master of the nature of the
error.
3.7.2.2 Exception Responses Codes
The exception code is sent as an 8-bit data, the range of valid codes is 1-8 in the protocol.
Supported exception responses codes are:
17 REPORT SLAVE ID NO
18 PROGRAM 884/M84 NO
19 RESET COMM. LINK NO
20 READ GENERAL REFERENCE NO
21 WRITE GENERAL REFERENCE NO
22 MASK WRITE 4X REGISTER NO
23 READ/WRITE 4X REGISTERS NO
24 READ FIFO QUEUE NO
Response:
Slave Function Byte Count Data Byte Data Byte Data Byte CRC CRC
Address Code = <nbytes> #1 #i #nbytes
(L) (H)
= 01
The coil or status in the response message is packed as one coil per bit of the data field.
Digital inputs can be single (coded on one bit) or double (in this case 1 or 2 bits defined in
configuration).
For Single DI or Double DI coded on one bit, status is indicated as: 1 = ON, 0 = OFF.
For double DI coded on two bits, status indicates: [open contact, closed contact] = [0,1] for
open, [1,0] for closed, [0,0] for jammed], [0,1] for the other states
The less significant bit of the first data byte contains the coil addressed in the query. The
other coils follow toward the high order end of this byte, and from 'low order to high order' in
subsequent bytes, as described in the frame example.
Important notes:
1. If the returned coil quantity is not a multiple of eight, the remaining bits in the final byte
will be padded with zeros (toward the high order end of the byte). The Byte Count
Field specifies the quantity of complete bytes of data.
For easiest understanding between the gateway and the SCADA, it is recommended
to read a number of points which is a multiple of 8.
2. If the starting address is not a point in configuration, the message will be not be
accepted, and an error exception 2 will be returned.
3. If the starting address is in configuration and if there is some “holes” (addresses not in
configuration) theses holes will be padded with 0 (i.e value OFF).
3.7.6 Function 03 / 04: Read Holding Registers / Input Registers
The request function 03 or 04 reads the values of analogue inputs, tap position and counters
values in the slave.
In case of tap position and counters values, only natural coding is supported.
These two functions are the only way to read registers points with the MODBUS protocol.
Flags (validity, topical, ..) are not supported in the MODBUS protocol base.
This is equal using the Read Holding Registers request or the Read Input Registers request.
Broadcast is not supported.
Addresses in frames may start from 0…65535.
Query:
Slave Function Byte Data Data Data Data Data Data CRC CRC
address code Count
(H) (L) (H) (L) (H) (L) (L) (H)
=
= 03 #1 #1 #i #i #nbytes/ 2 #nbytes/
<nbytes>
2
The register data in the response message are packed as two bytes per register, with the
binary contents right justified within each byte. For each register, the first byte contains the
high order bits and the second contains the low order bits.
C264/EN CT/C30 Communications
Important notes:
1. If the starting address is not a point in configuration, the message will be not be
accepted, and an error exception 2 will be returned.
2. If the starting address is in configuration and if there is some “holes” (addresses not in
configuration) theses holes will be padded with the value 0
3.7.6.1 Signed normalised coding
The signed normalised coding is used to encode the 16 bits-registers. Analogue maximal
value will be coded 7FFFh (decimal value + 32767), and minimal value will be coded 8000h
(decimal value –32768).
For this mode, the gateway may now code the value on 8 to 16 bits [ low part of the register
will be used ]. But, 16 bits is normally the standard to use the full scale conversion.
Example:
in configuration the maximal value for an analogue point is +3000 and minimum value for
this analogue is 0.
That means that when the analogue is received with value 0 from the system, the gateway
will send to the SCADA the register with 8000h value. If this analogue is equal to the
maximal value +3000, the value sent to the SCADA is 7FFFh. Calculation is linear for the
coding between the min and max values.
3.7.6.2 Unsigned normalised coding
The unsigned normalised coding is used to encode the 16 bits-registers. Analogue maximal
value will be coded FFFFh (decimal value + 65535), and minimal value will be coded 0000h
(decimal value 0).
For this mode, the gateway may now code the value on 8 to 16 bits [ low part of the register
will be used ]. But, 16 bits is normally the standard to use the full scale conversion.
