Section 3 - Sound Insulation
Section 3 - Sound Insulation
3
Sound insulation
1
3 Sound insulation
At the time of writing, a new laboratory full mechanical ventilation when external
measurement standard for impact sound noise levels are high but do not exceed
from rain on the roof, ISO 140-18[4], is 70 dB LAeq,30min.
under development. In the future this will The School Premises Regulations[6]
allow comparison of the insulation require that:
provided by different roof, window and "All occupied areas in a school building
glazing elements and calculation of the shall have controllable ventilation at a
sound pressure level in the space below minimum rate of 3 litres of fresh air per
the roof. second for each of the maximum number of
When designing against noise from rain persons the area will accommodate.
on the roof, consideration should also be All teaching accommodation, medical
given to any glazing (eg roof lights) in examination or treatment rooms, sick
the roof. Due to the variety of different rooms, sleeping and living accommodation
roof constructions, advice should be shall also be capable of being ventilated at a
sought from an acoustic consultant who minimum rate of 8 litres of fresh air per
will be able to calculate the sound second for each of the usual number of
pressure level in the space due to typical people in those areas when such areas are
rainfall on the specific roof. occupied."
In the case of the latter densely
3.2 External Walls occupied spaces such as classrooms, 8
For masonry walls, such as a 225 mm litres per second per person is the
solid brick wall, a brick/block cavity wall minimum amount of fresh air that should
or a brick-clad timber frame wall, the be provided by a natural or mechanical
sound insulation performance will ventilation system under normal working
normally be such that the windows, conditions, in order to maintain good
ventilators and, in some cases, the roof indoor air quality.
will dictate the overall sound insulation of In order to satisfy the limits for the
the building envelope. indoor ambient noise levels in Table 1.1,
Timber frame walls with lightweight it is necessary to consider the sound
cladding and other lightweight systems of attenuation of the ventilation openings so
construction normally provide a lower that the building envelope can be
standard of sound insulation at low designed with the appropriate overall
frequencies, where road traffic and aircraft sound insulation. In calculations of overall
often produce high levels of noise. This sound insulation the attenuation assumed
can result in a low airborne sound for the ventilation system should be for
insulation against these noise sources normal operating conditions.
unless the cladding system has sufficient The main choices for the natural
low frequency sound insulation. The ventilation of typical classrooms are
airborne sound insulation can be assessed shown in Figure 3.2. Case Studies 7.8
from laboratory measurements carried out and 7.9 describe the recent application of
according to the method of BS EN ISO two of these design solutions in new
140-3:1995[5]. secondary school buildings.
Additional ventilation such as openable
3.3 Ventilation windows or vents may be required to
The method of ventilation as well as the prevent summertime overheating. Under
type and location of ventilation openings these circumstances an increase in internal
will affect the overall sound insulation of noise levels is expected and the levels in
the building envelope. When external Table 1.1 may be exceeded depending on
noise levels are higher than 60 dB the ventilation strategy.
LAeq,30min , simple natural ventilation
solutions may not be appropriate as the 3.3.1 Ventilators
ventilation openings also let in noise. Passive ventilators normally penetrate the
However, it is possible to use acoustically walls, but in some cases they penetrate the
attenuated natural ventilation rather than window frames (eg trickle ventilators) or
2
Sound insulation 3
POSSIBLE SOUND
INSULATION MEASURES
CROSS-VENTILATION
SINGLE-SIDED VENTILATION
2.7 m
STACK VENTILATION
WIND TOWER/BALANCED
FLUE VENTILATION
3
3 Sound insulation
the windows themselves. Often windows insulation with thin glass it is often
are not used as intended as they cause necessary to use two panes separated by
uncomfortable draughts. For this reason, an air (or other gas) filled cavity. In
increased use is being made of purpose theory, the wider the gap between the
designed ventilation systems with or panes, the greater the sound insulation.
without acoustic attenuation. In practice, the width of the cavity in
Many proprietary products are double glazing makes relatively little
designed for the domestic sector and in difference for cavity widths between 6
some cases they do not have large enough mm and 16 mm. Wider cavity widths
openings for classrooms and other large perform significantly better.
