Transformer Test Report

1) The document reports test results for a 6000 KVA, 11000/3450 volt transformer before and after overhaul. 2) Key tests included voltage ratio, magnetic balance, insulation resistance, winding resistance and tan delta measurements. 3) Test results showed improvements in insulation resistance and BD value after overhaul, with all other parameters remaining satisfactory.

Uploaded by

Suraj Gangwar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4K views6 pages

Transformer Test Report

1) The document reports test results for a 6000 KVA, 11000/3450 volt transformer before and after overhaul. 2) Key tests included voltage ratio, magnetic balance, insulation resistance, winding resistance and tan delta measurements. 3) Test results showed improvements in insulation resistance and BD value after overhaul, with all other parameters remaining satisfactory.

Uploaded by

Suraj Gangwar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

TMM-2A TEST REPORT

Transformer Nameplate
Volts (No Load) Amperes Phases
KVA
HV LV HV LV HV
6000 11000 3450 314.9 1004.1 3

1. Vector Group Dyn11 Identification

R
415 V
Y
415 V
B

H.V. Side L.V. Side

Vector Group Dyn11 Identification Test Details (On Tap Position 3)


Dyn11 Conditions Before T/F Overhauling
RY = Rn + nY 416 = 75 + 341
Yb = Yy 310 = 310
Bb < By 311 < 438

Voltage Ratio Test


Before T/F Overhauling
HV Side LV Side
Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
1 416 418 417 71.9 72.1
2 417 418 417 73.8 74
3 416 418 417 75.7 76
4 416 418 417 77 78
5 416 418 417 79.9 80

Magnetic Balance Te
Before T/F Overhauling
HV Side LV Side
Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
3 417 338.4 79.6 75.7 61
3 242 418 177 43 76
3 95 322 417 17 58

Insulation Resistance & Polarisation Index (Mete


Before T/F Overhauling
Components IR (1 Minute) IR (10 Minutes) PI (10 Minutes)
LV – E (1 KV) 688 MΩ 807 MΩ 1.17
HV – E (5 KV) 994 MΩ 1.08 GΩ 1.08

Page 1
TMM-2A TEST REPORT
HV – LV (5 KV) 544 MΩ 550 MΩ 1.01

Winding Resistance Meas


Before T/F Overhauling (With Analog Motor Checker at Knob Position 4)
Text HV Side LV Side
Actual Value (%) 20 20 20 18 18
Calculated Value(Ω) 0.40 0.40 0.40 0.36 0.36

BD Value
Before T/F Overhauling(KV) - Old Oil After T/F Overhauling(KV) – New Oil
19 60

Tan Delta Testing (After T/F O


HV Side
Mode Voltage (KV) Capacitane (pf) Tan Delta (%)
UST 2 6095 5.505
UST 6 6097 5.505
GST 2 8223 4.639
GST 6 8223 4.638
GST-G 2 2126 2.165
GST-G 6 2126 2.163

Note – Magnetising current test is not carried out before overhauling.

Prepared By: Mr. Suraj Pal


Checked By:

Page 2
TMM-2A TEST REPORT
Transformer Nameplate Details
Phases Maker's Type of Frequency Impedance Connection
LV Diagram No. serial no. Cooling (Hz) Volts Symbols
3 RDM1087 M1087/1 ONAN 50 7.09 Dyn11

ctor Group Dyn11 Identification Test


R R,r

r r 30o
y
n
b y
n
b
y

b
B Y B Y

(On Tap Position 3)


After T/F Overhauling
419 = 76 + 343
311 = 312
312 < 340

Voltage Ratio Test


After T/F Overhauling
LV Side HV Side LV Side
Voltage(bn) Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
72 1 418 419 418 72 72
73.8 2 418 419 418 74 74
75.8 3 418 419 418 76 76
77.9 4 419 420 419 78 78
79.9 5 419 420 419 80 80

Magnetic Balance Test


After T/F Overhauling
LV Side HV Side LV Side
Voltage(bn) Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
14 3 418 346 73 76 62
32 3 240 419 179 43 76
75.9 3 86 332 418 15 60

tance & Polarisation Index (Meter Serial No. - METMD1-10-002)


After T/F Overhauling
PI (10 Minutes) Components IR (1 Minute) IR (10 Minutes) PI (10 Minutes)
1.17 LV – E (1 KV) 835 MΩ 930 MΩ 1.11
1.08 HV – E (5 KV) 951 MΩ 1.01 GΩ 1.06

Page 3
TMM-2A TEST REPORT
1.01 HV – LV (5 KV) 391 MΩ 397 MΩ 1.01

Winding Resistance Measurement


ition 4) After T/F Overhauling (With Vendor's Resistance Meter)
LV Side LV Side HV Side
17 rn (mΩ) yn (mΩ) bn (mΩ) Tap Position RY (mΩ) YB (mΩ)
0.34 5.11 5.13 5.27 1 123.1 122.0
2 119.9 118.9
3 116.7 115.8
4 114.3 113.7
5 111.5 110.3

Magnetising Current Test ( After T/F Overhauling )


HV Side (LV Open) LV Side (HV Open)
Parameter R Y B Parameter r y
Current (mA) 44 30 32 Current (A) 0.61 0.66

Tan Delta Testing (After T/F Overhauling)


LV Side
Tan Delta (%) Mode Voltage (KV) Capacitane (pf) Tan Delta (%)
5.505 UST 1 6100 5.508
5.505 UST 2 6100 5.508
4.639 GST 1 9961 4.689
4.638 GST 2 9960 4.690
2.165 GST-G 1 3860 3.395
2.163 GST-G 2 3860 3.397

Page 4
TMM-2A TEST REPORT

Year of
Manuf.
1993

LV Side
Voltage(bn)
72
74
76
78
80

LV Side
Voltage(bn)
13
32
76

PI (10 Minutes)
1.11
1.06

Page 5
TMM-2A TEST REPORT
1.01

er)
de
BR (mΩ)
123.0
119.8
116.7
113.8
110.9

V Open)
b
0.67

Tan Delta (%)


5.508
5.508
4.689
4.690
3.395
3.397

Page 6