EFX0089 - ICS Fan Controller Module FTC - I&O Manual
EFX0089 - ICS Fan Controller Module FTC - I&O Manual
www.icsindustries.com.au
[email protected]
309 Settlement Road
Thomastown VIC 3074
Ph 1800 0101 027
VERSION 1.2
ISSUE DATE: 13 MARCH 2018
1. OVERVIEW ............................................................................................................................................................ 3
THIS DOCUMENT DESCRIBES THE ASSEMBLY AND INSTALLATION OF THE PRODUCT SUPPLIED AND IN NO WAY DOES
IT INFER ANY OH&S CONSIDERATION WITH ITS ASSEMBLY OR OPERATION.
IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT THE PRODUCT IS INSTALLED IN A SAFE ENVIRONMENT
AND THAT INSTALLATION IS CARRIED OUT IN A MANNER THAT IS FULLY COMPLIANT WITH ANY WORKPLACE OH&S
REQUIREMENTS.
CONSIDERATION WHEN INSTALLING THE PRODUCT SHOULD BE MADE TO REQUIREMENTS INCLUDING, BUT NOT
LIMITED TO:
1.2. CONNECTIONS
The 24VDC or 48VDC is wired to the DC SUPPLY CONNECTOR using a MOLEX 39-01-2020 connector.
The EC FAN is wired to the FAN CONNECTOR using a MOLEX 39-01-2060 connector.
The Control Interface is wired to the CONTROL CONNECTOR using a MOLEX 39-01-2080 connector.
A REMOTE TEMPERATURE SENSOR (if used) is wired to the REMOTE TEMPERATURE CONNECTOR using a
MOLEX 39-01-2040 connector.
Connect the fan to the FAN CONNECTOR. Note that the fan must be the same voltage as the DC supply, i.e.
use a 48VDC fan with a 48VDC supply.
The RED led will flash slowly when the unit is operating, to indicate the “heartbeat” of the microprocessor,
and to show the system is working.
To perform the FAN TEST function, bridge FAN TEST and COM together. The fan will change to 100% speed.
The speed will return to normal when FAN TEST and COM contacts are open.
To perform the FAN INHIBIT function, bridge FAN INHIBIT and COM together. The fan will stop. The speed will
return to normal when FAN INHIBIT and COM contacts are open.
It is possible to change the fan minimum speed. To do this, bridge both FAN TEST and COM and bridge FAN
INHIBIT and COM for approximately 10 seconds. The RED led will blink fast 4 times and the minimum fan
speed will be set to approximately 10%.
To reset the minimum fan speed to 0%, bridge both FAN TEST and COM and bridge FAN INHIBIT and COM for
approximately 10 seconds. The RED led will blink fast 8 times and the minimum fan speed will be set back to
0%.
In a fan fail scenario the green LED will be OFF and the alarm contacts will be open. This will occur in any of
the following situations when;
1. the measured temperature is below 0 C°;
2. the measured temperature is above 60 C°;
3. the Fan Controller is set for an EXTERNAL temperature sensor, and the sensor is not connected;
4. the fan is running at more than approximately 30% speed, the fan controller checks the EC fan speed
pulses. If these pulses are missing, the alarm is activated, the fan fail output will open and the GREEN led
will go OFF; or
5. there is a power supply failure.
1.6 a) 1.6 b)
SETPOINT DIP SWITCH DIP SWITCH MAX FAN DIP SWITCH DIP SWITCH
EFX0089 POSITION 1 POSITION 2 SPEED POSITION 3 POSITION 4
25 C OFF OFF 100 % OFF OFF
30C OFF ON 75 % OFF ON
35C ON OFF 50 % ON OFF
40C ON ON 33 % ON ON
1.6 c)
SETPOINT DIP SWITCH DIP SWITCH
EFX0089-A POSITION 1 POSITION 2
15 C OFF OFF
20C OFF ON
25C ON OFF
30C ON ON
End of Document