Load Sched
Load Sched
1. ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE,
TO THE RULES AND REGULATION OF LOCAL AND NATIONAL AUTHORITIES CONCERNED AND THE REQUIREMENTS
0F LOCAL UTILITY COMPANIES.
2. WIRING METHOD SHALL BE AS FOLLOWS:
a. MAIN SERVICE ENTRANCE ------- THWN THRU EXPOSED & OPEN OVERHEAD
LOAD SCHEDULE b. RACEWAYS FOR POWER --------- THHN/ THWN NO. 12AWG THRU EXPOSED IMC (AFTER PANELBOARD)
NO. OF c. AUXILIARY SYSTEM ---------------- THHN/ THWN NO. 12AWG THRU EXPOSED IMC (AFTER PANELBOARD)
SWITCHES
crkt OUTLETS CB d. RACEWAYS FOR LIGHTING ------ THHN/ THWN NO. 12AWG THRU EXPOSED IMC (AFTER PANELBOARD)
DESCRIPTION V VA A CONDUCTOR CONDUIT
no. 3S RATING 3. MINIMUN SIZE OF WIRE SHALL BE 2.0mm² THHN/ THWN AND 55mm(1/2") NOMINAL DIAMETER RESPECTIVELY
CO/SPO LIGHTING S S2 S3
W
UNLESS OTHERWISE SPECIFIED ON PLANS.
4. NO BRANCH CIRCUIT WIRING IN LIGHTING AND POWER SHALL HAVE A LOAD MORE THAN 80% OF ITS RATING.
1 LIGHTING OUTLET 12 3 230 480 2.0900 15AT 2-2.0mm2 THHN & 1-2.0mm2 1
2 Ø PVC 5. LIGHT CONTROL SWITCHES SHALL BE RATED 20 AMPERES, 230V.
2 LIGHTING OUTLET 19 3 3 230 760 3.3000 15AT 2-2.0mm2 THHN & 1-2.0mm2 1
2 Ø PVC 6. UNLESS OTHERWISE SPECIFIED PULLBOXES OR JUNCTION BOXES SHALL BE PROVIDED
WHEREVER REQUIRED AND NECESSARY, ALTHOUGH SUCH BOXES ARE NOT INDICATED ON PLANS.
1
3 LIGHTING OUTLET 17 2 3 1 1 230 680 2.9600 15AT 2-2.0mm2 THHN & 1-2.0mm2 2 Ø PVC 7. FOR EACH SPARE CIRCUIT PANELBOARD, PROVIDE AN EMPTY CONDUIT 15mm(1/2") DIA, TERMINATING TO
A COVERED SQUARE BOX.
4 CONVENIENCE OUTLET 11 230 1980 8.6100 20AT 2-3.5mm2 THHN & 1-3.5mm2 1
2 Ø PVC
8. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW AND OF APPROVED TYPE FOR BOTH
5 CONVENIENCE OUTLET 8 230 1440 6.2600 20AT 2-3.5mm2 THHN & 1-3.5mm2 1
2 Ø PVC LOCAL AND PURPOSES
2-3.5mm2 THHN & 1-3.5mm2 1 9. ALL METAL FRAMES SHALL BE PROPERLY AND ADEQUATELY GROUNDED, GROUND WIRE SHALL BE
6 SPLIT TYPE ACU 1.5 HP 1 230 2300 10 30AT 2 Ø PVC PROVIDED ON ALL EQUIPMENT FEEDER
7 SPLIT TYPE ACU 1.5 HP 1 230 2300 10 30AT 2-3.5mm2 THHN & 1-3.5mm2 1
2 Ø PVC 10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:
8 SPLIT TYPE ACU 1.5 HP 1 230 2300 10 30AT 2-3.5mm2 THHN & 1-3.5mm2 1
2 Ø PVC a. LIGHT SWITCHES -------------------------------------- 1.40mm FINISH FLOOR LINE (F.F.L.)
2-3.5mm2 THHN & 1-3.5mm2 1 b. RECEPTACLES ---------------------------------------- 0.30mm F.F.L.
9 SPLIT TYPE ACU 1.5 HP 1 230 2300 10 30AT 2 Ø PVC
10 LAUNDRY LOAD 1 230 1500 6.5217 20AT 2-3.5mm2 THHN & 1-3.5mm2 1
Ø PVC
2 - 30mm2 THW & c. TELEPHONE/INTERCOM OUTLES --------------- 0.30mm F.F.L.
2
1 - 8mm2 THW d. PANELBOARDS ----------------------------------------- 1.80mm F.F.L.
11 SPACE e. COUNTER TOP OUTLET ----------------------------- 1.10mm F.F.L.
12 SPACE 11. THERE SHALL BE ONLY ONE SERVICE DROP SECONDARY TO THE PROPOSED BUILDING.
12. SECONDARY SERVICE SHALL BE 230Volts, SINGLE PHASE, 60Hz, FOR POWER & LIGHTING
ALL 20-AMPERES CIRCUIT HOMERUN TO PANELBOARD MORE THAN 30 METERS IN LENGTH
S.E.C. = 1.25*10 + 1*30 + 1.25*((480VA+760VA+680VA+1980VA+1440VA+1500VA)/230) =79.6739A SHALL BE 5.5mm²THHN (#10AWG). UNLESS OTHERWISE SPECIFIED ON PLANS.
