C Inter5 009
C Inter5 009
0
Function Block Library ILS_CEM
Function Description Edition 09/13
Interlock C_INTER5
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring to property damage only have no safety alert symbol. The notices shown below are graded according to the
degree of danger.
Danger
! indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
! indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
! with a safety alert symbol indicates that minor personal injury can result if proper precautions are not
taken.
Caution
without a safety alert symbol indicates that property damage can result if proper precautions are not
taken.
Attention
indicates that an unintended result or situation can occur if the corresponding notice is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used.
A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation
of a device/system may only be performed by qualified personnel. Within the context of the safety notices in this
documentation qualified persons are defined as persons who are authorized to commission, ground and label devices,
systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Warning
! This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
Correct, reliable operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG.
The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes
could violate the rights of the owner.
Siemens AG
Automation and Drives Siemens AG 2005
Postfach 4848, 90327 Nuremberg, Germany Technical data subject to change.
Siemens Aktiengesellschaft
Reference Manual Objects Interlock C_INTER5
INTERLOCK C_INTER5 1
Description of C_INTER5 4
Type/Number 4
Calling OBs 4
Function 4
Operating principle 5
Input Interfaces 5
Output Interfaces 7
Configuring 8
Error handling 9
Start-up characteristics 9
Time response 9
Assignment of the 32-bit status word VSTATUS 9
Message characteristics 9
Monitoring of process variables 9
I/O-bar of C_INTER5 10
OS-Variable table 11
Variable details 12
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Interlock C_INTER5 Reference Manual Objects
Description of C_INTER5
Type/Number
Module name: C_INTER5
Module no.: FB1058
Calling OBs
In the same OB with and after the last block whose signals are to be displayed on the
C_INTER5.
Function
The C_INTER5 block is used to implement a standardized interlock display which can be called
on the OS. The block can be assigned a maximum of 5 input signals, which can each be
inverted as required.
The main object of the C_INTER5 block was developed in order to save much as possible OS
variables. Therefore the signal designations are not entered at the input signals, but in the string
variable S_TEXT.
The designations of all 5 input signals must be entered in this string variable S_TEXT,
separated by a semicolon “;”. The string length for each signal designation is 16 characters.
The five inputs I1_1 to I1_5 form a group. Each signal can be linked logically either directly or
inverted by setting the corresponding inputs NEG1_1 to NEG1_5.
Important: The modification of the negation inputs NEG1_1 to NEG1_5 in runtime (download
! for changes) can lead to a loss of the RLO for one CPU Cycle.
Therefore we recommend inverting directly at the Inputs I1_1 to I1_5.
The type of logic operation of the group is set at the AND_OR1 parameter.
The logic result “LOG1” is represented by green color.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Reference Manual Objects Interlock C_INTER5
Operating principle
Input Interfaces
I1_1 Input Signal 1 Basic state 1-Signal
Format BOOL
The status of this interface is displayed in the interlock faceplate. The display is grey if the signal
is ok and red if the signal is missing.
At input I1_1 a direct connection of a negation can be used. The indicated status is the status
after the negation. The negation itself is not shown in the faceplate.
Note: The modification of the negation input NEG1_1 in runtime (download for changes) can
! lead to a loss of the RLO for one CPU Cycle.
Therefore we recommend inverting directly at Input I1_1.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Interlock C_INTER5 Reference Manual Objects
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Reference Manual Objects Interlock C_INTER5
Output Interfaces
Q Output signal
Format BOOL
The result of the interlock function is shown at output Q. This output is used for the connection
to the interface of the CEMAT block.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Interlock C_INTER5 Reference Manual Objects
Configuring
AS:
CFC Plan editing example:
The assignment of instance names is particularly important when the Interlock module is used.
Depending on the "main object", the name is formed as follows.
For example, C_DRV_1D motor with plant identifier "FK11/E001" should be given an interlock
protective circuit on the input interface "ESVG".
The name of the interlock module instances consists of:
FK11/E001 = main object
_ESVG = interface description
1-3 = number of the interlock modules, max. 3 units
i.e. FK11/E001_ESVG1 is the name of the first interlock module.
Please note:
- Correctly select the interconnection logic (red background means error)
- Assign the signal designations for the control room operator with understandable text.
- Enter the signal designations in S_TEXT.
- on one Interface it could only connect one of the Interlock module Type
(Interlock or Interlock5)
OS:
No further parameterization is necessary.
However, an OS compile must be carried out (in order to generate the tags in the tag
management).
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Reference Manual Objects Interlock C_INTER5
Error handling
Only by means of the operating system.
Start-up characteristics
No special measures taken.
Time response
The block does not have a time response.
Message characteristics
Does not exist.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Interlock C_INTER5 Reference Manual Objects
I/O-bar of C_INTER5
C_INTER5
Permitted
Element Meaning Format Default Type Attr. HMI
Values
aaaaaaaa
aaaaaaaa;
bbbbbbbb
bbbbbbbb;
Signal designations for the
STRING ccccccccc
S_TEXT input signals 1 to 5, separated I +
[86] ccccccc;
by a semicolon.
dddddddd
dddddddd;
eeeeeeee
eeeeeeee
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Reference Manual Objects Interlock C_INTER5
OS-Variable table
C_INTER5
PLC Data
OS Variable Description OS Data Type
Type
Signal designations for the
STRING
S_TEXT input signals 1 to 5, separated Text variable 8-bit character set
[86]
by a semicolon.
Extended status display in
VSTATUS DWORD Unsigned 32-bit value
block icons
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Interlock C_INTER5 Reference Manual Objects
Variable details
Internal structure of the Status word:
VSTATUS_B30 8
VSTATUS_B31 9
VSTATUS_B32 NEG1_1 10 1= I1_1 wird invertiert 1 = I1_1 will be inverted
VSTATUS_B33 NEG1_2 11 1= I1_2 wird invertiert 1 = I1_2 will be inverted
VSTATUS_B34 NEG1_3 12 1= I1_3 wird invertiert 1 = I1_3 will be inverted
VSTATUS_B35 NEG1_4 13 1= I1_4 wird invertiert 1 = I1_4 will be inverted
VSTATUS_B36 NEG1_5 14 1= I1_5 wird invertiert 1 = I1_5 will be inverted
VSTATUS_B37 15
VSTATUS_B20 16
VSTATUS_B21 17
VSTATUS_B22 18
VSTATUS_B23 19
VSTATUS_B24 20
VSTATUS_B25 21
VSTATUS_B26 AND_OR1 22 1= AND, 0= OR erste Gruppe 1= AND, 0= OR first group
VSTATUS_B27 23
VSTATUS_B10 24
VSTATUS_B11 25
VSTATUS_B12 Q 26 Ausgangssignal Output signal
VSTATUS_B13 27
VSTATUS_B14 28 I
VSTATUS_B15 29
VSTATUS_B16 30
VSTATUS_B17 31
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc
Reference Manual Objects Interlock C_INTER5
Display
When an interlock protective circuit is present, the corresponding interface is indicated with a
blue point in the diagnostic dialog of the associated module type.
The interlock dialog displays the input parameter name of its logical state and the subsequent
interconnection.
In an error situation, the input signal is displayed with a red background.
For the control room operator meaningful designations should be chosen for the input
parameters.
Operator Control
A single click on the corresponding interface designation opens the Interlock dialog.
Further functions are not enabled.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_INTER5_009.doc