0% found this document useful (0 votes)
50 views

Y2019-20 Tutorial 8

This document provides instructions for calculating fault currents using sequence components and the direct approach for various single-line to ground, line-to-line, and three-phase faults on 4-bus distribution systems. Impedance values and system configurations are given for each example case. Fault currents and post-fault voltages are to be calculated for faults at different locations in the systems.

Uploaded by

Souvik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views

Y2019-20 Tutorial 8

This document provides instructions for calculating fault currents using sequence components and the direct approach for various single-line to ground, line-to-line, and three-phase faults on 4-bus distribution systems. Impedance values and system configurations are given for each example case. Fault currents and post-fault voltages are to be calculated for faults at different locations in the systems.

Uploaded by

Souvik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Tutorial-8: Short-Circuit Analysis

1. Consider a 3-phase, 11-kV network. The equivalent positive-sequence, negative-sequence, and zero-
sequence impedances till the fault point on the network are as follows:
Z1  Z 2  0.54  j1.56 
Z 0  0.06  j1.17 
Find the magnitudes of fault currents for the following faults using sequence components.
(a) Three-phase fault
(b) LG fault
(c) LL fault
(d) LLG fault

2. A 22 kV upstream network with a short-circuit rating of 300 MVA and R/X of 0.3 is connected to an 800
kVA, 22/0.4 kV, delta-wye transformer as shown the figure. The star neutral point is directly connected to
ground. The transformer resistance RT and reactance XT are 2.68 mΩ and 9.07 mΩ, respectively. The
transformer feeds a load via an aluminum cable of 100 m length with resistance (RC) and reactance (XC) are
0.045Ω and 0.008Ω, respectively. Find the magnitudes of fault currents for the fault at load point for the
following faults using sequence components. Z0=Z1=Z2
(a) Three-phase fault
(b) LG fault
(c) LL fault
(d) LLG fault
Delta/Wye-
grounded

100m Cable
22 kV, 0.045 + j0.08
800 kVA,
SSC = 300 MVA
22/0.4 kV,
VSC = 4.5%
3. Consider a 4-bus distribution system shown in the following figure.
2 km 1 km 1 km

1a 2a 3a 4a
1b
2b 3b 4b
The feeder consists of two phases a and b. The impedance matrix is of the feeder is
0.21  j 0.42 0.05  j 0.21
Z ab     km
0.05  j 0.21 0.21  j 0.42
Find the magnitudes of fault currents for the following faults using the direct approach. Assume fault
impedance Zf is 0 Ω. System voltage is 11.0 kV.
(a) LG fault at Bus 4b. Also calculate post fault voltage at bus 3b.
(b) LL fault at between Bus 3a and 3b. Also calculate post fault voltages at bus 2a and 2b.
(c) LLG fault at Buses 2a and 2b
4. A 11 kV, 4-bus distribution system is shown in the following figure. The impedance (Ω/km) matrices of
three-phase, two-phase, and single-phase sections are represented as Zabc, Zab, and Zb respectively.
3

1 km 4
1 2 2 km
1 km
a

b
c
0.24  j 0.67 0.05  j 0.32 0.05  j 0.27 
Z abc   0.05  j 0.32 0.24  j 0.67 0.05  j 0.32   km
 0.05  j 0.27 0.05  j 0.32 0.24  j 0.67 
0.24  j 0.67 0.05  j 0.32 
Z ab    km
 0.05  j 0.32 0.24  j 0.67 
Z b  0.24  j 0.67  km
Find the magnitudes of fault currents for the following faults using the direct approach. Assume fault
impedance Zf is 0 Ω.
(a) LG fault at Bus 4b. Also calculate post fault voltage at bus 3a and 3b
(b) LL fault at Bus 2 between phases b and c.
(c) LLG fault at Buses 3a and 3b. Also calculate post fault voltages at bus 2a, 2b and 2c.
(d) If a line is connected between buses 2b to 4b with impedance 0.72 + j 2.01 Ω, find the fault current for
LG fault at Bus 4b using a direct approach based for the weakly meshed system.

You might also like