6ES73317PF010AB0 Datasheet en
6ES73317PF010AB0 Datasheet en
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 240 mA
from backplane bus 5 V DC, max. 100 mA
Power loss
Power loss, typ. 4.6 W
Analog inputs
Number of analog inputs 8
● For resistance measurement 8
permissible input voltage for voltage input 75 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio
(destruction limit), max. 1:20)
Input ranges
● Voltage No
Encoder
Connection of signal encoders
● for resistance measurement with two-wire Yes; without resistance correction
connection
● for resistance measurement with three-wire Yes
connection
● for resistance measurement with four-wire Yes
connection
Errors/accuracies
Operational error limit in overall temperature range
● Resistance, relative to input range, (+/-) 0.1 %
● Resistance thermometer, relative to input ±1 K
range, (+/-)
Basic error limit (operational limit at 25 °C)
● Resistance, relative to input range, (+/-) 0.05 %
● Resistance thermometer, relative to input ±0.5 K
range, (+/-)
Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable
Potential separation
Potential separation analog inputs
● between the channels Yes
● between the channels, in groups of 2
● between the channels and backplane bus Yes
● between the channels and the power supply of Yes
the electronics
Isolation
Isolation tested with 500 V DC
Connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 272 g