rooms found in schools. The acoustic In existing buildings, secondary glazing
performance of any ventilator can be may be installed as an alternative to
assessed with laboratory sound insulation replacing existing single glazing with
test data measured according to BS EN double glazing. The effectiveness of
20140-10:1992[7]. Because of the secondary glazing will be determined by
complexity of the assessment of the the thickness of the glass and the width of
acoustic performance of a ventilator, the air gap between the panes. Another
advice may be needed from a specialist alternative may be to fit a completely new
acoustic consultant. To maintain adequate double-glazed window on the inside of
ventilation, it is essential that the effective the existing window opening, leaving the
area of the ventilator is considered as it original window intact. The use of sound
may be smaller than the free area absorbing reveal linings improves the
(see prEN 13141-1[8]). performance of double-glazed windows,
It is important, particularly in the case but the improvement is mainly in the
of sound-attenuated products, that a good middle to high frequency region, where it
seal is achieved between the penetration has little effect on road traffic and aircraft
through the wall or window and the noise spectra.
ventilator unit. Where through-the-wall To achieve their optimum
products are used, the aperture should be performance, it is essential that the
cut accurately and the gap around the glazing in windows makes an airtight seal
perimeter of the penetrating duct should with its surround, and that opening lights
be packed with sound insulating material have effective seals around the perimeter
prior to application of a continuous, of each frame. Neoprene compression
flexible, airtight seal on both sides. seals will provide a more airtight seal than
In some schools bespoke ventilator brush seals. The framing of the window
designs, such as that shown in Figure 3.3, should also be assembled to achieve an
are needed. For more examples of airtight construction.
ventilator solutions see Case Studies 7.8 It is equally important that an airtight
and 7.9. seal is achieved between the perimeter of
the window frame and the opening into
3.4 External Windows which it is to be fixed. The opening
The airborne sound insulation of should be accurately made to receive the
windows can be assessed from laboratory window, and the perimeter packed with
measurements of the sound reduction sound insulating material prior to
index according to BS EN ISO 140- application of a continuous seal on both
3:1995[5]. When choosing suitable sides.
windows using measured data, care must For partially open single-glazed
be taken to differentiate between windows or double-glazed windows with
measured data for glazing and measured opposite opening panes, the laboratory
data for windows. The reason is that the measured airborne sound insulation is
overall sound insulation performance of a approximately 10-15 dB Rw . This
window is affected by the window frame increases to an Rw of 20-25 dB in the
and the sealing as well as the glazing. open position for a secondary glazing
To achieve the required sound system with partially open ventilation
4
Sound insulation 3
Softwood framing to
extend reveals
Sound-absorbing reveal
Existing inward-opening light, linings to head and sides
movement to be restricted
openings, with the openings staggered on crucial in achieving the potential Figure 3.3: Secondary
glazing producing a
plan or elevation, and with absorbent performance of the door itself. Effective
staggered air flow path
lining of the window reveals (see Figure seals should be provided at the threshold,
3.3). In situ, the degree of attenuation jambs and head of the door frame. As
provided by an open window also with windows, neoprene compression
depends on the spectrum of the noise and seals are more effective than brush seals,
the geometry of the situation. but their effectiveness will be strongly
The spreadsheet of sound reduction influenced by workmanship on site. Brush
indices on the DfES website seals can however be effective and tend to
(www.teachernet.gov.uk/acoustics) gives be more hard wearing than compression
values of Rw for various types of window, seals.
glazing thickness, and air gap. Indications It is also important that an airtight seal
are also given of the sound reduction is achieved between the perimeter of the
indices of open windows. door frame and the opening into which it
is to be fixed. The opening should be
3.5 External Doors accurately made to receive the door frame
For external doors the airborne sound and any gaps around the perimeter packed
insulation is determined by the door set, with insulating material prior to
which is the combination of door and application of a continuous, airtight seal
frame. The quality of the seal achieved on both sides.
around the perimeter of the door is A high level of airborne sound
5
3 Sound insulation
6
Sound insulation 3
be used only if the prevailing external
noise sources are insufficient to generate
an adequate internal level.
It is reasonable, under certain
conditions as specified below, to use the
test results to indicate the likely airborne sound
performance of building envelopes of a
similar construction, exposed to similar
sources. If the conditions are not met
then it is not reasonable to infer the
performance from existing sound
insulation test results and the calculation
procedure should be used.
impact sound
3.9.1 Conditions for similar
constructions
The following features of any untested
construction should be similar to those of
the tested construction:
• type and number of ventilators receiving room via indirect, or 'flanking' Figure 3.4: Sound
paths, see Figure 3.4. transmission paths
• glazing specification, frame between adjacent rooms:
construction and area of windows direct sound paths through
• type and number of doors 3.10 Specification of the airborne the wall and floor and
• external wall construction and area sound insulation between rooms flanking paths through the
• roof construction and area. using Rw surrounding ceiling, wall
Table 1.2 describes the minimum and floor junctions
3.9.2 Conditions for similar sources weighted sound level difference between
Only test results in terms of Dtr,2m,nT , rooms in terms of DnT (Tmf,max),w.
