BASE PLATE Design PDF
BASE PLATE Design PDF
Date : Page :
Basic Design Parameters
75 Column Section = 400 Design Load For Base Plate & Shear Key Design
Permissible Stress increase for Wind/Seismic Case = 25.0 % n' = Without Wind/Seismic Condition and 'y' = With Wind/Seismic Condition
- As per IS : 800
Permissible Stress without Wind/Seismic Case Permissible Stress with Wind/Seismic Case
Axial Tension stf = 120 MPa Axial Tension stf = 150 MPa
Effective Area of 24 f Anchor Bolts for Tension = 362 mm^2 - considering Net Area = 80% of Gross Area
Consideration
Safe
Shear tvf,cal N/A
Date : Page :
Calculation for Base Plate Thickness
Load Cases Bending Strength of Plate (R) =
Design Base Pressure swn 31 Kg/cm2 1682 Kg/cm2 (without wind/seismic case)
Case-1 For Cantilever Portion (considering 1/2 load effective because of stiffener) Minimum Thickness required for Case -1
Moment (M) kg-cm/cm 430.3 tpl = 1.07 cm
1/2
tpl =(6*M/R) = 1.1 cm
Case-2 For 3 side Supported Portion (As per Roark's Hand Book)
a = 12.5 cm b = 20.0 cm a/b = 0.625
At x = a/2, z = b sa= -b3* swn*b2 / tpl2 Minimum Thickness required for Case -2
tpl = 1.0 cm tpl = 1.0 cm
a = 12.5 cm b1 = 10.0 cm
c = 12.5 cm b2 = 10.0 cm
a1 = 6.3 cm b= b1 + b 2 = 20.0 cm
[ 'a' should not be greater than a1+b1; using design value of 'a' ]
a
Design value of a = 12.5 cm
b1
[ 'c' should not be greater than a1+b2; using design value of 'c' ] a1
Design value of c = 12.5 cm
b2
1/2
tpl =(6*M/R) = 1.46 cm
Case-2 Bending of Side -'b' Minimum Thickness required considering Case -1, 2 & 3
Moment (M) kg-cm/cm 6250 tpl = 1.5 cm
1/2
tpl =(6*M/R) = 0.92 cm
Summary :
Minimum thickness required for compression = 1.1 cm
Date : Page :
Calculation for Shear Key
Grout
Base Plate
Grout = 50.0 mm
Embedment
Embedment in Concrete = #####
Shear Key for Hx : Required
Shear Key Shear Key for Hz : Required
Load Cases 0
Hx 11.0 T
Wind/Seismic Condition y
Uniformly Distributed Load on Shear Key 28 Kg/Sq. cm - considering no contribution of Grout
Load Cases 0
Hz 4.5 T
Wind/Seismic Condition y
Uniformly Distributed Load on Shear Key 18 Kg/Sq. cm - considering no contribution of Grout