TID JIG-Microbial-Monitoring-Strategies-Oct-2015
TID JIG-Microbial-Monitoring-Strategies-Oct-2015
Introduction
The Joint Inspection Group (JIG) Standards only mandate the use of semi-annual microbial monitoring for vehicles
routinely used for the defueling of aviation fuel. However, microbial monitoring may also be used as an alternative to
quarterly visual inspections to assess the microbiological cleanliness of product recovery tanks and as a means to
evaluate possible extension to the main storage tank cleaning frequency.
This document seeks to provide guidance on appropriate monitoring strategies for use throughout the aviation fuel
supply chain up to the point of delivery to aircraft. It is intended to provide guidance and facilitate operations staff
wanting to employ microbial testing as part of their management and control strategy for both fuel product quality
assurance and facility maintenance. Where microbial contamination has been confirmed by testing, more detailed
monitoring can help identify potential upstream or local sources and provide remediation strategies.
Although IATA recommends maximum allowable levels of microbial contamination in aircraft fuel tanks, there are no
industry specified microbiological contamination limits for the manufacture or distribution of aviation fuels up to the
point of delivery to aircraft due to the wide variety of facilities involved and the extremely dynamic nature of the
distribution system. Guidance provided in this bulletin is intended to ensure microbe levels at the point of delivery to
aircraft are significantly lower than the IATA recommended maximum levels for aircraft fuel tanks.
Whilst microbes are inherent in most storage and distribution systems, proliferation of microbes requires certain
conditions. The industry recognises that good facility design, constant daily draining of storage tank sumps and
repetitive filtration of aviation fuel as it moves through the storage and distribution system can significantly attenuate
the movement of microbes downstream. In particular, facility design such as fully or partially lined tanks, cone down
centre sump tanks, floating suctions as well as appropriate water management protocols can help to prevent this
proliferation. To facilitate this management of fuel quality, an understanding of the normal background microbial
contamination levels in a facility and monitoring for change can provide early warning of potential problems and help
prevent expensive and disruptive remediation.
This document proposes the use of on-site microbiological test kits, recommended by IATA, to establish levels of
contamination that may give a warning or require action. In the IATA Guidance Material on Microbiological
Contamination in Aircraft Fuel Tanks there are suggested maximum levels provided for test kits best suited for testing
fuel samples. Other IATA recommended kits can be used to test water phase samples but will only be suitable if
sufficient water can be regularly recovered from the required sampling locations. IATA terminology uses Low, Moderate
and Heavy to describe contamination levels for aircraft tanks, but this is not appropriate in the supply chain as even a
“heavy” contamination from a tank sump in the supply chain may not be immediate cause for action, although further
investigation is mandated. The actual levels for warning and action may need to be modified based on location and type
of sample, as well as experience gained during the initial background level evaluation screening. However, the extent
and frequency of testing should be based on an assessment of risk of microbial growth in the fuel facility. As such,
monitoring for change in the background levels, rather than adhering to absolute limits is the key to successful control
strategies. Contact suppliers for further guidance on recommended limit values for monitoring in the fuel supply chain.
Page 1
Endorsed by IATA Technical Fuel Group
Technical Information Document
Fuel is fundamental and Microbes are always likely to be present, so only water can be managed to prevent microbial
growth. Removal of water breaks the triangle and prevents the active growth of microbes.
Thus, anti-microbial strategies are preferably avoidance strategies but occasionally have to be remedial strategies.
Obviously the most environmentally efficient and safest strategy is avoidance by both good facility design and good
housekeeping; keeping systems clean and as far as possible free of water. Even facilities with sub-optimal design can
be managed with appropriate enhanced water management procedures.
If, however, a fuel system is deemed to be unacceptably contaminated by microbes, active anti-microbial measures are
needed. The objectives of these measures could be one or more of the following:
- Decontaminate storage tanks, filters, pipelines, transports and, at the point of use, end-user equipment.
- Prevent microbial corrosion, particularly by Sulphate Reducing Bacteria (SRB).
- Minimise the contamination of facilities downstream.
- Return fuel to a “fit for service” condition through a combination of operational measures (e.g. settling,
filtration, tank to tank transfer, etc.)