Use 30mm2 THW
13. ADDITIONAL MATERIALS SPECIFICATIONS:
S.D.M. = 250% * (10A) + 3*10 + 29.7391A = 84.7391A
a. INTERMEDIATE METALIC CONDUIT (IMC) PIPE - NICHE OR APPROVED EQUIVALENT
Use 100 AT Circuit Breaker b. WIRES AND CABLES --------------------------------------- AMERICAN WIRES & CABLES OR APPROVED EQUIPMENT
c. CIRCUIT BREAKER (BOLT-ON TYPE) --------------- BOLT-ON FOR MAIN BREAKER
AND BOLT-ON FOR ALL PANELBOARDS
OR APPROVED EQUIVALENT
d. WIRING DEVICES -------------------------------------------- AMERICAN STANDARD DEVICES OR APPROVED EQUIVALENT
e. JUNCTION/PULLBOXES (GAUGE 16) ---------------- FUMACO OR FABRICATED ON SITE
LEGEND - ZINC CHROMATE FINISH
14. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE PROPER IDENTIFICATION AND LABELING OR ALL
100 AT MAIN C.B. CIRCUIT BREAKER, EACH PANEL WILL BE PROVIDED WITH A TYPEWRITTEN CIRCUIT DIRECTORY.
COMPACT WALL MOUNTED
15 AT 15 AT 15. THE JOB SHALL BE EXECUTED IN THE MOST THROUGH PROMPT AND WORKMAN LIKE MANNER, EMPLOYING
FLUORESCENT COMPACT L.O. 1 2 L.O. STANDARD TOOLS, EQUIPMENT, METHODS AND GOOD ENGINEERING PRACTICES, THE JOB SHALL BE DONE
FLUORESCENT BULB
BULB COMPLETE IN ALL ASPECTS AS REQUIRED IN PLANS AND SPECIFICATION AND READY FOR OPERATION.
15 AT 20 AT
FLUORESCENT L.O. 3 4 C.O.
16. THE DRAWING AND SPECIFICATIONS ARE INTENDED TO PRESENT A GENERAL LAYOUT AND BROAD OUTLINE
BULB 2
DUPLEX C.O. AND DESCRIPTION OF THE PROJECT AND NOT NECESSARY INDICATE , DESCRIBED ACTUAL LOCATION LEVELS
AND DISTANCES OF EQUIPMENT. THE CONTRACTOR IS HEREBY REQUIRED TO MAKE ADJUSTMENT AT THE
JOBSITE AS LOCATIONS, LEVELS AND DISTANCES ARE GOVERNED BY ACTUAL FIELD CONDITIONS.
C.O. 20 AT 30 AT
1 GANG 1.5 HP ACU 5 6 ACU (1.5 HP)
17. WIRE SHALL BE COLOR CODED:
Sa SWITCH ACU OUTLET LINE 1 ----- RED/ BLUE COMMON ----- WHITE
30 AT 30 AT LINE 2 ----- YELLOW GROUND ------ GREEN
ACU (1.5 HP) 7 8 ACU (1.5 HP)
2 GANG PP
CIRCUIT 18. NO REVISION IN THE DESIGN SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE AND APPROVAL OF
Sab
SWITCH 1 HOMERUN ACU (1.5 HP) 30 AT 20 AT
THE DESIGNER AND THE OWNER, ANY SUCH REVISION DONE WITHOUT THE APPROVAL SHALL CAUSE
9 10 LAUNDRY RESPONSIBILITY OF THE DESIGNER TO CEASED A WHOLE.
3 GANG LAUNDRY 19. ALL EQUIPMENT WIRE, ROYAL CORDS, SPECIAL TYPE PLUGS AND RECEPTACLE AS REQUIRED
Sabc
SWITCH LAUNDRY OUTLET SPACE
SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
11 12 SPACE
3 WAY
20. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULLY LICENSED
SERVICE ENTRANCE
ELECTRICAL ENGINEER AND / OR MASTER ELECTRICIAN
SINGLE PHASE
3Sw
SWITCH 230 VAC 60 HZ
PP
POWER PANEL
BOARD
Approved by: Owner: SCALE
Project Title: Title Sheet: 1:1 Sheet No.
E1
NIKKO C. GUTIERREZ ELECTRICAL NOTES
DRAWN BY:
PROFESSIONAL ELECTRICAL ENGINEER LEGENDS ENGR. PRINCE
TWO STOREY MODERN SCHEDULE OF LOADS AND MRS. ELVIRA C. GUTIERREZ VALIANT
HOUSE COMPUTATIONS BRGY. PULO, SAN ANTONIO, QUEZON ALFORTE
PRC No.: 1903728 SCHEMATIC SINGLE LINE DIAGRAM
ELECTRICAL LAYOUT DATE DRAWN
Revision No.
PTR No.: 31234718 26Sept19
TIN No.: 983742341 0 of 0