(110W ÷ 230V) × 125% CIRCUIT 6 CONVENIENCE OUTLET
COMPUTATION OF LOADS
AMPERE PER CIRCUIT = 0.6A 1 RANGE× 8000W = 8000W
CIRCUIT 1 LIGHTING OUTLET
WIRE: USE NO. 14 AWG THW WATTS PER CIRCUIT = 8000W
3 PINLIGHTS × 15W = 45W
PIPE: USE 13 MM ǿ CP (8000W ÷ 230V) × 125%
5 LIGHT BULBS × 100W = 500W
AMPERE PER CIRCUIT = 43.49A
WATTS PER CIRCUIT = 545W
CIRCUIT 4 CONVENIENCE OUTLET WIRE: USE NO. 8 AWG THW
(545W ÷ 230V) × 125%
6 THREE GANG CO × 180W = 1080W PIPE: USE 13 MM ǿ CP
AMPERE PER CIRCUIT = 2.96A
WATTS PER CIRCUIT = 1080W
WIRE: USE NO. 14 AWG THW
(1080W ÷ 230V) × 125% CIRCUIT 7 CONVENIENCE OUTLET
PIPE: USE 13 MM ǿ CP
AMPERE PER CIRCUIT = 5.87A 4 TV (19” COLOUR) × 100W = 400W
WIRE: USE NO. 12 AWG THW 2 CEILING FAN × 100W = 200W
CIRCUIT 2 LIGHTING OUTLET
PIPE: USE 13 MM ǿ CP WATTS PER CIRCUIT = 600W
8 LIGHT BULBS × 100W = 800W
(600W ÷ 230V) × 125%
WATTS PER CIRCUIT = 800W
CIRCUIT 5 CONVENIENCE OUTLET AMPERE PER CIRCUIT = 3.26A
(800W ÷ 230V) × 125%
4 THREE GANG CO × 180W = 720W WIRE: USE NO. 12 AWG THW
AMPERE PER CIRCUIT = 4.35A
2 TWO GANG CO × 180W = 360W PIPE: USE 13 MM ǿ CP
WIRE: USE NO. 14 AWG THW
WATTS PER CIRCUIT = 1080W
PIPE: USE 13 MM ǿ CP
(1080W ÷ 230V) × 125% CIRCUIT 8 CONVENIENCE OUTLET
AMPERE PER CIRCUIT = 5.87A
CIRCUIT 3 CONVENIENCE OUTLET
WIRE: USE NO. 12 AWG THW 1 REFRIGERATOR× 700W = 700W
2 PINLIGHTS × 15W = 30W
PIPE: USE 13 MM ǿ CP WATTS PER CIRCUIT = 700W
4 WALL LAMP × 20W = 80W
(700W ÷ 230V) × 250%
WATTS PER CIRCUIT = 110W
AMPERE PER CIRCUIT = 7.61A
WIRE: USE NO. 12 AWG THW WATTS PER CIRCUIT = 1119W 16842𝑊 + (25% 𝑂𝐹 1119)
𝐼=
230𝑉
PIPE: USE 13 MM ǿ CP (1119W ÷ 230V) × 250%
𝐼 = 74.44𝐴
AMPERE PER CIRCUIT = 12.16A
CIRCUIT PROTECTION – 85A
WIRE: USE NO. 12 AWG THW
SIZE OF WIRE – 22mm2 THW COPPER WIRE
CIRCUIT 9 CONVENIENCE OUTLET PIPE: USE 13 MM ǿ CP
1 HOME AIR CONDITION× 1119W = 1119W
WATTS PER CIRCUIT = 1119W CIRCUIT 12 CONVENIENCE OUTLET
(1119W ÷ 230V) × 250% 1 HOME AIR CONDITION× 1119W = 1119W
AMPERE PER CIRCUIT = 12.16A WATTS PER CIRCUIT = 1119W
WIRE: USE NO. 12 AWG THW (1119W ÷ 230V) × 250%
PIPE: USE 13 MM ǿ CP AMPERE PER CIRCUIT = 12.16A
WIRE: USE NO. 12 AWG THW
PIPE: USE 13 MM ǿ CP
CIRCUIT 10 CONVENIENCE OUTLET
1 HOME AIR CONDITION× 1119W = 1119W SOLVING FOR MAIN BREAKER
WATTS PER CIRCUIT = 1119W FIRST 10000W AT 100% DEMAND FACTOR =10000W
(1119W ÷ 230V) × 250% SUBTRACT 15915W – 10000W=5915W
AMPERE PER CIRCUIT = 12.16A MULTIPLY 5915W × 40%=2366W
WIRE: USE NO. 12 AWG THW AIRCONDITIONING UNIT AT 100% DEMAND FACTOR
PIPE: USE 13 MM ǿ CP 4 UNITS AT 1119W = 4476W
TOTAL WATTS = 16842W
CIRCUIT 11 CONVENIENCE OUTLET TOTAL CONNECTED LOAD PLUS 25% OF THE
LARGEST MOTOR
1 HOME AIR CONDITION× 1119W = 1119W