Incidents of growth vary widely in their severity, urgency, microbial nature and availability of equipment (including
spare tanks), waste disposal facilities and chemicals; these factors will control the anti-microbial strategies selected.
Most microbial contamination such as bacteria and fungi will be present predominantly in the tank bottom, particularly
in any free water at the fuel water interface; growth will normally be detected here first before it spreads into the fuel
and affects bulk fuel quality. For routine monitoring, it is best to test low point, dead bottom or drain line samples as
these will provide the earliest and most consistent indication of contamination. (Note that to a lesser extent, fungal
growth may occur on the walls of fuel storage tanks due to the lower water requirements of this microbe.)
Page 2
Endorsed by IATA Technical Fuel Group
Technical Information Document
When sampling storage tanks, drain or bottom samples should be taken after any standard product settling time has
been applied and immediately before tank release. Consistency of sampling conditions helps to reduce repeatability
and reproducibility errors in testing and provides more consistent management of the fuel system.
Sampling should follow standard aviation practice for flushing and sampling of low points (e.g. JIG 2 Section 6.1.1). The
procedure is to flush at full flow a quantity just in excess of the line content and then take a running sample from the
line for a visual check and microbial assay testing. (Where there is evidence of microbial contamination and an
investigation is warranted, see also ASTM D7464 Standard Practice for Manual Sampling of Liquid Fuels, Associated
Materials and Fuel System Components for Microbiological Testing)
Page 3
Endorsed by IATA Technical Fuel Group
Technical Information Document
Mould infection is characterised in samples by soft, brown, irregular particles that in the worst case form a mat of
coherent biological material particularly at the fuel/water interface. A very dirty water bottom with suspended "soft"
debris or the presence of suspended "soft" particulate in the fuel phase is an indication of “heavy” microbial
contamination. Swirling the bottle causes microbiological material to rise from the interface into the fuel phase.
Stable water haze in the fuel phase may be an indication of microbial biosurfactants produced as a result of microbial
activity. Badly contaminated fuel is often not clear and bright. Contamination, however, may not be visually apparent,
particularly if only the fuel phase is present.
Microbial growth may also be visible as brown, grey or translucent sludge or spotting when tanks or filter vessels are
inspected. “Leopard Spotting” is often one of the first visible indications that microbial growth is occurring in a fuel
facility or in the fuel distribution system upstream.
In any one location there will be variations in the numbers and types of microbes present at specific points. This may
alter with time of day and the season (Summer & Winter etc.) due to changes in settling time, aeration, pH, temperature,
salinity and nutrient availability. The precise location of a sampling point and the time of sampling is therefore important
information that should be noted.
Even when microbes are present in large numbers they may not be active because of adverse physical conditions,
particularly temperature and pH. Checking the pH of water bottom samples can be a simple first step.
• Any water bottoms that appear microbiologically contaminated (cloudy, discoloured, lacy/foam interface etc.)
should be checked for pH.
• pH results of 3 to 5.5 indicate possible microbial contamination and testing detailed below should be undertaken.
• If the smell of hydrogen sulphide (i.e., rotten egg) is evident or there is blackening in the sample – especially the
water bottom, this would also require specialised testing for sulphate reducing bacteria (SRB) not covered in this
bulletin. In this case, expert advice should be obtained and fuel supply from the affected tank temporarily suspended.
Note that blackening of water or fuel is usually due to the presence of iron sulphide (e.g. FeS) - a consequence of
the activity of SRB, and is indicative of a prolonged severe infection (stagnant water) and an increased risk of tank
corrosion.
• Some microbes that in exceptional circumstances produce very strong acids at inner tank roof corrosion sites can
only be assayed by a laboratory test. Sampling is also challenging and could only be undertaken as part of tank entry
and working at heights; a pH test result of 3.0 and below of a corrosion site could suggest that these microbes are
present and active there and further investigation should be undertaken.
• Strongly alkaline pH (typically greater than pH 8, but especially greater than pH 10 may indicate the presence of
Caustic (sodium hydroxide) carried over from refinery processing. If Merox treaters or caustic wash treaters are
being used for product sweetening in the supply chian, urgent investigation should be undertaken.
Microbes in samples from high salinity caverns may only grow in tests that have been adjusted to an equivalent high
salinity. No on-site tests are currently available for carrying out such investigations. Samples from these locations will
require expert handling and testing.