Example:
in configuration the maximal value for an analogue point is +3000 and minimum value for
this analogue is 0.
That means that when the analogue is received with value 0 from the system, the gateway
will send to the SCADA the register with 0h value. If this analogue is equal to the maximal
value +3000, the value sent to the SCADA is FFFFh. Calculation is linear for the coding
between the min and max values.
3.7.6.3 Natural coding
The natural coding is used to encode data without any calculation. That’s means that integer
value will be send.
Example:
if the gateway receives the value 10.xxxx, the value 0Ah will be set in the appropriate
register. The gateway receives the value –10,xxxx the value FFF6h will be coded. Sent
values are considered as signed values which are included between –32768 and +32767.
When minimum and maximum values are reached values FFF6h and FFFFh are
respectively sent.
Communications C264/EN CT/C30
Slave Function Code Sub Function Sub Function Data Data CRC CRC
Address code code
= 08 (H) (L) (L) (H)
(H) (L)
The query message specifies the data that will be echoed.
Response:
Slave Function Code Sub Function Sub Function Echoed Echoed CRC CRC
Address code code
= 08 Data Data (L) (H)
(H) (L)
(H) (L)
The normal response is an echo of the query with the same data send in the request.
NOTE: If the sub-function is different from 0, an exception error “illegal function” is
returned.
3.7.10 Function 15: Force Multiple Coils
Normally, this request function 15 is used to realise a control on several contiguous
addresses.
This function can be used, but only one control can be send at the same time.
NOTE: Only a count number equal to 1 is allowed, otherwise an exception error 3 will be
replied.
3.7.11 Function 16: Preset multiple registers
Normally, this request function 16 is used to preset on several contiguous addresses.
This function can be used, but only one preset can be send at the same time.
NOTE: Only a count number equal to 1 is allowed, otherwise an exception error 3 will be
replied.
Communications C264/EN CT/C30
4. IED COMMUNICATION
4.1 Overview
Different types of IEDs are connected to a MiCOM C264 through networks using various
legacy protocols:
1. IEC 60870-5-103 (T103)
2. Modbus
3. DNP3
4. IEC 60870-5-101 (T101)
All these networks use a serial link to communicate with IEDs. As there are several serial
links on a MiCOM C264, it is possible to have:
• Request / reply
Master emits a request to a slave of its choice and wait for the response. Between
master and slave, only one transaction can be initiated. Then, in order to transmit the
same request to two different slaves, two transactions are required.
• Broadcast
Master transmits a command to all of slaves connected to the network. They perform it
without send any response.
Common features to all IEDs and all protocols are specified below in the paragraph 0
Specific features to each protocol are specified in subsequent paragraphs.
4.2 IED Common functionality
4.2.1 Interface to IEDs
4.2.1.1 Input
Data Note
Digital input Treated
Measurement Treated
Default position Depending on the protocol
Counter Treated
Tap position Treated
Control acknowledgement Treated
Setpoint acknowledgement Treated
Alarm Not Treated
Disturbance record Depending on the protocol
Tunnelling Frame response Depending on the protocol
C264/EN CT/C30 Communications
4.2.1.2 Output
Data Note
Control Treated
Setpoint Depending on the protocol
Alarm acknowledgement Not Treated
Tunnelling Frame question Depending on the protocol
Time synchronisation Treated
4.2.2 Behaviour
4.2.2.1 Network supervision
The number of networks and IEDs is known by configuration.
Each network is managed independently of the other networks.
The management of a network consists of:
• Repetitions [if an IED doesn’t answer to a request, this request will be repeated the
next cycle]
• When an IED is disconnected, it may be questioned only time to time [not all cycles]
• When an IED has important data to transmit [DI], it may be questioned successively
several times
• Time synchronisation
Synchronisation is done periodically by sending a broadcast frame. After the
synchronisation frame has been sent, the polling starts again.
NOT_
INITIALISED
1
DISCON-
2
NECTED
2
1
CONNECTED
NOT_SYNCHRONISED
12
3 4
IN_SERVICE
5 OUT_OF_
GI
SERVICE
6 7
NORMAL
10 8
11 9 DISTUR-
TUNNELING BANCE
C0109ENa
• NOT_INITIALISED: That’s the initial state of an IED. The MiCOM C264 polls the IED
every cycle in order to connect it.
