Warning codes : A911 Vdc_max controller active
-------------------------------------------------------------------------------------
The Vdc_max controller works to keep the DC-link voltage (r0026) below the
level specified in r1242.
---------------------------------------------------------------------------------------------------
Check the following:
• Supply voltage must lie within limits indicated on rating plate.
• Ramp-down time (P1121) must match inertia of load.
---------------------------------------------------------------------------------------------------
Note:
Higher inertia requires longer ramp times; otherwise, apply braking resistor.
------------------------------------------------------
P0003 User access level 0 – 4 fact def ; 1
Defines user access level to parameter sets.
0 User defined parameter list - see P0013 for details on use
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access, for example, to inverter I/O functions
3 Expert: For expert use only
4 Service: Only for use by authorized service, password protected
---------------------------------------------------------------------------------------------------
r0026[0] CO: Actual filtered Dclink voltage [V]
Displays filtered DC-link voltage. This value is available filtered (r0026) and
unfiltered (r0070).
MMTS
---------------------------------------------------------------------------------------------------
r1242 CO: Switch-on level of Vdc_max [V]
Displays switch-on level of Vdc_max controller.
Following equation is only valid, if P1254 = 0:
r1242 = 1.15 * sqrt(2) * V_mains = 1.15 * sqrt(2) * P0210
otherwise r1242 is internally calculated.
-----------------
P1254 Auto detect Vdc switch on levels 0–1 fact def ; 1
Enables / disables auto-detection of switch-on levels for Vdc_max controller. For
best results, it is recommended to set P1254 = 1 (auto-detection of Vdc switch-on
levels enabled).
Setting P1254 = 0 is only recommended when there is a high degree of fluctuation
of the DC-link when the motor is being driven. Note that the auto detection only
works when the inverter has been in standby for over 20s.
0 Disabled
1 Enabled
-----------------
P0210 Supply voltage [V] 0 – 1000 fact def ; 400
P0210 defines the supply voltage. Its default value depends upon the type of
inverter. If P0210 does not correspond to the supply voltage, then it must be
modified.
Dependency:
Optimizes Vdc controller, which extends the ramp-down time if regenerative
energy from motor would otherwise cause DC-link overvoltage trips.
Reducing the value enables controller to cut in earlier and reduce the risk of
overvoltage.
MMTS
Set P1254 ("Auto detect Vdc switch-on levels") = 0. Cut-in levels for Vdc
controller and compound braking
are then derived directly from P0210 (supply voltage):
• Vdc_min switch-on level (r1246) = P1245 * sqrt(2) * P0210
• Vdc_max switch-on level (r1242) = 1.15 * sqrt(2) * P0210
• Dynamic braking switch-on level = 1.13 * sqrt(2) * P0210
• Compound braking switch-on level = 1.13 * sqrt(2) * P0210
Set P1254 ("Auto detect Vdc switch-on levels") = 1. Cut-in levels for Vdc
controller and compound braking
are then derived from r0070 (DC-link voltage):
• Vdc_min switch-on level (r1246) = P1245 * r0070
• Vdc_max switch-on level (r1242) = 1.15 * r0070
• Dynamic braking switch-on level = 0.98 * r1242
• Compound braking switch-on level = 0.98 * r1242
Auto-detection calculations are only performed when the inverter has been in
standby for over 20s. When pulses are enabled, the calculated values are frozen
until 20s after pulses cease.
Note:
For best results, it is recommended that auto-detection of Vdc switch-on levels
(P1254 = 1) is used.
Setting P1254 = 0 is only recommended when there is a high degree of fluctuation
of the DC-link when the motor is being driven. In this case, ensure the setting of
P0210 is correct.
If mains voltage is higher than value entered, automatic deactivation of the Vdc
controller may occur to avoid acceleration of the motor. A warning will be issued
MMTS
in this case (A910). Default value is depending on inverter type and its rating
data.
---------------------------------------------------------------------------------------------------
P1121[0...2] Ramp-down time [s]
This parameter sets the time taken for motor to decelerate from maximum motor
frequency (P1082) down to standstill when no rounding is used.
Range: 0.00 ... 650.00 (factory default: 10.00)
-------------------------------------------------
MMTS
Setting the Vdc controller
Functionality ;
If ramp-down time is too short, the inverter may display the alarm A911 which
means the DC link voltage is too high. The Vdc controller dynamically controls
the DC link voltage to prevent overvoltage trips on high inertia systems.
MMTS
r0056.0...15 CO / BO: Status of motor control.
Displays status of motor control (in bit format), which can be used to diagnose
inverter status.
Bit 14 Vdc_max controller active Signal 1; Yes Signal 0; No
---------------------------------------------------------------------------------------------------
Setting parameters ;
P1240[0...2] Configuration of Vdc controller
This parameter enables / disables Vdc controller.
= 0: Vdc controller disabled
= 1: Vdc_max controller enabled (factory default)
= 2: Kinetic buffering (Vdc_min controller) enabled
= 3: Vdc_max controller and kinetic buffering (KIB) enabled
Note: This parameter must be set to 0 (Vdc controller disabled) if a braking
resistor is used.
---------------------------------------------------------------------------------------------------
P0210 Supply voltage [V]
This parameter defines the supply voltage. Its default value depends upon the type
of inverter. Range: 0 ... 1000
------------------------------------------------------
Kesimpulan ;
- r1242 menampilkan batas maksimum tegangan DC.
- P0210 setelan masukan tegangan pada inverter.
- Ramp down time P1121 ( jeda dari freq awal ke freq baru ) di naikkan , untuk
mengurangi tegangan balik pada inverter.
MMTS
Saat setelan freq pada inverter sudah turun, tapi putaran motor masih tinggi, motor
akan menjadi generator, dan terjadi tegangan balik ke inverter.
- Naikkan setelan P0210 Supply voltage [V], untuk menaikkan VDC Max switch
level.
• Vdc_min switch-on level (r1246) = P1245 * sqrt(2) * P0210
• Vdc_max switch-on level (r1242) = 1.15 * sqrt(2) * P0210
• Dynamic braking switch-on level = 1.13 * sqrt(2) * P0210
• Compound braking switch-on level = 1.13 * sqrt(2) * P0210
Atau rumus pada halaman 82 ;
R1242 = 1.15 * akar 2 * V mains = 1.15 * akar 2 * P0210
- Tambah BREAKING RESISTOR eksternal untuk mengurangi tegangan balik
pada inverter.
- Ganti inverter dengan Daya yang lebih tinggi kemudian setel parameter sesuai
name plate motor / Daya inverter lebih tinggi dari motor.
MMTS