TMM-2A TEST REPORT
Transformer Nameplate
Volts (No Load) Amperes Phases
KVA
HV LV HV LV HV
6000 11000 3450 314.9 1004.1 3
1. Vector Group Dyn11 Identification
R
415 V
Y
415 V
B
H.V. Side L.V. Side
Vector Group Dyn11 Identification Test Details (On Tap Position 3)
Dyn11 Conditions Before T/F Overhauling
RY = Rn + nY 416 = 75 + 341
Yb = Yy 310 = 310
Bb < By 311 < 438
Voltage Ratio Test
Before T/F Overhauling
HV Side LV Side
Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
1 416 418 417 71.9 72.1
2 417 418 417 73.8 74
3 416 418 417 75.7 76
4 416 418 417 77 78
5 416 418 417 79.9 80
Magnetic Balance Te
Before T/F Overhauling
HV Side LV Side
Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
3 417 338.4 79.6 75.7 61
3 242 418 177 43 76
3 95 322 417 17 58
Insulation Resistance & Polarisation Index (Mete
Before T/F Overhauling
Components IR (1 Minute) IR (10 Minutes) PI (10 Minutes)
LV – E (1 KV) 688 MΩ 807 MΩ 1.17
HV – E (5 KV) 994 MΩ 1.08 GΩ 1.08
Page 1
TMM-2A TEST REPORT
HV – LV (5 KV) 544 MΩ 550 MΩ 1.01
Winding Resistance Meas
Before T/F Overhauling (With Analog Motor Checker at Knob Position 4)
Text HV Side LV Side
Actual Value (%) 20 20 20 18 18
Calculated Value(Ω) 0.40 0.40 0.40 0.36 0.36
BD Value
Before T/F Overhauling(KV) - Old Oil After T/F Overhauling(KV) – New Oil
19 60
Tan Delta Testing (After T/F O
HV Side
Mode Voltage (KV) Capacitane (pf) Tan Delta (%)
UST 2 6095 5.505
UST 6 6097 5.505
GST 2 8223 4.639
GST 6 8223 4.638
GST-G 2 2126 2.165
GST-G 6 2126 2.163
Note – Magnetising current test is not carried out before overhauling.
Prepared By: Mr. Suraj Pal
Checked By:
Page 2
TMM-2A TEST REPORT
Transformer Nameplate Details
Phases Maker's Type of Frequency Impedance Connection
LV Diagram No. serial no. Cooling (Hz) Volts Symbols
3 RDM1087 M1087/1 ONAN 50 7.09 Dyn11
ctor Group Dyn11 Identification Test
R R,r
r r 30o
y
n
b y
n
b
y
b
B Y B Y
(On Tap Position 3)
After T/F Overhauling
419 = 76 + 343
311 = 312
312 < 340
Voltage Ratio Test
After T/F Overhauling
LV Side HV Side LV Side
Voltage(bn) Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
72 1 418 419 418 72 72
73.8 2 418 419 418 74 74
75.8 3 418 419 418 76 76
77.9 4 419 420 419 78 78
79.9 5 419 420 419 80 80
Magnetic Balance Test
After T/F Overhauling
LV Side HV Side LV Side
Voltage(bn) Tap Position Voltage(RY) Voltage(YB) Voltage(BR) Voltage(rn) Voltage(yn)
14 3 418 346 73 76 62
32 3 240 419 179 43 76
75.9 3 86 332 418 15 60
tance & Polarisation Index (Meter Serial No. - METMD1-10-002)
After T/F Overhauling
PI (10 Minutes) Components IR (1 Minute) IR (10 Minutes) PI (10 Minutes)
1.17 LV – E (1 KV) 835 MΩ 930 MΩ 1.11
1.08 HV – E (5 KV) 951 MΩ 1.01 GΩ 1.06
Page 3
TMM-2A TEST REPORT
1.01 HV – LV (5 KV) 391 MΩ 397 MΩ 1.01
Winding Resistance Measurement
ition 4) After T/F Overhauling (With Vendor's Resistance Meter)
LV Side LV Side HV Side
17 rn (mΩ) yn (mΩ) bn (mΩ) Tap Position RY (mΩ) YB (mΩ)
0.34 5.11 5.13 5.27 1 123.1 122.0
2 119.9 118.9
3 116.7 115.8
4 114.3 113.7
5 111.5 110.3
Magnetising Current Test ( After T/F Overhauling )
HV Side (LV Open) LV Side (HV Open)
Parameter R Y B Parameter r y
Current (mA) 44 30 32 Current (A) 0.61 0.66
Tan Delta Testing (After T/F Overhauling)
LV Side
Tan Delta (%) Mode Voltage (KV) Capacitane (pf) Tan Delta (%)
5.505 UST 1 6100 5.508
5.505 UST 2 6100 5.508
4.639 GST 1 9961 4.689
4.638 GST 2 9960 4.690
2.165 GST-G 1 3860 3.395
2.163 GST-G 2 3860 3.397
Page 4
TMM-2A TEST REPORT
Year of
Manuf.
1993
LV Side
Voltage(bn)
72
74
76
78
80
LV Side
Voltage(bn)
13
32
76
PI (10 Minutes)
1.11
1.06
Page 5
TMM-2A TEST REPORT
1.01
er)
de
BR (mΩ)
123.0
119.8
116.7
113.8
110.9
V Open)
b
0.67
Tan Delta (%)
5.508
5.508
4.689
4.690
3.395
3.397
Page 6