Dat,2m,nT , Drt,2m,nT and Dls,2m,nT However, manufacturers provide
values are applicable, and these should information for individual building
not be used interchangeably. The elements based on laboratory airborne
following features concerning the sound insulation data measured according
prevailing sources of noise should be to BS EN ISO 140-3:1995[5], in terms of
similar to those of the previously tested the sound reduction index, Rw. Figure
construction: 3.5 shows the values of Rw for some
• relative contributions of road traffic, typical building elements.
railway and aircraft noise This section provides some basic
• orientation of the building relative to guidance for the designer on how to use
the main noise source(s) laboratory Rw values to choose a suitable
• ground height of the building relative separating wall or floor for the initial
to the main noise source(s) design. However, specialist advice should
always be sought from an acoustic
SOUND INSULATION BETWEEN consultant early on in the design stage to
ROOMS assess whether the combination of the
This section describes constructions separating and flanking walls is likely to
capable of achieving the different levels of achieve the performance standard in Table
sound insulation specified in Tables 1.2 1.2. An acoustic consultant can use
and 1.4. advanced methods of calculation to
Appendix 1 describes how sound predict the sound insulation (eg Statistical
insulation between adjacent rooms is Energy Analysis or BS EN 12354-
measured and calculated. 1:2000[11]). The correct specification of
In addition to the transmission of flanking walls and floors is of high
direct sound through the wall or floor, importance because incorrect specification
additional sound is transmitted into the of flanking details can lead to reductions in
7
3 Sound insulation
100 mm slab
150 mm with resilient
60 staggered stud hangers
6 mm with 12 mm 100 mm slab
glass plasterboard with rigid
55 200 mm hangers
space
50
Average sound reduction index, dB R w
45 225 mm
115 mm brickwork
6 mm
40 glass concrete slab plastered
6 mm 25 mm 10 mm with 50 mm
glass wall board 100 mm breeze screed
35 space
plastered
one side 115 mm
30 12 mm brickwork
12 mm plasterboard plastered
glass with
25 3 mm 50 x 100 studs 100 mm breeze
glass plastered
20 100 mm breeze both sides
unplastered
15 Solid core
timber door
10 Hollow core
panel door
5
0
1 10 20 50 100 200 400
Weight kg/m 2
8
Sound insulation 3
c. Calculate the final estimate for the
Figure 3.6: The four main
weighted sound reduction index Rw that flanking transmission paths
should be used to select the separating
wall or floor from laboratory test data:
Rw = Rw,est + X dB
Through the junction
with the external walls
3.10.1 Flanking details
A simplified diagram indicating the main
flanking transmission paths is shown in
Figure 3.6. General guidance on flanking
details for both masonry and framed
constructions can be found in Approved
Through the junction
Document E. Specific guidance on with the internal walls
flanking details for products can also
sometimes be found from manufacturers'
data sheets, or by contacting
manufacturers’ technical advisers.
9
3 Sound insulation
10
Sound insulation 3
3.12 Internal walls and partitions leaves, with performance increasing with
the width of the air gap between the
3.12.1 General principles leaves and the physical separation of the
Figure 3.5 shows typical values of the leaves. (Note that for double-leaf
sound reduction index (Rw) for different plasterboard constructions, timber
wall constructions. For comparison the studwork is rarely used to achieve high
performance of other constructions standards of sound insulation because
including doors, glazing and floors is lightweight metal studs provide better
included. mechanical isolation between the leaves.)