If the IED responds, it becomes CONNECTED 2 .
If after some attempts the IED doesn’t respond, it becomes DISCONNECTED 1 .
• DISCONNECTED: The IED is disconnected. The MiCOM C264 polls the IED time to
time in order to connect it.
If the IED responds, it becomes CONNECTED 2 .
C264/EN CT/C30 Communications
• CONNECTED: The IED is connected. This state includes several states. When an IED
becomes Connected, it goes to the NOT_SYNCHRONISED state.
• OUT_OF_SERVICE: The IED is connected and says it is Out of service. The MiCOM
C264 polls the IED time to time waiting for the IED to become IN_SERVICE 5 .
• IN_SERVICE: The IED is connected and it says it is In Service. This state includes
several states. When an IED becomes In Service, it goes to the GI state.
• NORMAL: The IED is In Service and the monitoring of DI, AO and DO are performed.
If a disturbance record becomes present and the MiCOM C264 have enough places to
store the file, the IED goes in the DISTURBANCE state 8 .
If a request to open a tunnel for the IED arrives, it is accepted and the IED goes in the
TUNNELING state 10 .
Time to Time, a GI may be done. In this case the IED goes in the GI state 7 .
• 5: see 3
• 8: A disturbance file is available in the IED and there are enough places to store it in
the MiCOM C264.
A disturbance uploading is activated.
Communications C264/EN CT/C30
• at initialisation time
• upon reconnection
• Cyclically [optional]
Messages received during the initial general interrogation are not sent to the processing
function. Instead the content of the table is sent at the end of the sequence.
Messages received during a general interrogation performed after the initialisation sequence
are sent immediately to the processing function
Some IEDs send a message indicating the end of the response to a general interrogation.
When this message is received, the sequence is considered as finished. If the IED does not
send this message, the MiCOM C264 must check that all data are received.
If all data are not received within a given time another request is sent. This process can be
repeated N times. If the response is still not received after N times a fault message is sent,
however the IED is still polled.
Disturbance File Management
The following rules apply for the management of the Disturbance Files of the IED:
• For each IED, there is an information in the configuration indicating if automatic upload
of Disturbance File has to be done. This indication may be overwritten by a command
from the application.
• When the MiCOM C264 detects that an IED has a Disturbance File ready to be
uploaded and that automatic upload is enabled, it uploads and stores it. When the
upload is finished, an indication is sent to the Upper transmission management to
inform it that a Disturbance file is ready.
• When there isn’t enough places to store a Disturbance File, the oldest file is deleted.
• The upper transmission management can only get Disturbance files stored in the
MiCOM C264. Once the upper transmission management has treated a file it is
deleted.
C264/EN CT/C30 Communications
If the command is a double command, the application send one order, and depending on the
protocol, two cases have to be distinguished:
• The Double command is referenced only once in the IED Mapping. In this case, if an
OPEN (respectively CLOSE) command is received from the application, the master
send an OFF (respectively ON) order to the IED at the corresponding address.
• The double command is referenced by two addresses in the IED Mapping: one refers
to the Open Contact and the other to the Close Contact. In this case, if an OPEN
(respectively CLOSE) command is received from the application, the master sends an
ON order to the IED, at the address corresponding to the Open Contact (respectively
Close Contact).
4.2.4.2 Setpoints
SP controls are priority message. The polling sequence must be interrupted in order to send
the SP control as soon as possible.
Not all IEDs send SP control acknowledgement. If they do not, an acknowledgement is
simulated and sent to the handling of SP control sequences function.
When an IED is disconnected [or out of service] a negative acknowledgement is sent.
If the SP commands are always "direct execute" command (no “select before operate”).
For an IED, only one SP command is possible at a time.
4.2.5 Tunnelling
The serial tunnelling enable to connect a lap top computer – which run an IED setting
software – to a serial (RS232) line of the PACiS computer in order to communicate with an
IED connected to a legacy bus of the PACiS computer.
C264
Lap Top IED
Computer
All serial RS232 lines of the computer – including the port onto the front panel – can be used
for serial tunnelling.
The choice of the serial line to be used for serial tunnelling is done by the computer
configuration.
The cable dedicated to tunnelling must be disconnected from the front panel when
tunnelling is not used.