Page 5
Page 6
Endorsed by IATA Technical Fuel Group
Technical Information Document
For initial site evaluation where there is no evidence or history of microbial contamination, it is recommended that testing
is conducted at least quarterly for the first year. This will also reveal seasonal variation (if any) and indicate the best
timing for ongoing annual testing.
Some of the test kits for microbial contamination provide quantitative results with either fuel or water samples, others
provide only semi-quantitative results with fuel only samples. Appropriate test selection needs to be made based on a
realistic understanding of test sensitivity and whether water is routinely found in drain samples or not. For routine
monitoring it may be sufficient to use a single type of test. However, no single test can detect the entire spectrum of
microbes that may be present and for a more comprehensive investigation a range of tests should be used.
Thus, for the initial background screening it is suggested that samples are subjected to more than one of the
recommended tests to identify variations that can inform the planned routine onward screening program. The two
categories of microbes, aerobic (oxygen requiring) and anaerobic (oxygen hating) have to be assayed separately. If there
is perceived to be a risk of microbial influenced corrosion, a separate test for anaerobic sulphide generating
microorganisms (e.g. SRB) is advisable. (Note, the IATA recommended tests do not include tests specific for SRB; contact
the test kit supplier or subject matter expert for a suitable SRB test).
From the tests that are available an appropriate selection can be made, either laboratory based or on-site. Laboratory
tests will normally only be carried out by a contractor and they are usually only considered necessary if there are dispute
or insurance issues, a concern over health and safety, a need to trace sources of contamination or to look more deeply
into implementing successful anti-microbial strategies. In all cases it is recommended to seek expert advice from fuel
microbiologists for test selection.
To improve the representation of the system sampled it is preferable to take samples of about 1 litre in volume; this will
enable easier visual observation of the sample for water, dirt, particulates and suspected microbial growth.
Once fuel samples have been taken, any microbes present will tend to slowly die and therefore it is important to test
samples as soon as possible; if samples are to be sent to a laboratory or other facility for testing then the test should be
conducted without delay and ideally within 24 hours. Samples will give increasingly less reliable results as they get older.
The advantage of the IATA recommended on-site test kits detailed in Part 2 below is that all testing can be conducted on
site without delay.
It should be noted that results from all detection kits are only an indication of microbial contamination. Physical
inspection is the only definitive method to determine the condition of the fuel tank, filter or vehicle tank.
2) Assess the need for routine microbial monitoring for tank cleaning evaluation or general quality assurance.
3) Where testing is defined, select appropriate test kit(s) and sampling regime by reference to this bulletin.
Additional advice may be needed from subject matter experts.
4) Generate microbial assay data on site contamination levels and compare with proposed normal, warning and
action levels proposed in this bulletin. Note above comments on pH testing.
5) Where results exceed low levels of contamination, evaluate sampling methodology and repeat testing to
confirm data.
6) Where results are confirmed above low levels, institute appropriate remediation strategies which may include:
a. increased flushing frequency and volume from low points/ sump drains
b. review and testing of supply sources
c. replacement or filter elements and cleaning/ disinfection of filter vessels
d. tank cleaning and disinfection
e. increased microbial testing subsequent to remediation
Incidents of heavy microbial contamination shall require an investigation into cause and shall instigate more frequent
microbial testing as detailed in Part 2 of this bulletin. Subject matter expert input is recommended in these cases.
Consider facilities to be "high risk" if at any time in the previous 2 years, “Action Level” microbial contamination has
been detected at any sampling location on more than one occasion or if significant microbial growth has been observed
during inspection of tanks or filters.
Consider facilities to be "moderate risk' if there has been a single incident of “Action Level” microbial contamination
detected at any sampling location in the previous 2 years and/or if the facility operates under conditions which may be
conducive to microbial growth (e.g. facilities in hot, humid environments, facilities where water or dirt is known to ingress
or accumulate in tanks, facilities which are ship fed and facilities undergoing engineering works such as hydrant
installation or repairs).
Facilities which do not operate under conditions specifically conducive to microbial growth can be considered "low risk'
if no samples have shown “Action Level” contamination and there have been no other indications of microbial growth in
the previous 2 years. Some limited sampling and testing of these facilities (e.g. annually) might be advisable.