The solid line shows the theoretical At low frequencies the performance of
value based purely on the mass law. For plasterboard partitions is limited by the
single leaf elements (eg walls, single mass and stiffness of the partition.
glazing, doors, etc) the mass law states Therefore, masonry walls can provide
that doubling the mass of the element better low frequency sound insulation
will give an increase of 5 to 6 dB in Rw . simply because of their mass. This is not
When constructions provide less sound obvious from the Rw figures, as the Rw
insulation than predicted by the mass law rating system lends more importance to
it is usually because they are not airtight. insulation at medium and high
In general, lightweight double-leaf frequencies rather than low frequencies.
constructions such as double glazing, This is not normally a problem in general
cavity masonry or double-leaf classroom applications where sound
plasterboard partitions provide better insulation is mainly required at speech Figure 3.8: Chart for
sound insulation than the mass law would frequencies. However, it can be important estimating transmission
loss (TL) for a composite
indicate. At medium and high in music rooms and in other cases where
wall consisting of 2
frequencies, double-leaf constructions low frequency sound insulation is elements of differing
benefit from the separation of the two important. transmission losses
15.0
The percentage of the total area of the wall occupied
14.0 by the element with the lower transmission loss, eg a
Area 5% door, and the difference between the higher TL and
13.0
the lower TL, are used to calculate the correction in
12.0
dB which is added to the lower TL to give the TL of
11.0 the whole wall.
10%
10.0 For example: Assume a classroom to corridor wall has
9.0 an Rw of 45 dB and a door in the wall has an Rw of 30
Correction, dB
11
3 Sound insulation
12
Sound insulation 3
Figure 3.9: Walls - sound
reduction index for some
typical wall constructions
13
3 Sound insulation
Figure 3.10: Glazing - sound reduction index for some typical glazing constructions
14
Sound insulation 3
3.12.5 Corridor walls and doors The mass of a door is not the only
The Rw values in Table 1.3 should be variable that ensures good sound
used to specify wall (including any insulation. Good sealing around the frame
glazing) and door constructions between is crucial. Air gaps should be minimised
corridors or stairwells and other spaces. by providing continuous grounds to the
To ensure that the door achieves its frame which are fully sealed to the
potential in terms of its airborne sound masonry opening. There should be a
insulation, it must have good perimeter generous frame rebate and a proper edge
sealing, including the threshold where seal all around the door leaf. Acoustic
practical. seals can eliminate gaps between the door
Note that a lightweight fire door will and the door frame to ensure that the
usually give lower sound insulation than a door achieves its potential in terms of its
heavier, sealed acoustic door. airborne sound insulation.
Greatly improved sound insulation will As a rule of thumb, even a good
be obtained by having a lobby door quality acoustically sealed door in a 55 dB
arrangement between corridors or Rw wall between two classrooms will
stairwells and other spaces. However, this reduce the Rw of the wall so that the
is not often practicable between classrooms DnT(Tmf,max),w is only 30-35 dB. Two
and corridors. Some noise transmission such doors, separated by a door lobby, are
from corridors into classrooms is necessary to maintain the sound
inevitable, but this may not be important insulation of the wall. Figure 3.12 shows
if all lesson changes occur simultaneously. the effect of different doors on the overall
For some types of room, such as music sound insulation of different types of wall.
rooms, studios and halls for music and In a conventional layout with access to
drama performance, lobby doors should classrooms from a corridor, the corridor
generally be used. acts as a lobby between the two classroom
doors.
3.13 Internal doors, glazing, windows
and folding partitions 3.13.2 Lobbies
Internal doors, glazing and windows are Some more specific sound reduction
normally the weakest part of any indices, both single value and octave band
separating wall. Figures 3.10 and 3.11 data, and further references to specific
show the performance of a number of manufacturers’ data are in the sound
different types of door and window. In reduction indices spreadsheet included on
general, rooms which require at least 35 the DfES website
dB Dw should not have doors or single www.teachernet.gov.uk/acoustics. The
glazing in the separating wall or partition. greater the distance between the doors,
the better the sound insulation,
3.13.1 Doors particularly at low frequencies. Maximum
The choice of appropriate doors with benefit from a lobby is associated with
good door seals is critical to maintaining offset door openings as shown in
effective sound reduction, and controlling Figure 3.13(a) and acoustically absorbent
the transfer of sound between spaces. wall and/or ceiling finishes.
Internal doors are often of lightweight A lobby is useful between a
hollow core construction, providing only performance space and a busy entrance
around 15 dB Rw which is about 30 dB hall. Where limitations of space preclude a
less than for a typical masonry wall (see lobby, a double door in a single wall will
Figure 3.5). The sound insulation of an be more effective than a single door; this
existing door can be improved by configuration is illustrated in Figure
increasing its mass (eg by adding two 3.13(b).
layers of 9 mm plywood or steel facings) Inter-connecting doors between two
as long as the frame and hinges can music spaces should be avoided and a
support the additional weight. However, lobby used to provide the necessary
it is often simpler to fit a new door. airborne sound insulation.