4.2.5.1 Interface through the tunnelling serial line
The tunnelling serial line gives access to a user dialog.
This dialog enables an user to give commands to the Tunnelling RS232 software.
Commands are ASCII string terminated by ‘↵’ (code ASCII 13H) and are case sensitive.
A command is executed at the reception of the ‘↵’ character. An ASCII message is sent in
response, and a prompt message may be sent in order to indicate the computer is ready to
treat a new command.
If a command is unknown, an error message “Unknown command !” is sent.
C264/EN CT/C30 Communications
• TunRSIed nl↵: List the IED of a legacy line and their state [ln = line number].
The first line of the response gives information on the line:
Line <line Number>: <Protocol>
Each following line of the response corresponds to an IED and have the following format:
IED <Address>: <State>
Where <State> can be “available” or “not available”
If the line isn’t available for Tunnelling, the response is “The line nl is not available for serial
tunnelling.”
• TunRSStart ln, ad↵: Start a serial tunnelling session with the specified legacy line
[ln = legacy line number; ad = IED address].
The response is either “Serial Tunnelling started” or an error message explaining why the
command can’t be executed.
If the response is “Serial Tunnelling started”, legacy frames are awaited on the serial
Tunnelling link.
• Execute settings actions with the setting Software (that implies exchange of legacy
frames between the setting software and the IED through the computer)
• If the questioned IED does not answer, no frame of answer is returned to the setting
Software.
• If the setting software sends a new question frame [or repeats the last frame] whereas
the computer is still awaiting the answer from the IED, this new frame is ignored.
4.2.5.6 Serial tunnelling through a modem
C264
Modem IED
Computer
Specialised
or RTC line RS232 link
Legacy bus
dedicated to serial
(Modbus,
tunneling
T103)
C0150ENa
If modems are well configured, this operating mode is transparent for the computer and no
specific management is needed in the software.
4.2.5.7 Tunnelling limits and Performances
The legacy protocols supported [protocols for which serial tunnelling is available] are the
following:
• MODBUS
• T103
The line to be used for serial tunnelling can be set through computer configuration.
If The serial tunnelling line is “frontal RS232”, it’s automatically configured:
19200Bd, 8 bits data, no parity, 1 stop bit.
For the other ports (COM1 to COM4), it follows the configuration parameters.
Only RS232 mode is supported.
C264/EN CT/C30 Communications
• The number of serial links available limits the number of legacy network that can be
managed simultaneously by a MiCOM C264.
• The maximum number of IED that can be managed for a network is 16.
• Performance depends on the protocol used and on the number of IEDs connected to
each Network.
4.3 MODBUS communication
4.3.1 Finality
MODBUS is a legacy bus master/slave protocol that is used by many devices such as
relays, MiCOM C264s or monitoring devices. The aim of this chapter is not to describe the
protocol itself and its mechanisms (other documents and norms are there for that) but to give
the specificity of the functions that will be implemented in the MiCOM C264. These are the
MODBUS function numbers that will be used, the way in which each type of data will be
internally or externally updated, the general mechanisms used for the time synchronisation
and the configuration needs.
As the MiCOM C264 is the master on the legacy bus - regards to protections and IEDs - this
protocol is referenced as “Master Modbus” in the MiCOM C264.
4.3.2 Interface to IEDs
The following MODBUS functions are implemented in the MiCOM C264:
Function
Sub-code Used for Commentary
number
1–2 / Read DIs Read N bits
3–4 / Read DIs / MEAS / Read N words
Disturbance files
5 / Write CO Write 1 bit
15 / Write CO Write N bits
This function could be used with the
following restriction: you can only write
COs one after the other.
7 / Polling Read status byte
This function is used for detecting a DI
change of state, the presence of
disturbance files (Areva IEDs)
8 0 Polling Echo
This function could be used for
detecting if a device is connected or
not.
6 / Eventually for Write 1 word
tunnelling
16 / Eventually for Write N words
tunnelling
Communications C264/EN CT/C30
4.3.3 Behaviour
4.3.3.1 Polling
During a polling procedure, each slave is polled one after the other. This means that the
master waits for the answer to a request sent to a device before sending a new request to
the same or an other device.