“Action Level” microbial contamination is defined as a test result confirmed in the “Action” level category of the
recommended test kits below. Where “Warning” level results are confirmed from the test kits, increase the frequency
and volume of flushing from the affected vessels and retest initially weekly until the level has returned to normal
background levels.
Page 8
Endorsed by IATA Technical Fuel Group
Technical Information Document
The following tables and schemes provide framework guidance for monitoring regimes
(Note this only applies to moderate and high risk facilities as the investigation implies actual incidence of microbial
contamination. Ongoing testing is required for 2 years following return of levels to Low level)
Refuellers Low point drain Contamination Monthly for Quarterly for affected
samples found in vehicle affected vehicle(s) vehicle(s)
drain samples
Contamination Monthly at least Quarterly at least one vehicle
found in upstream one vehicle in in rotation to cover all vehicles
tank or filter rotation to cover all during a 2 year monitoring
samples vehicles during a 1 period
Year monitoring
Hydrant Filter inlet/sump Contamination Monthly at least Quarterly at least one vehicle
Servicers drain samples found in upstream one vehicle in in rotation to cover all vehicles
(Dispensers) tank or filter rotation to cover all during a 2 Year monitoring
samples or vehicles during a 1 period
hydrant low point Year monitoring
drain samples period
Note that results from detection kits are only an indication of microbial contamination. Physical inspection is the only
definitive method to determine the condition of the fuel tank, filter or vehicle tank. Where heavy microbial
contamination has been detected in part of a facility an investigation shall be undertaken to identify cause. At risk
components identified should be physically inspected.
At intervals based on tables above, check product tank bottoms or drains, filter water separator drains, import tank
bottoms or drains. This should be done at least annually where there are no contra-indications to provide historic
contamination levels for the facility.
For fuel samples that are visually clear of free water, fuel water mixes and water only samples it is recommended to use
either the MicrobMonitor2 test (IP613 / ASTM D-7978) or Merck HY-LiTE Jet A1 (ASTM D7463) test or the Conidia Fuelstat
Resinae Plus test. Both the HY-LiTE and Fuelstat tests use an extraction process that recovers the microbes associated with
water or concentrates metabolites and cellular components for the assay. In all cases, care needs to be taken interpreting
results. The background screening level evaluation may provide additional confidence. If in doubt, seek subject matter
expert input. Positive results on a fuel only sample with MicrobMonitor2 may be an indication of fungal spores that would
not give a positive response in the other tests as they detect active growth. Thus a combination of assay tests may be the
best approach. Presence of active spores may be indicative that microbial growth is occurring within the system at a point
distant from the point of sampling.
Each of the three test kits listed above detects and reports microbial growth in a different way. Consult the test
manufacturer’s instructions or guidance for authoritative definitions of Warning and Action levels of contamination. For
each of the recommended tests, typical definitions of contamination levels are provided in Table 3 below. The
MicrobMonitor2 and Conidia Fuelstat Resinae Plus tests have separate definitions of contamination levels for fuel and for
water samples; the levels shown below are for fuel samples for the MicrobMonitor2 and HY-LiTE Jet A-1 tests and for water
samples for the Conidia Fuelstat Resinae Plus test.
Note: Other IATA recommended kits can be used to test water phase samples but will only be suitable if sufficient water
can be regularly recovered from the required sampling locations. Seek subject matter experts and manufacturers for
further advice.
• If WARNING Level contamination is detected, confirm that draining regimes are adequate and review records for all
designated low points and sumps for warning indicators (increased water, poor appearance etc.) Check filter
differential pressure (DP) and Filter Membrane Test records for anomalies.
• Repeat testing as soon as practical and in any event within 1 week to confirm and, if still present, seek further
technical advice.
• Increase Frequency and volume of flushing of tank/vessel sump drain. As a minimum, weekly re-testing should be
completed until microbe levels return to normal background levels.
USE ALL RESULTS TO PRIORITISE SAMPLING POINTS AND PROGRAMMES FOR FUTURE MONITORING
ACCCORDING TO RISK.