15
3 Sound insulation
16
Sound insulation 3
Sound insulation of wall 11
with door (dB) Double doors, ie, one door either side
of a lobby (the diagonal straight line
50 illustrates how the insulation value of
the original partition can only be
maintained at 100% by incorporating a
'very good'
set of double doors with a lobby)
40
Heavy door with edge seal
'good'
Light door with edge seal
30
Any door (gaps round edges)
'poor'
17
3 Sound insulation
Figure 3.14: Existing timber floors - sound reduction index for some typical floor/ceiling constructions
18
Sound insulation 3
Option Construction - timber floors Rw Lnw depth
mm
8 As 7 but mineral wool replaced by 100 mm 55–60 50–55 240–
pugging of mass 80 kg/m2 on lining laid on top of 290
ceiling
19
3 Sound insulation
Figure 3.15: Lightweight 3.14.1 Impact sound insulation In general, impact noise should be
concrete floors - sound Impact noise on floors may arise from: reduced at source through use of soft
reduction index of some floor coverings or floating floors.
typical constructions • foot traffic, particularly in corridors at
break times/lesson changeover Planning and room layout can be used
• percussion rooms to avoid impact noise sources on floors
• areas for dance or movement above noise-sensitive rooms. Soft floor
• loading/unloading areas (eg in coverings and floating floor constructions
kitchens and workshops) and independent ceilings are the most
• machinery. effective means of isolation, and resilient
20
Sound insulation 3
Option Construction - heavyweight concrete floors Rw Lnw depth
mm
21
3 Sound insulation
floor finishes are also appropriate for variety of configurations. The performance
some sources. for both airborne and impact sound
Typical airborne and impact noise improves with the depth of the ceiling
performance are listed for a number of void, with the mass of the ceiling and
constructions in Figures 3.14, 3.15 and with the deflection of the ceiling hangers
3.16. Note that, unlike airborne sound under the mass of the ceiling. Adding a
insulation, impact sound insulation is layer of lightweight acoustically absorbent
measured in terms of an absolute sound glass wool or mineral wool in the ceiling
level, so that a lower figure indicates a void increases the sound insulation,
better standard of insulation. (See typically by 2-3 dB, but there is no point
Appendix 1 for a more detailed explanation in adding more than specified.
of airborne and impact sound insulation.) Performance on site is strongly
dependent on good workmanship to
3.14.2 Voids above suspended avoid air gaps, so careful attention should
ceilings be given to ensuring that joints are close-
Where partitions run up to the underside butted, taped and filled and that all gaps
of lightweight suspended ceilings, the are properly sealed. At the perimeter a
airborne sound insulation will be limited small gap should be left between the
by flanking transmission across the ceiling plasterboard and the walls, and this
void, which will often prevent the should be sealed using non-setting mastic
minimum values for airborne sound to allow a small amount of movement
insulation in Table 1.2 being achieved. without cracking.
Therefore, partitions should either be Penetrations through the ceiling need
continued through the ceiling up to the to be properly detailed to maintain an
soffit, or a plenum barrier should be used. airtight seal while allowing movement,
and services should not be allowed to
3.14.3 Upgrading existing wooden provide a rigid link between the ceiling
floors using suspended plasterboard and the floor above. This can be a
ceilings particular problem with sprinkler pipes. A
Figure 3.14 shows the airborne and problem with these constructions is that
impact noise performance of a standard recessed light fittings, grilles and diffusers
wooden floor with various forms of significantly reduce the sound insulation
suspended plasterboard ceiling. so any services should be surface-
Option 2 is possibly the most widely mounted.
used system of increasing both impact The plasterboard finish is acoustically
and airborne sound insulation, with or reflective whereas in some rooms an
without the original plaster ceiling. In acoustically absorbent ceiling is required,
small rooms good results can be achieved to meet the specifications for room
using timber studs fixed only to the walls, acoustics and reverberation times. One
but large timber sections are needed to solution to this, if there is sufficient
span wider rooms. height, is to suspend a separate
In wider span rooms it is generally lightweight sound absorbing ceiling under
more convenient to suspend the the sound insulating plasterboard ceiling.
plasterboard from the floor joists above, This can be a standard lightweight
fixing through the existing ceiling if this is composite or perforated metal tile system.
retained, using a proprietary suspension These lightweight, acoustically absorbent,
and grid system (option 4). The grid can ceilings add very little to the sound
be hung from simple metal strips or, for insulation but do provide acoustic
higher performance, special flexible absorption. Lights and services can be
ceiling hangers. recessed in the absorbent ceiling.
