Flat Slab
Flat Slab
2.1. INTRODUCTION:
The term flat slab means a reinforced concrete slab with or without drops, supported generally
without beams, by columns with or without flared column heads. A flat slab may be solid slab or
may have recesses formed on the soffit so that the soffit comprises a series of ribs two directions.
The recesses may be formed by removable or permanent filler blocks.
a) Column strip: Column strip means a design strip having a width of 0.25 I,, but not greater than
0.25 1, on each side of the column centre-line, where I, is the span in the direction moments are
being determined, measured centre to centre of supports and 1, is the -span transverse to 1,,
measured centre to centre of supports.
b) Middle strip: Middle strip means a design strip bounded on each of its opposite sides by the
column strip.
c) Panel: Panel means that part of a slab bounded on-each of its four sides by the centre -line of a
Column or centre-lines of adjacent-spans.
Design of an interior panel of a flat slab of panel size 4.5m X 6m without providing drop and
column head. (IS: 456)
Fig2.1. Panel of a flat slab
Size of column= 4KN/m2
Floor finish=1KN/m2
Height of column is 4m above and below the slab.
Grade M20 Concrete and Fe 415 steel
Mol=264.6KN.m d=175mm
Column strips, width=2250 Middle strips, width=2250
-ve +ve -ve +ve
Mu 0.65x0.75x264.6 0.35x0.60x264.6 0.65x264.6-129 0.35x264.6-55.6
=129KNm =55.6KNm =43KNm =37KNm
Pt% =0.59% =0.235% =0.17% =0.153%
2
Total Ast =2323mm =925.31mm2 =669.38 mm 2
=602.43 mm2
Ast/m =1032.5 mm2 =411.24 mm2 =297.5 mm2 =267.75 mm2
Provided Ast 16 Φ @190 mm 10 Φ @190mm 8 Φ @160mm 8 Φ @160mm
c/c (1058 mm2) c/c (413 mm2) c/c (314 mm2) c/c (314 mm2)
2.3. CONCLUSION:
Drops are important criteria in increasing the shear strength of the slab.
Enhance resistance to punching failure at the junction of concrete slab & column.
By incorporating heads in slab, we are increasing rigidity of slab.
The negative moment’s section shall be designed to resist the larger of the two interior
negative design moments for the span framing into common supports.
According to Indian standard (IS 456) for RCC code has recommended characteristic
strength of concrete as 20, 25, and 30 and above 30 for high strength concrete. For design
purpose strength of concrete is taken as 2/3 of actual strength this is to compensate the
difference between cube strength and actual strength of concrete in structure. After that we
apply factor of safety of 1.5. So in practice Indian standard actually us es 46% of total
concrete characteristic strength. While in International practice is to take 85% of total
strength achieved by test and then apply factor of safety which is same as Indian standard so
in actual they use 57% of total strength.
Prefabricated sections to be integrated into the design for ease of construction.
Chapter-3
DESIGN OF RAIN WATER HARVESTING
3.1. INTRODUCTION:
Rainwater harvesting system, also called rainwater collection system or rainwater catchment
system, technology that collects and stores rainwater for human use. Rainwater harvesting
systems range from simple rain barrels to more elaborate structures with pumps, tanks,
and purification systems. The nonpotable water can be used to irrigate landscaping, flush toilets,
wash cars, or launder clothes, and it can even be purified for human consumption. With water
scarcity a pressing problem for many densely populated regions, rainwater harvesting systems
can supply households and businesses with water for use in dry seasons and lessen the demand
on municipal systems.
Given that rainfall is sporadic and that only a small proportion of global precipitation is easily
available for human use, rainwater harvesting can be an efficient means of capturing
that precious resource. In cities, much of the rain that falls on buildings, roofs, roads, and other
hard landscaping does not percolate into the soil and is instead directed into storm sewers for
disposal. Impermeable surfaces cause urban flooding in many areas and generate contaminated
unusable water that is directed away from potable water resources. During dry months,
local groundwater can be depleted, and many localities struggle to consistently provide enough
potable water to meet demand. Rainwater harvesting for nonpotable functions, such as gardening
and washing clothes, significantly reduces both the demanded amount of the total fresh
water and the strain on stormwater infrastructure. That saving in the demand and supply of
potable fresh water is significant in large cities. Although many localities encourage and even
subsidize rain barrels and other rainwater harvesting systems, some areas, particularly those in
the south-western United States, view rainwater harvesting as a water rights issue and place
restrictions on such collections.