NOTE WARNING AND ACTION LEVELS ARE PROVISIONAL PENDING FIELD EXPERIENCE. DETECTION OF HEAVY
CONTAMINATION IN TANK BOTTOM OR FILTER DRAIN SAMPLES DOES NOT NECESSARILY MEAN THERE IS AN
IMMEDIATE RISK OF SUPPLYING FUEL THAT IS NOT FIT FOR SERVICE.
HOWEVER AN URGENT INVESTIGATION IS MANDATORY.
Page 11
Endorsed by IATA Technical Fuel Group
Technical Information Document
Table 3. Typical definitions of WARNING and ACTION Levels for the fuel distribution system
Result
Take fuel Run MBG assay
in normal
sample test
limits? Yes
No
Yes
End
Page 12
Endorsed by IATA Technical Fuel Group
Technical Information Document
The phenomenon of fuel spoilage by microbes has been recorded since the 1930’s when investigators reported the
presence of sulphate reducing bacteria and other microbes in gasoline and kerosene. Rare, early recognised problems
were associated with SRB in aviation gasoline tanks.
When aviation fuel use changed from gasoline to kerosene, the associated organisms and the nature and the frequency
of the problems also changed and in the 1960’s numerous fouling and corrosion problems occurred in aircraft wing
tanks.
Growth does not occur to any significant extent when the fuel is cold or in the absence of free water.
The incidence of contamination problems in aircraft is very much influenced by the climate in which the aircraft is
operating (30° South to 30° North is considered a high-risk area) in conjunction with the efficacy of water draining
procedures. There has undoubtedly been an increase in microbial problems in kerosene fuel during distribution and
use over the last few years. Rapid growth can also occur in warm water bottoms in ground storage installations and
filters.
The consequences of microbial spoilage can be exceedingly severe; the aviation fuel industry significantly improved the
design of aircraft fuel installations to maximise water removal and minimise water accumulation. (Cone down bottoms,
fixed roofs, fast flush systems, lined tanks etc) As a result of these changes, the incidence of microbial problems
significantly reduced in the 1980’s and early 1990’s.
However, the trend towards the installation of hydrant systems for fuel loading at airports, as opposed to batch delivery
by fuelling vehicles, has required changes to the control strategies of microbial growth in some airfield aviation fuel
systems. Hydrant systems utilise underground pipelines, which may accumulate water, microbes and sludge at low
points and release them into the fuel when flow velocity increases at a critical stage in the fuel distribution - just prior
to loading onto the aircraft. It is thus critical that hydrants are properly designed for the flow requirements, and that
routine effective maintenance of the hydrant low points is performed.
The use of hydrant refuelling has also reduced the availability of airfield refuelling vehicles for de-fuelling contaminated
fuel or fuel containing biocide and this has resulted in changes to anti-microbial procedures by IATA and JIG.
Hundreds of different species of microbes are capable of proliferating in water associated with petroleum products.
Some basic knowledge of microbes is desirable for an understanding of the phenomena that they produce and to plan
logical anti-microbial strategies. Three classes of microbes predominate in the petroleum industry; these classes are
very briefly summarised in the table below. (Note: Bacteria may be aerobic or anaerobic.)
Although individual microbes are invisible to the naked eye, their reproduction will produce visible aggregates of “scum
and sludge” - Biomass - with a tendency to adhere to surfaces and interfaces as biofilm. To provide some perspective,
a 1 millimetre diameter water drop is significantly larger in relative terms to an Olympic swimming pool for a microbe
compared to a human. Thus relatively small pockets of water can initiate microbial proliferation and corrosion.
Microbes require an aqueous phase for active growth as most nutrients diffuse into the cell in an aqueous solution or
dispersion. A few microbes have the ability to surround themselves with a hydrated slime, which protects them and
sustains slow growth; for instance some moulds can proliferate slowly in conditions of only high humidity. The microbes
have to build their cell substance from the nutrients they absorb and hence require carbon, hydrogen, sulphur, nitrogen
and phosphorus in substantial amounts in the nutrients and lesser amounts of very many other elements.
Microbes must also be able to obtain energy from the nutrients to sustain their vigorous growth and activity. This
energy, is usually derived by the oxidation or fermentation of organic carbon substrates (such as fuel hydrocarbons and
sugars). A wide range of hydrocarbons can be attacked, although some only by specialised microbes. Certain organisms
can derive energy by the oxidation of inorganic substrates such as nitrites and sulphur or can use light energy but these
are rarely associated with fuel systems.