The major manufacturers of dry-lining The term ‘acoustic ceiling’ generally
systems all provide their own systems for refers to lightweight acoustically
these options, and provide sound absorbent ceiling tile systems, designed to
insulation data and specifications for a provide acoustic absorption. Note that
22
Sound insulation 3
these systems do not always increase the Figure 3.14 shows a number of typical
sound insulation as well. lightweight floating floor constructions
There are, however, some systems and indicative sound insulation figures.
which use relatively heavy ceiling tiles There are many proprietary systems using
which are designed to fit into ceiling grids a wide range of isolating materials and
to provide a reasonably airtight fit. These manufacturers should supply test data in
may consist of dense plasterboard or accordance with ISO 140 measurements.
mineral fibre products, or perforated The isolating layer will typically consist
metal tiles with metal or plasterboard of rubber, neoprene, open-cell or closed-
backing plates. If properly installed and cell foams, mineral fibre or composite
maintained these can provide a useful materials. The isolating layer can be in the
increase in sound insulation as well as form of individual pads, strips or a
acoustic absorption. Manufacturers of continuous layer of material.
these systems can provide both airborne The sound insulation increases with the
and impact sound insulation figures, as deflection of the resilient layer (up to the
well as acoustic absorption coefficients. If limit of elasticity for the material), with
no measured sound insulation data are the mass of the floating layer and with the
provided, it is better to err on the side of depth of the cavity. Adding a layer of
caution and assume that the tile will not lightweight acoustically absorbent glass
provide a significant increase in sound wool or mineral wool in the ceiling void
insulation. increases the sound insulation, typically by
The sound insulation performance 2-3 dB, but there is no point in adding
figures quoted in Figure 3.14 all assume more than specified. In each case the
that the floorboards are in good deflection of the material under the
condition and reasonably airtight, with permanent ‘dead’ load of the floating
thin carpet laid on top. If retaining the layer and the varying ‘live’ loads of
original floorboards it is good practice to occupants and furniture must be
fill in any gaps with glued wooden strips, considered. If the material is too resilient
caulking or mastic, or to lay hardboard on and the floating layer is insufficiently
top, to provide an airtight seal. If not heavy or rigid, the floor will deflect under
retaining the original boards, 18 mm the varying loads as people move about
tongue-and-grooved chipboard can be the room. For this reason it is
used to achieve the same effect, with all advantageous for the floating layer to be
joints and gaps properly sealed, especially as heavy and as stiff as practicable, in
at the perimeters. some cases using ply or fibre-bond board
(for mass) laid on top of the resilient
3.14.4 Upgrading existing wooden layer, with tongue-and-grooved chipboard
floors using platform and ribbed floors on top of this.
The systems discussed in Section 3.14.3 If there are likely to be very heavy local
all maintain the original wooden floor loads in the room (eg pianos) it may be
mounted directly on joists. This has the necessary to increase the stiffness of the
advantage of maintaining the original resilient material, or, in the case of pads,
floor level at the expense of loss of ceiling to space the pads more closely together to
height below. An alternative approach is support these loads.
to provide a floating floor system either Junctions with walls and at doors need
on top of the existing floorboards (a to be designed to maintain an effectively
platform floor) or to remove the existing airtight seal while allowing movement of
floorboards and build a new floor on the floating layer. Manufacturers generally
resilient material placed on top of the provide their own proprietary solutions
floor joists (a ribbed floor). In both cases for this, with or without skirtings.
the increase in both airborne and sound Lightweight floating floors are quite
insulation relies on the mechanical specialist constructions, and achieving the
isolation of the floor from the joists using correct deflection under varying live loads
resilient material. without overloading the resilient material
23
3 Sound insulation
can be difficult. Most materials suffer and without suspended ceilings and
from long term loss of elasticity or ‘creep’ floating floors.
under permanent loads and this should be
taken into account in the design and 3.15 Design and detailing of
selection of materials. The system building elements
manufacturer should normally be Important points to remember when
provided with all of the relevant designing constructions to achieve
information and required to specify a adequate sound insulation are:
system to meet all of the acoustic and • Weak elements (eg doors and glazing,
structural requirements over the expected service penetrations, etc) will reduce the
lifetime of the floor. In difficult cases the effectiveness of the walls in which they are
advice of an acoustics consultant and/or located.