There will be 2 types of polling:
• the polling performed by the application for the measurements and the digital inputs
NOTE: BI, Measurement and Counter are polled with the variation 0. That means
that all variations are required.
All other DNP3 objects are not treated.
4.4.2.2 Output
The DNP3 Master manages both direct control Command and Select before Operate for
digital control only.
When operate command is received from application, the Master checks in database to
know if the command is:
1. An execute command, which belongs to a SBO Control: OPERATE function is used in
this case.
2. A direct control: DIRECT OPERATE function is used is this case
C264/EN CT/C30 Communications
4.4.3 Behaviour
• Synchronisation:
− The DNP3 object used to synchronise IEDs is “Write Date and Time Request
(Object 50, Variation 01).
• Initialisation:
− When the response is OK, the Master DNP3 send a message to the application to
tell that connection step is passed.
• General Interrogation:
− When the IED is connected, the MiCOM C264 ask for static data state and value with
a sequence of:
− Read BI,
− Read Measurement,
− Read TPI,
− Read Counter
• Polling:
− The polling cycle must be interrupted at minimum in the two following case:
− Clock Synchronisation
− Remote control
• Event acquisition:
− Event occurs spontaneously. The slave device waits for being polled by the master.
• IED monitoring:
• Digital inputs:
− Digital inputs which are received as changes of state are identified by the DNP3
object number 02
− Digital inputs which are received as static data are identified by the DNP3 object
number 01
• Measurements:
− Measurements which are received as changes of state are identified by the DNP3
object number 32
− Measurements which are received as static data are identified by the DNP3 object
number 30
• Counters:
− Counters which are received as changes of state are identified by the DNP3
object number 22
− Counters which are received as static data are identified by the DNP3 object
number 20
4.4.5 Data sent to IEDs
• Controls:
− In case of basic control (Set, Reset, Trip, Close), DNP3 object 12 is used with the
Variation 01
C264/EN CT/C30 Communications
Others
______________________________________________________________________________
Attach explanation if 'Variable' or 'Configurable' was checked for any timeout
Sends/Executes Control Operations:
WRITE Binary Outputs Never Always Sometimes Configurable
SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE - NO ACK Never Always Sometimes Configurable
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change
Events
Specific variation requested: when no specific variation requested:
Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable to send both, one or the Configurable (attach explanation)
other (explanation below)
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes
(dec) (hex)
(dec) (hex)
1 0 Binary Input – All Variations 1, 22 00,01,06
1 1 Binary Input 1 00,01,06 129,130 00,01
1 2 Binary Input with Status 1 00,01,06 129,130 00,01
2 0 Binary Input Change - All Variations 1 06,07,08
2 1 Binary Input Change without Time 1 06,07,08 129,130 17,28
2 2 Binary Input Change with Time 1 06,07,08 129,130 17,28
2 3 Binary Input Change with Relative Time 1 06,07,08 129,130 17,28
10 0 Binary Output - All Variations 1 00,01,06
10 1 Binary Output
10 2 Binary Output Status 1 00,01,06 129,130 00,01
12 0 Control Block - All Variations (1)
12 1 Control Relay Output Block (1) 3,4,5,6 17,28 129 Request
echo
12 2 Pattern Control Block 5,6 17,28 129 Request
echo
12 3 Pattern Mask 5,6 00,01 129 Request
echo
20 0 Binary Counter - All Variations 1,7,8,9,10, 00,01,06
22