Property Bacteria Yeasts Moulds
Shape Spherical, Ovoid or Ovoid Filaments (Branching to form Mats)
more often Short
Rods
Typical Size 1 micron 5 to 8 micron > 3 micron
Reproduction Length doubling Bud formation and Growth and branching of filaments
(Times based and then division. separation
Several hours
on doubling
20 minutes or Several hours or
under ideal
greater greater
conditions*)
Preferred Neutral to slight Slight acidity Slight acidity
Conditions alkaline
Note:- some species
are acid tolerant
and can produce
strong mineral acids
(anaerobic SRB)
Issues / Notes Progeny may Growth can Nutrient diffusion through the mats
remain loosely appear like may limit growth to the periphery.
attached to parent filaments leading Dormant spores are produced
or separate and to confusion with which are hydrophobic and disperse
disperse. moulds readily in fuel. If spores in fuel
come into contact with water in
other parts of the fuel system they
can germinate to give new colonies
of growth
Microscope
pictures
showing
typical
appearance
* Conditions for growth in fuel tanks and systems will usually not be optimal and in practice doubling rates will be
significantly longer than those shown.
Endorsed by IATA Technical Fuel Group
Technical Information Document
If molecular oxygen is utilised the microbes are termed ‘Aerobic’. Molecular oxygen need not be involved and there are
a variety of mechanisms by which one compound is oxidised whilst another is reduced. Microbes, which do not need
molecular oxygen, are termed ‘Anaerobic’; for example Sulphate Reducing Bacteria (SRB) will grow by reducing sulphate
(SO4) to sulphide in the absence of oxygen. Some microbes can switch between aerobic and anaerobic modes of growth
according to whether a system is aerated or stagnant.
Many of the operational problems that arise in the petroleum industry are a consequence of the microbial degradation
of hydrocarbons. Partial degradation of hydrocarbons by some microbes can provide ‘food’ for non-hydrocarbon
degraders. Problems occur during distribution, storage, in end-use and can be especially prevalent in product recovery
systems and filters.
Coatings, particularly rubber and paint, can be attacked by microbes. Synthetic polymers, with the exception of some
polyurethanes, are usually resistant to microbial attack, but the fillers, accelerators and plasticisers are not; the physical
characteristics of a formulated plastic may therefore change. For example flexible PVC may become brittle and porous.
Resistance of seals and lining materials if in contact with the fuel should be checked.
Microbes can flourish over a wide range of physical conditions. Microbes with extreme growth preferences, are known
as extremophiles, and some can be found growing slowly in the freezer whilst others occur in hot crude oil tankers; one
group can exist below pH 1, whilst others grow at pH 10. Extremophiles are rarely associated with fuel tanks and systems.
The most abundant growth of a wide variety of species tends to take place from 25 – 40°C at around neutral pH,
although regimes outside of these conditions cannot be considered immune
Moderate physical pressure (e.g. hydraulic pressure) and moderate salinity (osmotic pressure) has little influence on
microbial growth. Some microbes actually prefer high salt conditions, e.g. in salt caverns.
It should not, however, be assumed that any one species can flourish over a wide range of physical conditions as each
species has its own well-defined set of optimal physical conditions. When the physical and chemical environment is not
favourable to active growth the microbial growth may slow down or stop; however it should be noted that under these
‘non-growth’ conditions, considerable chemical change can still be catalysed.
Microbial Corrosion
Microbial proliferation causes system fouling, detrimental chemical and physical changes in fuel products and materials
and equipment malfunction. Microbial influenced corrosion (MIC) may be less visible but the economic consequences
are frequently dramatic and expensive and in some cases safety is compromised. Microbes may influence corrosion
indirectly by destroying corrosion inhibitors or by destroying paint and other coatings and protective oxide films such
as on aluminium and passivized stainless steel. Microbes also accelerate normal electrochemical corrosion processes
as follows:
• When aggregated in slimes or crevices, most aerobic microbes use up oxygen and create an oxygen deficient zone
around them which is anodic in relation to relatively oxygen rich zones where there are few microbes. Oxygen
gradients make electrons flow and anodic corrosion pits develop.