structural engineer should be sought. • Impact sound will travel with little
reduction through a continuous member
3.14.5 Concrete floors such as a steel beam or servicing pipe.
In general concrete floors provide much • Partitions between sensitive spaces
greater airborne sound insulation than should normally continue beyond the
wooden floors by virtue of their greater ceiling up to the structural soffit or roof
mass. There are, however, considerable layer, to prevent noise passing over the
variations in performance between dense top of the partition above the ceiling or
poured concrete floors and comparatively through a loft space.
lightweight precast concrete plank floors. • Openings in walls caused by essential
Impact sound transmission can be a services passing through should be
problem even in heavy concrete floors acoustically sealed. Pipework passing
because of the lack of damping in between noise sensitive spaces should be
concrete, and a soft or resilient floor appropriately boxed-in (see Approved
covering is generally required. This may Document E[1]).
simply be carpet on suitable underlay. Figure 3.17 shows how possible
Figures 3.15 and 3.16 show typical transmission paths through the structure
airborne sound insulation and impact of a building can be prevented.
sound transmission for a number of
typical concrete floor constructions, with
24
Sound insulation 3
References
[1] Approved Document E - Resistance to the [9] BS EN 12354-3:2000 Building Acoustics -
passage of sound. Published by the Stationery Estimation of acoustic performance in buildings
Office, 2002 ISBN 001 753 6433 from the performance of elements. Part 3.
Airborne sound insulation against outdoor
[2] Sound Control for Homes (BRE report 238, sound.
CIRIA report 127 available from CRC Ltd),
BRE & CIRIA, 1993 [10] BS EN ISO 140-5: 1998 Measurement of
BRE ISBN 0 85125 559 0 sound insulation in buildings and of building
CIRIA ISBN 0 86017 362 3 elements. Part 5. Field measurements of
CIRIA ISBN 0305 408 X airborne sound insulation of façade elements
and facades.
[3] J. McLoughlin, D.J. Saunders, R.D. Ford.
Noise generated by simulated rainfall on [11] BS EN 12354–1:2000 Building Acoustics.
profiled steel roof structures. Applied Acoustics Estimating of acoustic performance in building
42 (1994) 239-255 from the performance of elements. Part 1.
Airborne sound insulation between rooms.
[4] ISO 140-18 Acoustics Measurement of
sound insulation in buildings and of building [12] BS 476 Fire tests on building materials
elements - Part 18: Laboratory measurement and structures.
of sound generated by rainfall on building
elements, forthcoming standard. [13] BS EN ISO 140-6: 1998, Acoustics -
Measurement of sound insulation in buildings
[5] BS EN ISO 140-3: 1995 Measurement of and of building elements. Part 6. Laboratory
sound insulation in buildings and of building measurement of impact sound insulation of
elements. Part 3. Laboratory measurement of floors.
airborne sound insulation of building elements.
[14] BS EN 12354-2: 2000 Building Acoustics.
[6] The Education (School Premises) Estimating of acoustic performance in building
Regulations 1999. (Statutory Instrument 1999 from the performance of elements. Part 2.
No 2, EDUCATION, ENGLAND & WALES ). The Impact sound insulation between rooms.
Stationery Offiice, 1999. ISBN 0 11 080331 0
£3.00 and on website [15] BS EN ISO 140-8: 1998 Acoustics.
www.legislation.hmso.gov.uk/si/si1999/19990 Measurements of sound insulation in buildings
002.htm and of building elements. Part 8. Laboratory
measurements of the reduction of transmitted
[7] BS EN 20140-10: 1992 Acoustics, impact noise by floor coverings on a
Measurement of sound insulation in buildings heavyweight standard floor.
and of building elements. Part 10. Laboratory
measurement of airborne sound insulation of [16] BS EN ISO 717-2: 1997 Acoustics - Rating
small building elements. of sound insulation in buildings and of building
elements. Part 2. Impact sound insulation.
[8] BS 98/704582 DC. Ventilation for
buildings. Performance testing of
components/products for
residential ventilation. Part 1. Externally and
internally mounted air transfer devices. Draft
for Public Comment (prEN 13141-1 Current
Euronorm under approval).
25