20 1 32-Bit Binary Counter 1 00,01,06 129,130 00,01
20 2 16-Bit Binary Counter 1 00,01,06 129,130 00,01
20 3 32-Bit Delta Counter 1 00,01,06 129,130 00,01
20 4 16-Bit Delta Counter 1 00,01,06 129,130 00,01
20 5 32-Bit Binary Counter without Flag 1 00,01,06 129,130 00,01
20 6 16-Bit Binary Counter without Flag 1 00,01,06 129,130 00,01
20 7 32-Bit Delta Counter without Flag 1 00,01,06 129,130 00,01
20 8 16-Bit Delta Counter without Flag 1 00,01,06 129,130 00,01
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes
(dec) (hex)
(dec) (hex)
21 0 Frozen Counter - All Variations 1 00,01,06
21 1 32-Bit Frozen Counter 1 00,01,06 129,130 00,01
21 2 16-Bit Frozen Counter 1 00,01,06 129,130 00,01
21 3 32-Bit Frozen Delta Counter 1 00,01,06 129,130 00,01
21 4 16-Bit Frozen Delta Counter 1 00,01,06 129,130 00,01
21 5 32-Bit Frozen Counter with Time of 1 00,01,06 129,130 00,01
Freeze
21 6 16-Bit Frozen Counter with Time of 1 00,01,06 129,130 00,01
Freeze
21 7 32-Bit Frozen Delta Counter with Time of
Freeze
21 8 16-Bit Frozen Delta Counter with Time of
Freeze
21 9 32-Bit Frozen Counter without Flag 1 00,01,06 129,130 00,01
21 10 16-Bit Frozen Counter without Flag 1 00,01,06 129,130 00,01
21 11 32-Bit Frozen Delta Counter without Flag
21 12 16-Bit Frozen Delta Counter without Flag
22 0 Counter Change Event - All Variations 1 06,07,08
22 1 32-Bit Counter Change Event without 1 06,07,08 129,130 17,18
Time
22 2 16-Bit Counter Change Event without 1 06,07,08 129,130 17,18
Time
22 3 32-Bit Delta Counter Change Event 1 06,07,08 129,130 17,18
without Time
22 4 16-Bit Delta Counter Change Event 1 06,07,08 129,130 17,18
without Time
22 5 32-Bit Counter Change Event with Time 1 06,07,08 129,130 17,18
22 6 16-Bit Counter Change Event with Time 1 06,07,08 129,130 17,18
22 7 32-Bit Delta Counter Change Event with
Time
22 8 16-Bit Delta Counter Change Event with
Time
Remarks:
Frozen counters (type21) are uploaded during general interrogation, but never polled after this.
Communications C264/EN CT/C30
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes
(dec) (hex)
(dec) (hex)
23 0 Frozen Counter Event - All Variations 1 06,07,08
23 1 32-Bit Frozen Counter Event without 1 06,07,08 129,130 17,18
Time
23 2 16-Bit Frozen Counter Event without 1 06,07,08 129,130 17,18
Time
23 3 32-Bit Frozen Delta Counter Event 1 06,07,08 129,130 17,18
without Time
23 4 16-Bit Frozen Delta Counter Event 1 06,07,08 129,130 17,18
without Time
23 5 32-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17,18
23 6 16-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17,18
23 7 32-Bit Frozen Delta Counter Event with
Time
23 8 16-Bit Frozen Delta Counter Event with
Time
30 0 Analogue Input - All Variations 1 00,01,06
30 1 32-Bit Analogue Input 1 00,01,06 129,130 00,01
30 2 16-Bit Analogue Input 1 00,01,06 129,130 00,01
30 3 32-Bit Analogue Input without Flag 1 00,01,06 129,130 00,01
30 4 16-Bit Analogue Input without Flag 1 00,01,06 129,130 00,01
31 0 Frozen Analogue Input - All Variations
31 1 32-Bit Frozen Analogue Input
31 2 16-Bit Frozen Analogue Input
31 3 32-Bit Frozen Analogue Input with Time
of Freeze
31 4 16-Bit Frozen Analogue Input with Time
of Freeze
31 5 32-Bit Frozen Analogue Input without
Flag
31 6 16-Bit Frozen Analogue Input without
Flag
32 0 Analogue Change Event - All Variations 1 06,07,08
32 1 32-Bit Analogue Change Event without 1 06,07,08 129,130 17,18
Time
32 2 16-Bit Analogue Change Event without 1 06,07,08 129,130 17,18
Time
32 3 32-Bit Analogue Change Event with 1 06,07,08 129,130 17,18
Time
32 4 16-Bit Analogue Change Event with 1 06,07,08 129,130 17,18
Time
33 0 0 Frozen Analogue Event - All Variations
33 1 32-Bit Frozen Analogue Event without
Time
