Assignment 5 - 2008 - Solution - 2
Assignment 5 - 2008 - Solution - 2
Assignment : #5 (Solutions)
Figure 1
(10 marks)
Solution
The equivalent sequence diagram for the given system and its connection for
a B-C-G fault are shown below in figure 1a and 1b respectively. For a two
phase to ground fault all the three impedance networks are connected in
parallel at the fault point as shown in figure 1b. In addition since the
transformer configuration is YnD, there will not be any zero sequence current
at the relay location for ground faults on the star side of the transformer.
1 Of 11
Figure 1a
Figure 1b
The three phase transformer ratio is considered to be “1”. Since we are only
interested in finding the impedance at location 2, we have not considered the
30° shift in the sequence currents introduced by the transformer (this shift
will affect the phase relationship between the currents and voltages across
the primary and secondary of the transformer and will not affect the phase
relationship between voltages and currents on any one side).
We can calculate the sequence currents and voltages at the relay point
looking at the figure 1b as follows (All values are given in per unit)
Zeq = Zs1+ZL1+Zt1+Zt2+ZL2+Zs2
= 0.02 + j 1.14 pu.
iRA=iR0+iR1+iR2 = 0 pu
iRB = iR0 + a2 * iR1 + a * iR2 = -1.5189 – j 0.0266 pu = 1.5191<-179º
iRC = iR0 + a * iR1 + a2 * iR2 = 1.5189 + j 0.0266 pu m = 1.5191<1.005 º
iRN = iRA+iRB+iRC = 0
2 Of 11
vRA=vR0+vR1+vR2 = 0.9123 - 0.0015i pu = 0.91231<-0.09662 º
vRB = vR0 + a2 * vR1 + a * vR2 = -0.4615 – j 0.5615 pu = 0.72679<-129.4169 º
vRC = vR0 + a * vR1 + a2 * vR2 = -0.4508 + j 0.5630 pu = 0.72127<128.6852 º
The impedance measured by BC, B-G and C-G units are calculated as
ZBC = (vRB
(vRB-
RB-vRC)/(iRB-
vRC)/(iRB-iRC) = 0.0100 + j 0.37 pu
k = (z0 - z1)/(3*z1)
Figure 2
(10 marks)
Solution
The equivalent circuit of the above system can be drawn as shown in the
figure 2a below;
3 Of 11
j0.05
j0.05
j0.2
j0.25
j0.35
Figure 2a
A T B
j0.2 j0.15
j0.05
IT
j0.05
j0.2
j0.25
c
j0.35
E
1.0 pu
Figure 2b
From the above circuit we can find the fault current and current flowing in
different branches as;
E 1 .0
It = = = − j4
0 .4 × 0 .4 0 .4 × 0 .4
j + 0.05 j + 0.05
0 .8 0 .8
If = It + Ib = -j (2.5 + 4) = -j 6.5 pu
0 .4
Ia = − j × 4 = − j2
0 .8
4 Of 11
Ic = It-Ia = -j(4-2) = -j 2
We have been asked to calculate the impedance seen by the relays at circuit
breaker 1 (location A) and circuit breaker 3 (location C).
Where Va, is the voltage at the point A with respect to ground. This voltage
can be found as
Therefore,
Za = Va/Ia = 0.6 / (-
(-j 2) = j 0.3
0.3 p.u
But from the system diagram we know that the relay at A should have
measured only 0.2+.05=0.25 p.u, but in actual case the relay measures higher
impedance and thus will make it to underreach. This under reaching is due to
the infeed at point “T” from the source B.
Where Vb, is the voltage at the point B with respect to ground. This voltage
can be calculated as
Therefore,
Zc = Vb/Ib = 0.5
0.5 / (-
(-j 2)
2) = j 0.25
0.25 p.u.
Again we know that the relay at C should have measured only 0.15+.05=0.2
p.u, but due to the infeed at T from the source A, the relay measures the fault
impedance as 0.25 p.u., thus causing it to underreach.
3. Determine the three zone settings for the relay Rab in the system shown
in figure 3. The system nominal voltage is 138 kV and the positive
sequence impedances for the various elements are given in the figure3.
Assume that the maximum load at the relay site is 120MVA, and select a
CT ratio accordingly. The available distance relay has zone 1 and zone 2
5 Of 11
settings from 0.2 to 10 ohms and zone 3 settings from 0.5 to 40 ohms in
increments of 0.1 ohm. The angle of maximum torque can be adjusted to
75° or 90°.
Figure 3
(10 marks)
Solution
120 × 10 3
IL = = 502 A
3 × 138
Zone 1 of the relay has to be set to protect 80% of the line, thus
Since the setting range available in the relay for impedance is in steps of
0.1Ω, we will set the zone 1 as 3.3Ω.
6 Of 11
The angle setting available in the relay is either 75° or 90° only. So select the
angle setting as 90°
Zone 2 of the relay has to be set to protect atleast 120% of the protected line.
At the same time this setting should not reach beyond the zone 1 setting of
the shortest downstream line relay, which is the relay on line BD.
So we will set the Z2 to 5.5 Ω, which would cover 100% of the protected line
and 50% of the shortest adjacent line
Zone 3 element of the relay should provide back-up protection to the longest
line from the remote bus, which in this problem is the line BE, with 5+j100 Ω
impedance. Normally it’s a practice to set the Z3 as 110% of the sum of the
protected line plus the longest adjacent line. So we get;
Zone 1 – 3.3 Ω
Zone 2 – 5.5 Ω
Zone 3 – 14.6 Ω
Relay characteristic angle – 90°
7 Of 11
b. the current in the parallel circuit is not available to the relay at
breaker 2
Figure 4
(10 marks)
(10 marks)
Solution
Figure 5
8 Of 11
In order to calculate the fault current simplified sequence network shown in right hand
side of figure 5 is used to drive equivalent sequence impedances as follow:
Zeqpos=ZL1pos*ZL2pos/(ZL1pos+ZL2pos)+Zs1=2.6776 +j 30.4557
Zeqneg=Zeqpos= 2.6776 +j 30.4557
Zeqzero=(ZL1zero*ZL2zero-ZLm0^2)/( ZL1zero+ZL2zero-2*ZLm0)+Zs0=
7.9993 +j 80.0055
IR2a=1.8208<-84.9404
IR2b=0.02885<-88.6731
IR2c=0.02885<-88.6731
VRa= 114.1254<-0.88873
VRb= 135.5626<-121.6159
VRc= 134.8097<121.8131
9 Of 11
a)
For double circuit line having access to second line current, seen impedance is
calculated from following equation:
ZR2seen=VRa/(IR2a+k0*IR2zero+k0m*IR3zero)=4+j40 Ω
b)
if there is no access to second line current, IR3zero should be considered as
zero in above equation. Hence we have:
ZR2seen=VRa/(IR2a+k0*IR2zero) = 4.2545 +j 43.6028 Ω
Solution
10 Of 11
Relay
Characteristic
Line
8sin(80)=7.88
80
70
x
Figure 5a
The relay will operate for a fault resistance upto 4.18/0.347 = 12.04 Ω
(primary) at 80% of its setting
11 Of 11