3.2. CASE STUDY
The example of the rainwater tank sizing is based on the proposed construction of 18 storey
office including 3 storey podium and one storey car park for MITI (Ministry of International
Industrial for Malaysia). The rainwater will be collected from the roof of the (office and podium
block) and from the proposed building and directed to the downpipe and rainwater tank located
at ground level of the building (Figure 3.1). Part of the collection consists of the green roof
garden landscapes with the ornamental plant and trees to meet the functional objective of the
building (see Appendix for the detail drawing). The rainwater harvesting system is assumed to be
used as a bathroom cistern flushing for supply up to 1,000 installation of cisterns.
Table 3.6: Frictional Resistance of Draw-off Taps Expressed as Equivalent Pipe Lengths
Discharge Equivalent length of pipe of same
Fitting (BS 1010) rate tap fully diameter as tap(m)
open
(litre/s)
Copper Galvanised steel
15 mm diameter bib 0.20 2.7 4.00
tap
or pillar tap
20 mm diameter bib 0.3 8.50 5.75
tap
or pillar tap
25 mm diameter bib 0.60 20.00 13.00
tap
or pillar tap
The flow rate for 40 units loading is 0.70 liter/s using relationship between design flow rate and
loading unit shown in Figure 7.2 The calculation of head loss due to frictional resistance for
elbow and tee in equivalent pipe length from Table 7.5.
Elbow = 0.7 meter run of pipe
Tee = 1.8 meter run of pipe
The calculation of the effective length of the main pipe serving the appliances in the bathroom.
Assuming the system used 25 mm (O.D) galvanized steel pipe
Actual length of the main pipe = 15 meters
Effective length = actual length + equivalent length
Equivalent length = 4 elbows + 1 tee
Equivalent length = (0.7 × 4) + (1.8 ×1) = 4.6 meters
Effective length = 15 + 4.6= 19.6 meter
The head loss in 25 mm copper pipe due to frictional resistance obtained from Figure 7.4 is0.10.
The head loss due to fitting of stop valve is equivalent to 0.6 (Figure 7.3). Hence, the total head
loss can be calculated as follows:
Total head loss = (19.6 × 0.1) + 0.6
Total head loss = 2.56 meter
The available head is 5 meter, therefore the residual head at appliances distribution point is:
Residual head = 5 – 2.56
= 2.44 meter – the system is adequate.
3.3. RESULT:
4.1. ABSTRACT:
We are living in the 21st century number of complex and irregular structure and designed to
resists the Earthquake, Wind and needs to analyse, design the structure by the various software
like ETABS, STAAD. Pro, TEKLA and to design the structure in this project we used the
ETABS software due to company suggestion and to find stress analysis in slab, shear force for
the beam and area reinforcement for the column and design the foundation depends upon the
reaction and height of the foundation level depends upon site and safe bearing capacity of the
soil due to stability purpose designed the retaining wall in this project.
4.2. INTRODUCTION:
Structural are design to resist earthquake, wind load and stable the structure in the structure
causes loss of peoples and the high raise buildings stiffness and resists the displacement of the
building by proper designs and detail ductile of the building and is able to design the proper
gravity building, the paper deals the analysis E-TABS. ETABS is 3D structural software Analysis
of Building System. Hence revisions are done depend upon the result given by the analysis Also
after proving the credibility of ETABS b materials in ETABS, and the necessary steps taken
below.
4.3. OBJECTIVE:
To perform analysis and design of the structure without any type of failures.
1. To understand the basic principles of structures by using Indian Standard Codes
2. To understand the parameters of the design for beams, columns, slabs and other structural
components.
3. To prepare the 3D model of the structure by using the E-TABS Software for detailed analysis
and design.
The live load was taken as 2 KN/m2 since the analysis and design being done for Residential
building as per IS Code 875 part-2 and as there is no need of giving Dead load in E-TABS which
is an advantageous thing. Wall load for 9 inches is given as 12.42 KN/m2 and for inner walls
6.21 KN/m2. Floor finish was given as 0.8 KN/m2.
4.4.1. Methodology/Procedure:
By using centre line diagram the grid system is given by X and Y co-ordinates and spacing
method of grid system is adopted for convenient of user.
4.5. CONCLUSION:
The structure is design based on the E-TABS, and the theory of LIMIT STATE METHOD which
provide adequate strength, serviceability, and durability besides economy. The displacement,
shear force, bending moment variation has been shown. If any beam fails, the dimensions of
beam and column should be changed and reinforcement detailing can be produced.