Wind Load and Earthquake Resistant Example
Wind Load and Earthquake Resistant Example
Mean
Probable
Sr. No. Class of Structure Design Life of
Structure in
Years
1 All general buildings and structures 50
Temporary sheds,structures such as those used during construction
2 operations ( for example , formwork and false work ) , structures 5
during construction stages and boundary walls
Buildings and structures presenting a low degree of hazard to life
3 and property in the event of failure , such as isolated towers in 25
wooded areas,farm buildings other than residential buildings.
4 Important buildings and structures such as hospitals communication 100
buildings/towers,power plant structures.
K1 = X NP / X 50,0.63 = A - B [ log { -1 / N log ( i - P N ) } ] / A + 4 B
N = mean probable design life of structure in years ;
Slope Le
Where
7 7 30
6 6 25.0
5 5 21.0
4 4 17.0
3 3 13.0
2 2 9.0
1 1 5.0
0 0 0.0
-1
-2
-3
-4
-5
-6
-7
-8
Design wind
pressure Pz 0.6 x Vz2
N / m2 =
Design wind Load ( F ) =Cf x Ae x Pz
Cf = Force co-efficient of building
Ae = Effective Frontal Area
Pz = Design wind load wind load on face of =
a= 20 m
b = 30 m
h = 30 m
a / b = 0.666666666666667
h / b = 1.00
Cf = fig 4(a)
= 1.22 There are
Ae = 4.29
Nodes are considered at the centre of beam-column joint.Assume the beam overall depth =
7 7 30
6 6 25.0
5 5 21.0
4 4 17.0
3 3 13.0
2 2 9.0
1 1 5.0
0 0 0.0
-1
-2
-3
-4
-5
-6
-7
-8
7 7 30
6 6 25.0
5 5 21.0
4 4 17.0
3 3 13.0
2 2 9.0
1 1 5.0
0 0 0.0
-1
-2
-3
-4
-5
-6
-7
-8
ses of Structures in Different Wind Speed Zones
K1 Factor for Basic Wind Speed m /s
33 39 44 47 50 55
1.0 1.0 1.0 1.0 1.0 1.0 1
egory 1 - average height of any object surrounding the structure is less than 1.5 m.
egory 2 - average height of few object surrounding the structure is between 1.5 m and 10 m.
ucture is upto 10 m.
600 sq.m.
m on floors
2
(1) (2) (3)
m2 on roofs
m2 on floors
m2 on roofs
YPICAL FLOOR 6 @ 5000
Design wind
K2 Vz m/sec
pressure Pz N / m2
1.06 49.9048 1494.29
1.04 48.7278 1424.64 4 @ 5000
1.02 47.7862 1370.11
0.99 46.42088 1292.94 PLAN
0.95 44.53768 1190.16
0.91 42.8428 1101.30 3000
0.91 42.8428 1101.30
0.91 42.8428 1101.30
3000
3000
3000
ELEVATION
d load on face of = 30
7 rows of columns.
Force @
Design wind Design wind each Story
pressure Pz N Load ( F ) =Cf x F ( KN / m ) Level,Nodal
/ m2 Ae x P z ( N / m ) Point Load
( KN )
(B)
(C )
X
(D)
Wind Direction
No. of Storey
1
2
3
6
7
8
9
10
11
12
13
14
15
16
20
30
EXAMPLE : - Calculation of Design Seismic Force by Static Analysis Method
DATA :
No. of storey 4 ( Including Terrace )
Type of All other buildings like office Moment Resisting R.C.C. frame building with brick infill panels
Building building
Location Shillong
Name
Building Syste Steel buildings with special moment resisting frame ( SMRF )
Soil Type soft soil sites
Seismic zone V
zone factor 0.36
importance 1
factor I
response
reduction 5
factor R
Floor Area 15 X 20 = 300
Dead Load 12 KN / m on floors
2
10 KN / m2 on roofs
Live load 4 KN / m2 on floors
1.5 KN / m2 on roofs
Floor Height 3.2 m TYPICAL FLOOR
4.2 m G.F.