33 2 16-Bit Frozen Analogue Event without
Time
33 3 32-Bit Frozen Analogue Event with Time
33 4 16-Bit Frozen Analogue Event with Time
40 0 Analogue Output Status - All Variations 1 00,01,06
40 1 32-Bit Analogue Output Status 1 00,01,06 129,130 00,01
40 2 16-Bit Analogue Output Status 1 00,01,06 129,130 00,01
C264/EN CT/C30 Communications
REQUEST RESPONSE
OBJECT
(slave must parse) (master must parse)
Func Qual
Func Codes Qual Codes
Obj Var Description Codes Codes
(dec) (hex)
(dec) (hex)
41 0 Analogue Output Block - All Variations 3,4,5,6 17,28 129 Request
echo
41 1 32-Bit Analogue Output Block 5,6 17,28 129 Request
echo
41 2 16-Bit Analogue Output Block 5,6 17,28 129 Request
echo
50 0 Time and Date - All Variations
50 1 Time and Date 2 07 (quantity=1)
50 2 Time and Date with Interval
51 0 Time and Date CTO - All Variations
51 1 Time and Date CTO 129,130 07
(quantity=1)
51 2 Unsynchronized Time and Date CTO 129,130 07
(quantity=1)
52 0 Time Delay - All Variations
52 1 Time Delay Coarse 129,130 07
(quantity=1)
52 2 Time Delay Fine 129,130 07
(quantity=1)
60 0
60 1 Class 0 Data 1 06,07,08
60 2 Class 1 Data 1 06,07,08
20,21,22 06
60 3 Class 2 Data 1 06,07,08
20,21,22 06
60 4 Class 3 Data 1 06,07,08
20,21,22 06
70 1 File Identifier
80 1 Internal Indications 2 00 (index=7 ou
index=4)
1 00,01
81 1 Storage Object
82 1 Device Profile
83 1 Private Registration Object
83 2 Private Registration Object Descriptor
90 1 Application Identifier
100 1 Short Floating Point
100 2 Long Floating Point
100 3 Extended Floating Point
101 1 Small Packed Binary-Coded Decimal
101 2 Medium Packed Binary-Coded Decimal
101 3 Large Packed Binary-Coded Decimal
No Object (Cold Restart)
4.5.2.2 Output
4.5.3 Behaviour
4.5.3.1 Synchronisation
The “Master T103” link is always synchronised by the MiCOM C264. No calculation of the
transmission delay is performed.
4.5.3.2 Polling
To connect an IED, a “Reset CU” frame is sent to the IED.
By default an IED is polled by a “Polling C2” frame, allowing to get “non priority information”.
If an IED signals it has “priority information”, it is polled with a “Polling C1” frame.
4.5.3.3 IED monitoring
The “OUT_OF_SERVICE” state is managed. It corresponds to the “Lock of communication”
[DI 20].
A GI may be done after each end of Tunnelling session.
The MiCOM C264 may regularly look for Disturbance file presence
4.5.3.4 Tunnelling mode
During tunnelling mode, only polling C2 may be done by the MiCOM C264 [Normally, if
“priority information” is present, the remote Master may send a “polling C1 frame”].
The MiCOM C264 must spy the tunnelling exchange in order not to loose information [DI and
AI change]
For security raison, at the end of a tunnelling session, a GI is done
4.5.3.5 Station Interlocking
This functionality is only available on MiCOM P139 in private T103 range (Alstom D protocol
variant)
After GI, and only if IED is MiCOM Px3x, we send a read on MiCOM Px3x parameter adress
0 which corresponds to Device Type. If MiCOM Px3x responds with analog parameter set to
139, we activate Station Interlocking Management.
Case of local control (front panel of the MiCOM P139) with Station interlock:
As soon as a user will try to control a switchgear by the front panel, the MiCOM P139 will
send an ASDU 72 with FUN/TYP = F8h/74h in order to request to PACiS system the station
interlock conditions. PACiS system should check if the command is allowed (specific
treatment done by CONDUITE of the computer) and respond to the MiCOM P139.
Communications C264/EN CT/C30
− DI which are not transmitted during a GI. For these DI, the IED signals only
change of state from OFF to ON. The MiCOM C264 must generate by itself the
change from ON to OFF.
