Data sheet 6ES7331-7PF01-0AB0

SIMATIC S7-300, Analog input SM 331, isolated, 2/3/4-wire, 8 AI,


Resistor, Pt100/200/1000 NI100/120/200/500/1000, CU10,
characteristics according to GOST 16 (internal 24) bit, 50ms, 1x 40-
pole

Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes

Input current
from load voltage L+ (without load), max. 240 mA
from backplane bus 5 V DC, max. 100 mA

Power loss
Power loss, typ. 4.6 W

Analog inputs
Number of analog inputs 8
● For resistance measurement 8
permissible input voltage for voltage input 75 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio
(destruction limit), max. 1:20)
Input ranges
● Voltage No

6ES7331-7PF01-0AB0 Subject to change without notice


Page 1/4 12/13/2019 © Copyright Siemens
● Current No
● Thermocouple No
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V No
● 1 V to 5 V No
● 1 V to 10 V No
● -1 V to +1 V No
● -10 V to +10 V No
● -2.5 V to +2.5 V No
● -250 mV to +250 mV No
● -5 V to +5 V No
● -50 mV to +50 mV No
● -500 mV to +500 mV No
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA No
● -10 mA to +10 mA No
● -20 mA to +20 mA No
● -3.2 mA to +3.2 mA No
● 4 mA to 20 mA No
Input ranges (rated values), thermocouples
● Type B No
● Type C No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 Yes
● Ni 100 Yes
● Ni 1000 Yes
● LG-Ni 1000 Yes
● Ni 120 Yes

6ES7331-7PF01-0AB0 Subject to change without notice


Page 2/4 12/13/2019 © Copyright Siemens
● Ni 200 Yes
● Ni 500 Yes
● Pt 100 Yes
● Pt 1000 Yes
● Pt 200 Yes
● Pt 500 Yes
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
● 0 to 300 ohms Yes
● 0 to 600 ohms Yes
Characteristic linearization
● parameterizable Yes
Cable length
● shielded, max. 200 m

Analog value generation for the inputs


Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), 16 bit; Two's complement
max.
● Integration time, parameterizable Yes
● Basic conversion time (ms) up to 4 channels: 10 ms per module, over 5 channels: 190 ms per
module, 8 channels: 80 ms
● Interference voltage suppression for 400 / 60 / 50 Hz
interference frequency f1 in Hz

Encoder
Connection of signal encoders
● for resistance measurement with two-wire Yes; without resistance correction
connection
● for resistance measurement with three-wire Yes
connection
● for resistance measurement with four-wire Yes
connection

Errors/accuracies
Operational error limit in overall temperature range
● Resistance, relative to input range, (+/-) 0.1 %
● Resistance thermometer, relative to input ±1 K
range, (+/-)
Basic error limit (operational limit at 25 °C)
● Resistance, relative to input range, (+/-) 0.05 %
● Resistance thermometer, relative to input ±0.5 K
range, (+/-)

Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable

6ES7331-7PF01-0AB0 Subject to change without notice


Page 3/4 12/13/2019 © Copyright Siemens
Alarms
● Diagnostic alarm Yes; Parameterizable per group
● Limit value alarm Yes; Parameterizable
● Hardware interrupt Yes; Parameterizable, channels 0 to 7
Diagnostic messages
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes

Potential separation
Potential separation analog inputs
● between the channels Yes
● between the channels, in groups of 2
● between the channels and backplane bus Yes
● between the channels and the power supply of Yes
the electronics

Isolation
Isolation tested with 500 V DC

Connection method
required front connector 40-pin

Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm

Weights
Weight, approx. 272 g

last modified: 12/10/2019

6ES7331-7PF01-0AB0 Subject to change without notice


Page 4/4 12/13/2019 © Copyright Siemens