Seismic Weight :
Floors :
W1 = W2 = W3 =
4200 KN
Roof :
W4 = 3000 KN
Total Seismic weight of the structure
W = (3 x 4200 + 1 x 3000 )
W= 15600 KN
Fundamental Period
EL in X - Direction :
T =0.09 h / d√
where h = height of building in m
d = base dimension of the building at the plinth level along the considered direction of earthquake shaking in m.
h= 13.8 m
d= 20 m
T= 0.28 sec
Sa / g = 2.5 Design acceleration coefficient
Design horizontal seismic coefficient A h
Ah = ( z / 2 ) x ( Sa / g ) / ( R / I )
= 0.09
Design base shear VB = Ah W
VB = 1404 KN
EL in Y - Direction :
√
T =0.09 h / d
where h = height of building in m
d = base dimension of the building at the plinth level along the considered direction of earthquake shaking in m.
h= 13.8 m
d= 15 m
T= 0.32 sec
Sa / g = 2.50 Design acceleration coefficient
Design horizontal seismic coefficient A h
Ah = ( z / 2 ) x ( Sa / g ) / ( R / I )
= 0.09
Design base shear VB = Ah W
VB = 1404 KN
Lateral Load Distribution with Height by the static Method
Storey Level Wi ( KN ) hi ( m )
4 4 3000 13.8
3 3 4200 10.6
2 2 4200 7.4
1 1 4200 4.2
0
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10
-11
Storey Level Wi ( KN ) hi ( m )
7 7 4400 30.75
6 6 5400 26.75
5 5 5400 22.75
4 4 5400 18.75
3 3 5400 14.75
2 2 5400 10.75
1 1 5400 6.75
0 0 1600 1.25
-1
-2
-3
-4
-5
-6
-7
-8
38400
th brick infill panels
Y
sq.m.
(1) (2) (3) (4)
3 @ 5000
4 @ 5000
PLAN
3200
3200
3200
4200
ELEVATION
W i hi 2 x Lateral Force at i th
( 1000 ) Level for EL in
/(1000000) W i hi 2 / Ʃ W i h i 2 direction ( KN )
( N / mm2 )
X Y
571.3 0.424 595.3582 595.3582
471.9 0.350 491.7676 491.7676
230.0 0.171 239.6689 239.6689
74.1 0.055 77.20524 77.20524
30.75 C1 C2 C2
26.75
22.75
18.75
14.75 6000
10.75 C3 C3
6.75 C2
1.25
sq.m.
6000
C2 C3 C3
6000
C1 C2 C2
6000 6000
Lateral Force at i th
Level for EL in
W i hi 2 x direction ( KN )
( 1000 )
/(1000000) W i hi 2 / Ʃ W i h i 2
( N / mm2 ) Q i , KN Q i , KN V i KN (
( point ( point shear )
Load ) X Load ) Y
4160.5 0.282 400.68 400.68 400.68
3864.0 0.262 372.13 372.13 772.81
2794.8 0.189 269.16 269.16 1041.97
1898.4 0.129 182.83 182.83 1224.80
1174.8 0.080 113.14 113.14 1337.95
624.0 0.042 60.10 60.10 1398.05
246.0 0.017 23.69 23.69 1421.74
2.5 0.000 0.24 0.24 1421.98
(B)
(C )
X
(D)
C1
C2
C2
C1
6000
4 15 25 15
7500
3 25 40 35 25
7500
2 25 40 40 40
7500
1 15 25 25 25
A B C D E
7500 7500 7500 7500
Beam Size = 300 mm X 600 mm
Column Size = 500 mm X 500 mm
Concrete Grade M 25
Floor Seismic Load = 480 KN
Floor Height = 5 m
Ec = 25000 MN/m2 1 MN/m2 = 1000 KN/m2
For Columns
Ic = 0.005208 m4
EI/L = 26.04167 MNm
For Beams
Ib = 0.0054 m4
EI/L = 18 MNm
Lateral stiffness of the frames
Beams Columns Kf =12/h2 x [
1 / ( 1/Ʃ
Frames Ʃ[ EI/L] = No. of Ʃ[EI/L] =
( EI/l )c + 1/
No. of 18 Nb columns 26.04 Nc
Ʃ( EI/l )b )]
beams Nb MNm Nc MNm
1,2,3 4 72 5 130.2083 22.2542757
4 2 36 3 78.125 11.8291347
A,B,C 3 54 4 104.1667 17.0706006