Page 15
Endorsed by IATA Technical Fuel Group
Technical Information Document
• Most microbes produce acids, which can be directly corrosive. Weak organic acids are usually produced, but a few
species can oxidise sulphides and sulphur to sulphates. Sulphates in the presence of hydrogen ions produce
sulphuric acid and can additionally oxidise ferrous compounds to ferric compounds. Sulphuric acid will directly
attack steel and concrete; this corrosion can occur in crude oil cargo tanks on ships and in concrete storage facilities.
Weak organic acids attack aluminium and aluminium alloys; this kind of corrosion can occur in aviation fuel
distribution and aircraft wing fuel tanks.
• Sulphate Reducing Bacteria (SRB) produce hydrogen sulphide (H2S) and ions such as Hydrosulphide (HS-) and
Sulphide (S2-), which are highly aggressive to steel and yellow metals and can result in formation of characteristic
craters. In carbon steel corrosion, a skeleton of carbon remains which is seen as a graphitic (lead pencil) colour.
The bottom of the pit is usually black (ferrous sulphide) although some re-oxidation of this may occur at the surface
of the metal.
• When ferrous sulphide (FeS) forms, it is itself cathodic, and continues to drive electron flow and cause anodic
pitting even after the SRB have been killed or they have become less active. Corrosion driven by SRB is very
pronounced during intermittent aeration, in regular aerobic/anaerobic cycles (irregular/ infrequent resupply) ,
or in oxygen gradients (for instance active aerobic microbe environments.) Consortia of interdependent microbes
are involved. Many different species may be involved in each consortium, differing not only from system to system
but in differing micro-environments in the same system; conditions may differ millimetre by millimetre in terms of
pH, oxygen, Electrode Potential (Eh) and chemical composition. Conditions, and species, may also change with
time, sometimes cyclically. Biofilm is a typical micro-environment for SRB proliferation. SRB influenced corrosion
is most notably a problem where there is long term storage of crude oil or petroleum products and where there is
contamination by sea water.
The overall microbiological process is usually for oils and occasionally other organic substances to first become food for
aerobic microbes. Partially oxidised compounds are formed and become nutrients for other microbes, particularly the
Sulphate Reducing Bacteria.
• SRB cannot normally feed on hydrocarbons directly but only on the organic acids and alcohols produced by aerobic
hydrocarbon degraders.
• SRB cannot use molecular or dissolved oxygen but they extract and use the oxygen in sulphate (or nitrate) to oxidise
organic nutrients. SRB cannot tolerate oxygen, but they are protected from oxygen by the activity of the aerobic
microbes, which locally utilise and deplete the dissolved oxygen. At the same time the aerobes change the
electrode potential (Eh) from 200-300 mV positive to a negative potential; this is another essential parameter
change needed for SRB proliferation.
Page 16
Endorsed by IATA Technical Fuel Group
Technical Information Document
Very many species of bacteria, moulds and yeasts possess the facility to degrade distillate fuels.
The microbes colonise in the free water phase, particularly near the fuel/water interface. Without water, significant
proliferation is impossible. This is a primary reason for the extensive (daily) sump draining requirements for aviation
facilities.
Many more species of microbes associate with the primary hydrocarbon degraders, feeding on the intermediate by-
products of fuel degradation; these species include aerobic secondary degraders and anaerobic SRB. SRB will tend to
be found in the bottom of fuel tanks where oxygen is depleted and oxidation reduction potential (REDOX or ORP) is
negative.
The mould Hormoconis resinae was once considered the predominant cause of fuel spoilage but more recently bacteria
and yeasts and the polymers that they synthesise are of increasing importance.
Any agitation readily disperses the microbes and their associated polymeric slime from the water phase and interface
into the fuel phase. Mould spores are hydrophobic and disperse easily in fuel enabling contamination to spread from
one part of the system to another. Wherever spores in fuel come into contact with water they can germinate and a
new colony of growth is established.
Microbes are rarely distributed evenly within fuel systems. If microbes and microbial material become suspended in
the fuel phase they will usually slowly settle downwards. Hence upper tank fuel will normally be less contaminated
than lower fuel.
Microbes will attach to surfaces in exceedingly high numbers as biofilms, where they probably play an important role
in continually replenishing the populations of freely suspended microbes. Biofilms pose particular problems, as they
can be exceedingly hard to eliminate.