4.5.4.2 Measurements
A Measurement is identified by:
Description TI VSQ COT ADR FUN INF DB0-DB4 DB5-DB9 DB10-DB14 DB15-DB19
Energy 4FH 04H 01H CAD F8H 6CH Active + Active - Reactive + Reactive -
counter
TI = Type identification
VSQ = variable structure qualifier
COT = cause of transmission
ADR = CAD = common address
FUN = function number
INF= information number
DB0-DB4 = active energy output
DB5-DB9 = active energy input
DB10-DB14 = reactive energy output
DB15-DB19 = reactive energy input
Format of the energy counter value
Value
Value
Value
S Value
IV CA CY Sequence number
• A DI with the same (Function Type, Information Number) as the control and with a
‘Cause Of Transmission’ equals to ‘positive return’ or ‘negative return’ in public range
• A DI (ASDU 1) with the same (Function Type, Information Number) as the control and
with a ‘Cause Of Transmission’ equals to ‘positive return’ or ‘negative return’ in public
range.
The possible selection (blank, X, R or B) is specified for each specific clause or parameter.
NOTE: In addition, the full specification of a system may require individual
selection of certain parameters for certain parts of the system, such as
the individual selection of scaling factors for individually addressable
measured values.
4.6.2.1 System or device
(system specific parameter, indicates the definition of a system or a device by marking one
of the following with ‘X’)
System definition
Unbalanced interchange
CIRCUIT V24/V28 Balanced interchange
Recommended if Circuit X24/X27
Standard
> 1200 bits/s
Unbalanced interchange
CIRCUIT V24/V28 Balanced interchange
Recommended if Circuit X24/X27
Standard
> 1200 bits/s
⌧ Two octets
⌧ Structured
⌧ Unstructured
⌧ Three octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked ‘X’)
⌧ <14> := Measured value, short floating point value with time tag M_ME_TC_1
<18> := Packed start events of protection equipment with time tag M_EP_TB_1
<19> := Packed output circuit transmission of protection equipment with time tag M_EP_TC_1
⌧ <36> := Measured value, short floating point number with time tag CP56Time2a M_ME_TF_1
<39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
<40> := Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1
File transfer
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ <122> := Call directory, select file, call file, call section F_SC_NA_1
Special use
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
None
Communications C264/EN CT/C30
<3> M_DP_NA_1 X X X X X
<4> M_DP_TA_1 X X X
<5> M_ST_NA_1 X X X X X
<6> M_ST_TA_1 X X X
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1 X
<11> M_ME_NB_1 X X X X
<12> M_ME_TB_1 X
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1 X
<15> M_IT_NA_1 X X
<16> M_IT_TA_1 X
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X X
<30> M_SP_TB_1 X X
<31> M_DP_TB_1 X X
<32> M_ST_TB_1 X X
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X X X X X
<46> C_DC_NA_1 X X X X X X X X X
C264/EN CT/C30 Communications
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1 X
<121> F_SR_NA_1 X
<122> F_SC_NA_1 X
<123> F_LS_NA_1 X
<124> F_AF_NA_1 X
<125> F_SG_NA_1 X
<126> F_DR_TA_1 X X
Remote initialisation
Read procedure
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Spontaneous transmission
Communications C264/EN CT/C30
General interrogation
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Global
Group 6 Group 12
⌧ Global
Group 4
Clock synchronisation
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Clock synchronisation
Notes:
The controlled station reports the change of hour by sending a clock synchronisation message (ASDU 103) to the
controlling station.
Command transmission
(object -specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ C_SE_ACTTERM used
⌧ No additional definition
Persistent output
Parameter loading
(object-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
Threshold value
Smoothing factor
Parameter activation
(object-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
Test procedure
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Test procedure
File transfer
(station-specific parameter), mark ‘X’ if function is used)
File transfert in monitor direction
⌧ Transparent file
Transparent file
Background scan
(station-specific parameter, mark each type ID ‘X’ if it is only used in the standard direction,
‘R’ if only used in the reverse direction, and ‘B’ is used in both directions)
⌧ Background scan
Test procedure
A test command may be issued by the controlling station to ensure the availability of the
communications link and the commands subsystem.
Test commands are received at the controlled station on the active link. The controlled
station mirrors the test command, on the link from which it was received, with a cause of
transmission indicating activation confirmation.
An error response should be sent if the command is incorrect, with a cause of transmission
indicating negative activation confirmation.
In the case of balanced mode, the controlled station may also send a test command to the
controlling station, to ensure the availability of the communications link as there is no polling
made by the controlling station.
C264/EN CT/C30 Communications
BLANK PAGE