D,E 2 36 3 78.125 11.8291347
Centre of mass
Xm = 13.56 m
Ym = 9.81 m
Centre of rigidity
Xr = 13.75 m
Yr = 10 m
Accidental eccentricity and torsion
Seismic load acting in x direction :
bi = floor plan dimension of floor i , perpendicular to the direction of the force. = 22.5
0.05 bi = 1.125 m
esi =ey = 0.19 m
edi =1.5 esi + 0.05 bi OR edi = esi - 0.05 bi
edi = 1.40 m -0.94 m
Torsion Tx = 674.04 OR -450.6383 KNm
Seismic load acting in y direction :
bi = floor plan dimension of floor i , perpendicular to the direction of the force. = 30
0.05 bi = 1.5 m
esi =ey = 0.19 m
edi =1.5 esi + 0.05 bi OR edi = esi - 0.05 bi
edi = 1.78 m -1.31 m
Torsion Ty = 854.04 OR -630.6383 KNm
Distribution of Lateral Forces
( i ) Resultant force of 480 KN acting at centre of rigidity
Hux = 480 KN Huy = 480 KN
Frame kxx MN/m Hu =( kxx / Ʃ kxx ) x Hux KN Frame kyy MN/m Hu =( kyy / Ʃ kyy ) x Huy KN
1 22.25428 135.9179 A 17.0706 109.4414
2 22.25428 135.9179 B 17.0706 109.4414
3 22.25428 135.9179 C 17.0706 109.4414
4 11.82913 72.24638 D 11.82913 75.83784
Ʃ 78.59196 480 E 11.82913 75.83784
Ʃ 74.87007 480
( ii ) Tx = 674.04 KNm or -450.6383 KNm
Column
Line lp = ( kx y2
kx ky y x + ky x2 ) Tx = 674.04 Tx =
Vxi = Tx y Vyi = Tx x Vxi = Tx y
kx/ Ʃ lp ky/Ʃlp kx/Ʃlp
MN/m MN/m MNm KN KN KN
1 22.25428 - -10 - 2225.4 -11.79 - 7.88
2 22.25428 - -2.5 - 139.1 -2.95 - 1.97
3 22.25428 - 5 - 556.4 5.90 - -3.94
4 11.82913 - 12.5 - 1848.3 7.84 - -5.24
A - 17.0706 - -13.75 3227.4 - -12.44 -
B - 17.0706 - -6.25 666.8 - -5.65 -
C - 17.0706 - 1.25 26.7 - 1.13 -
D - 11.82913 - 8.75 905.7 - 5.49 -
E - 11.82913 - 16.25 3123.6 - 10.19 -
12719.4
( iii ) Ty = 854.04 KNm or -630.6383 KNm
Column
Line lp = ( kx y2
kx ky y x + ky x2 ) Tx = 854.04 Tx =
Vxi = Tx y Vyi = Tx x Vxi = Tx y
kx/ Ʃ lp ky/Ʃlp kx/Ʃlp
MN/m MN/m MNm KN KN KN
1 22.25428 - -10 - 2225.4 -14.94 - 11.03
2 22.25428 - -2.5 - 139.1 -3.74 - 2.76
3 22.25428 - 5 - 556.4 7.47 - -5.52
4 11.82913 - 12.5 - 1848.3 9.93 - -7.33
A - 17.0706 - -13.75 3227.4 - -15.76 -
B - 17.0706 - -6.25 666.8 - -7.16 -
C - 17.0706 - 1.25 26.7 - 1.43 -
D - 11.82913 - 8.75 905.7 - 6.95 -
E - 11.82913 - 16.25 3123.6 - 12.91 -
12719.4
( iv ) Final Forces acting on frames
25
15
E
m
/ Ʃ kyy ) x Huy KN
-450.6383
Vyi = Tx x
ky/Ʃlp
KN
-
-
-
-
8.32
3.78
-0.76
-3.67
-6.81
-630.6383
Vyi = Tx x
ky/Ʃlp
KN
-
-
-
-
11.64
5.29
-1.06
-5.13
-9.53
Load to
Load due to Tx or Ty be taken
for
analysis
s in y-direction
- 11.03 *
- 2.76 *
- 7.47 *
- 9.93 *
11.64 121.08
5.29 114.73
1.43 110.87
6.95 82.79
12.91 88.74
116
C1 C2 C2 C1
147
7.5
C3 C3
C2 C2
140
7.5 350 KN
C2 C3 C3 C2
130
7.5
115
C1 C2 C2 C1
97
7.5 7.5 7.5
6 th Floor Plan
No. of storey = 7
horizontal seismic shear = 350 KN at 6 th floor 41
All columns = 500 mm X 500 mm
All Beams = 300 mm X 600 mm
Floor Height = 5m
Concrete Grade M 20
E = 22360.68 MN/m2
For Beams
Ib = 0.0054 m4
lb = 7.5 m
Ʃ [ EI/l]b = 193.20 MNm ( 12 beam )
For Columns