If microbes and the fouling materials they produce are disturbed from the bottom of a tank or the interface into the
fuel, they can cause rapid filter plugging. Fouling of engine fuel system orifices and injectors can result in fuel flow
variations and consequent engine wear and damage.
Once microorganisms have established a presence in an aircraft fuel system a variety of operational and maintenance
issues can occur that could affect the safe and economic operation of the aircraft. For example, uncontrolled microbial
contamination can lead to the corrosion of metallic structures such as wing tanks; degradation of protective coatings,
alloys, and electrical insulation; erratic readings in the Fuel Quantity Indication System (FQIS); blocking of the scavenge
systems; as well as blocking of engine fuel filters.
.
Microbes, typically moulds, can proliferate on the ‘socks’ of coalescer filters and prevent effective water separation.
The microbes colonising the socks contaminate the fuel passing through the coalescer.
Leopard Spotting on Coalescers
Although some fouling and spoilage problems are entirely attributable to microbes, in many cases they are only an
aggravating factor, for example by producing slimes which trap and entrain other particulates.
Corrosion
In storage tanks severe pitting corrosion of the internal steel surface of the tank floor can occur as a result of the activity
of the anaerobic Sulphate Reducing Bacteria. In aircraft fuel tanks, aerobic microbes can cause corrosion of aluminium
wing surfaces by creating local oxygen gradients and by producing aggressive organic acids.
Physical methods of fuel treatment avoid the use of hazardous chemicals, they are generally user friendly and have little
environmental impact. They do not decontaminate the facility in which infected fuel is stored or used and there is no
ongoing downstream affect.
Settling
The simplest physical method of fuel treatment is gravitational settlement; the rate of settlement of microbes and other
particles is governed by Stoke's Law and is dependent on the size and density of the particle relative to the density and
viscosity of the fuel. The density of microbes and microbial debris varies from 0.9 - 1.3 gm/cm3 and is considerably greater
than the density of fuel.
In a quiescent tank individual microbes gravitate very slowly to the tank bottom. However, contamination has greater
operational significance when it is suspended in fuel as larger microbial aggregates or microbial debris; these larger
microbial particles will settle more quickly, typically within the extended settling time prescribed in the Quality Control
section of JIG Guidelines (i.e. for jet fuel 3 hours per metre depth of fuel). As time progresses, any viable microbial units
detected in upper fuel will actually be very small units and have reduced fouling significance. Occasionally, turbulence or
thermal convection currents within the fuel in the tank will impede settlement of microbial contaminants. Rarely, large
aggregates of microbes and debris have exhibited positive buoyancy due to gas production and gas entrainment.
Production of biosurfactants by microbes may also prevent adequate settling, as the organisms remain suspended in water
drops, which form a stable water haze. The concentration of contamination into the lower fuel by settlement may
necessitate supplementary treatment of this, for example, by filtration.
Fuel Filtration
Transportable filter systems have become available and have been used for
processing large volumes of Jet fuel at a rate up to 5000 m3 per day. A final
filtration stage of about 1 µm will provide some decontamination Jet fuel based
on the sizes detailed in the table above; filtration may be the only practical
option for decontaminating bulk Jet fuel as biocide treatment is usually restricted
in the distribution chain.
The picture shows a typical skid mounted filtration unit with integral pump and
microfilter units on the left (vertically mounted) protecting the coalescer vessel
(horizontally mounted).
In all cases the preferred option and treatment protocol usually calls for expert advice.
If there is very heavy microbial contamination a cleaning programme should precede biocide treatment.
Further reading:
Energy Institute (EI) “EI Guidelines for the investigation of the microbial content of petroleum fuels and for the
implementation of avoidance and remedial strategies”
International Air Transport Association (IATA) “Guidance Material on Microbiological Contamination in Aircraft Fuel
Tanks”
American Society for Testing and Materials (ASTM) “ASTM D6469 “Standard Guide for Microbial Contamination in Fuels
and Fuel Systems”
Acknowledgement: JIG Ltd thank Graham Hill of ECHA Microbiology Ltd. and The Clouds Network Ltd. for the technical
support and pictorial input to this bulletin
Page 20