Transformer Presentation Vfto

The document contains tables with information about substations including the number of transformers, reactors, and circuit breakers. It also includes graphs showing overvoltage distributions and peak voltages measured on different dates and phases. There are also calculations of electric field stress values for different test positions and insulation conditions. Diagrams illustrate different types of thyristor controlled reactor regulations including linear, reverse, and coarse-fine.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
96 views28 pages

Transformer Presentation Vfto

The document contains tables with information about substations including the number of transformers, reactors, and circuit breakers. It also includes graphs showing overvoltage distributions and peak voltages measured on different dates and phases. There are also calculations of electric field stress values for different test positions and insulation conditions. Diagrams illustrate different types of thyristor controlled reactor regulations including linear, reverse, and coarse-fine.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

Site Sh. R Tr.

Cable CB note
Singimpo S/S 4 1 1 10<
Sungdong S/S 1 1 - -
NamPusan S/S 1 - - -
BukPusan S/S 1 - - -
Jungbu S/S - 1 - -
Uijeongbu S/S 1 - - -
Sinmasan S/S - 1 - - VCB
Sinansung S/S - 1 - - 765kV
Doosan Factory - 3 - - VCB
sum 8 8 1 10<
Enrollado
superior

avería
Enrollado
inferior
400kV

19 veces

7.54kV
TR Línea
Lado de AT
AT

R R R

C C C
Divisor de voltaje
Caja de igualacion de impedancia

Cable de blindaje

Caja blindada OSC


<Sobrevoltaje de encendido>

<Sobrevoltaje de apago>
Reencendido mútilple 520us(1.9kHz)

225us 175us

IEEE C37.015
Peak Voltage on off sum %
1.15p.u.~2p.u. 18 15 33 31%
2p.u.~3p.u. 33 23 56 53%
3p.u.~4p.u. 0 13 13 12%
4p.u. ~ 0 3 3 3%
sum 51 54 105 100%
Peak Voltage A ph B ph C ph sum
1.15p.u.~2p.u. 18 3 12 33
2p.u.~3p.u. 2 10 44 56
3p.u.~4p.u. 0 3 10 13
4p.u. ~ 0 0 3 3
sum 20 16 69 105
Y M D t m on/off max[kV] max[p.u.] Max Phase
2018 1 4 7 3 off 1244 4.41 C

Fuera del rango de medición

1880kV

<Sobrevoltaje de apago>
Calculation using n=150 for Imp Paper an n=13,7 for Oil [kV]

Critical Position Critical Condition (FW) Strength (1.2/50us)* Strength (50% Duration)** Duration(us) VFTO Stress

HV Test 1-2nd Disk Paper: 2.7 mm / Duct: 6 mm 188 234.5 0.05 163(50% duration:50ns)
Section-
Section
XV Test 2-3nd Disk Paper: 1,5 mm / Duct: 5 mm 129 174.9 0.03 82.5(50% duration:30ns)

HV Test 1st Disk Paper: 2.7 mm 126 131.9 0.05 81.5(50% duration:50ns)
Turn-
Turn
XV Test 1st Disk Paper: 1,5 mm 70 73.5 0.03 42.6(50% duration:30ns)
Regulación tipo lineal Regulación tipo reverso

Regulación tipo Gruesa-Fina


* 3 fases 60Hz 362kV 70-160Mvar Tipo Gruesa-Fina VSR * 3 fases 60Hz 362kV 34-60Mvar Tipo Lineal VSR

● Parte activa con CTBC tipo Gruesa-Fina ● Parte activa con CTBC tipo Lineal
● 3 X M I 501-170/DE-18 35 1 tipo aceite, 35 pasos ● 3 X VRG I 1001-170/E-18 18 0 tipo vacío, 18 pasos