Ic = 0.005208 m4
lc = 5m
Ʃ [ EI/l]c = 372.68 MNm ( 16 column )
Displacement due to column rotation
D1 = V h2/12Ʃ[EI/h]col KNm2 / MNm
= 1.957 mm
Displacement due to Beam rotation
D1 = V h2/12Ʃ[EI/l]beam KNm2 / MNm
= 3.774 mm
Total drift of the storey δ = D1 + D2
= 5.731 mm
Lateral stiffness ks,i = Hu,i / δ i
Hu i = lateral shear acting on the i th storey
δu i = lateral displacement of i th storey i.e. drift of i th storey
ks,i = 12/hs2 [ 1 / (1/ Ʃ(EI/l)col + 1/Ʃ(EI/l)beam)]
ks,i = 61.07 MN/m OR KN/mm
Drift due to wind shear of 147 KN
δ6 = Hu6 / k 6
δ6 = 2.407 mm
All beam Concrete Grade M 20
Column 1,2,3,4 Storey Concrete Grade M 25
Column 5,6,7 Storey Concrete Grade M 20
For M20 Grade of concrete E = 22360.68 MN/m2
For M25 Grade of concrete E = 25000 MN/m2
For beams
Ib = 0.0054 m4
lb = 7.5 m
Ʃ [ EI/l]b = 193.20 MNm for all storey (12 beam )
For columns
Ic = 0.005208 m4
lc = 5m
Ʃ [ EI/l]col = 16 x Ec x Ic /lc , since Ec and lc are different in different storeys. ( 16 column )
= 0.083333 Ec /lc MNm
LATERAL STIFFNESS OF A STOREY :
Storey Mix Ec h Ʃ [ EI/l]col Ʃ [ EI/l]b = ks,i = 12/hs2 [ 1 / (1/ Ʃ(EI/l)col + 1/Ʃ(EI/l)beam)]
7 20 22360.68 5 372.68 193.20 61.07
6 20 22360.68 5 372.68 193.20 61.07
5 20 22360.68 5 372.68 193.20 61.07
4 25 25000 5 416.67 193.20 63.36
3 25 25000 5 416.67 193.20 63.36
2 25 25000 4.1 508.13 193.20 99.92
1 25 25000 1.1 1893.94 193.20 1738.64
STOREY DRIFT AND ABSOLUTE DISPLACEMENT DUE TO WIND
Drift Absolute
ks ,
Storey Qu , KN Hu , KN KN/mm δ=Hu/Ks Displace
mm ment mm
7 116 116 61.07
1.90 39.35
6 147 263 61.07
4.31 37.45
5 140 403 61.07
6.60 33.15
4 130 533 63.36
8.41 26.55
3 115 648 63.36
10.23 18.14
2 97 745 99.92
7.46 7.91
1 41 786 1738.64
0.45 0.45
39.35
For wind loads , as per IS 456:2000,maximum sway at top storey is permitted as H/500.
H= 30.2 m
maximum sway permitted = 60.4 mm
maximum sway = 39.35 mm safe
STOREY DRIFT AND ABSOLUTE DISPLACEMENT DUE TO SEISMIC LOADS
For seismic loads,as per IS:1893 , the storey drift shall not be more than 0.004 H
Drift
Drift Absolute
Height H permitted ks ,
Storey Qu , KN Hu , KN δ=Hu/Ks Displace
mm 0.004 H KN/mm
mm ment mm
mm
7 5000 20 439 439 61.07 7.19 86.49 safe
6 5000 20 350 789 61.07 12.92 79.30 safe
5 5000 20 225 1014 61.07 16.60 66.38 safe
4 5000 20 128 1142 63.36 18.02 49.78 safe
3 5000 20 57 1199 63.36 18.92 31.75 safe
2 4100 16.4 13 1212 99.92 12.13 12.83 safe
1 1100 4.4 0 1212 1738.64 0.70 0.70 safe
86.49
stability indices
Q =( Ʃ
Storey Ʃ Pu KN hs , m ks KN/m Pu / hs ) x Type
( 1/ Ks )
7 360 5 61073.64 0.0012 No-sway
6 653 5 61073.64 0.0021 No-sway
5 968 5 61073.64 0.0032 No-sway
4 1264 5 63357.28 0.0040 No-sway
3 1542 5 63357.28 0.0049 No-sway
2 1856 4.1 99923.36 0.0045 No-sway
1 2164 1.1 1738641 0.0011 No-sway
KN 439 KN
5 m 5 m
KN 350 KN
5 m 5 m
KN 225 KN
5 m 5 m
KN 128 KN
5 m 5 m
KN 57 KN
5 m 5 m
KN 13 KN
4.1 m 4.1 m
KN 0 KN
1.1 m 1.1 m
Ʃ(EI/l)col + 1/Ʃ(EI/l)beam)]