0% found this document useful (0 votes)
109 views

Power & Motor Control Center

The document describes a power and motor control center with the following specifications: - 3 phase, 415V, 1600A busbar with 2 incomers rated 1600A and 630A with numerical relays - Various motor feeders ranging from 110kW to 0.55kW totaling 43 feeders - Non-motor feeders ranging from 16A to 315A MCCB totaling 14 feeders - The switchboard will have protection devices, metering, and interfaces for PLC control and is suitable for top cable entry and bottom cable exit.

Uploaded by

Sandeep Kr Arya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
109 views

Power & Motor Control Center

The document describes a power and motor control center with the following specifications: - 3 phase, 415V, 1600A busbar with 2 incomers rated 1600A and 630A with numerical relays - Various motor feeders ranging from 110kW to 0.55kW totaling 43 feeders - Non-motor feeders ranging from 16A to 315A MCCB totaling 14 feeders - The switchboard will have protection devices, metering, and interfaces for PLC control and is suitable for top cable entry and bottom cable exit.

Uploaded by

Sandeep Kr Arya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

S.NO.

DESCRIPTION UNIT

1 POWER & MOTOR CONTROL CENTER

3 phase, 4 wire, 415V ± 6%, 50Hz ± 3%, 1600A, 50kA for 1 sec Al busbar Single front, fully
draw out type MV switchboard with following details -
i) 1 No. 1600A ACB incomer with numerical multifunction relay.
ii) 1 No. 630A ACB incomer with numerical multifunction relay.
iii) 1600A ACB buscoupler with Auto changeover.
iv) Outgoing Motor Feeders
110 kW motor feeder : 2 Nos.
75 kW motor feeder : 3 Nos
30 kW motor feeder : 7 Nos
22 kW motor feeder : 3 Nos.
15 kW motor feeder : 3 Nos
11 kW motor feeder : 8 Nos.
9.3 kW motor feeder : 5 Nos.
7.5 kW motor feeder : 2 Nos.
5.5 kW motor feeder : 11 Nos.
3.7 kW motor feeder : 15 Nos.
2.2 kW motor feeder : 3 Nos. No.
1.5 kW motor feeder : 3 Nos.
.55 kW motor feeder : 2 Nos.
v) Outgoing Non-motor Feeders
16A MCCB feeder : 3 Nos.
32A MCCB feeder : 4 Nos.
63A MCCB feeder : 5 Nos.
250A MCCB feeder : 4 Nos.
315A MCCB feeder : 2 Nos.
Motor feeders shall consist of breakers with contactor and associated protective relays. Non
motor feeders shall be complete with required protection and control devices. Switchboard
shall be complete with protection relays, CT, PT, control, metering and interlock devices
required for successful functioning. Switchboard Incomers and 55 kW and above feeders
shall have facilities to interface with PLC.
Switchboard shall be suitable for top entry incoming busduct connections. Outgoing feeders
shall have bottom entry for cables.
TOTAL SUPPLY
REMARKS
QUANTITY UNIT RATE TOTAL RATE