Unidrive-M Frame Size 3 EMC Data Sheet
Unidrive-M Frame Size 3 EMC Data Sheet
Unidrive-M
series Frame
size 3
All models
Variable Speed AC
drive for induction
and permanent
magnet motors
Unidrive-M Frame size 3 EMC Data Sheet
Safety Warnings
NOTE:
A Note contains information which helps to ensure correct operation of the product.
The information given in this data sheet is derived from tests and calculations on sample products. It is
provided to assist in the correct application of the product, and is believed to correctly reflect the behaviour of
the product when operated in accordance with the instructions. The provision of this data does not form part
of any contract or undertaking. Where a statement of conformity is made with a specific standard, the
manufacturer takes all reasonable measures to ensure that its products are in conformance. Where specific
values are given these are subject to normal engineering variations between samples of the same product.
They may also be affected by the operating environment and details of the installation arrangement.
The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or
incorrect installation of the equipment.
The contents of this data sheet are believed to be correct at the time of printing. The manufacturer reserves
the right to change the specification of the product or its performance, or the contents of the data sheet,
without notice.
Copyright
All rights reserved. No parts of this data sheet may be reproduced or transmitted in any form by any means,
electrical or mechanical including photocopying, recording or by an information storage or retrieval system,
without permission in writing from the publisher
Contents
1. Products ...................................................................................................................................................... 4
2. Immunity ..................................................................................................................................................... 5
3. Emission ..................................................................................................................................................... 7
3.1 General ............................................................................................................................................... 7
3.2 Low Frequency Emissions .................................................................................................................. 8
3.3 Conducted Emissions .......................................................................................................................14
3.4 Radiated Emissions ..........................................................................................................................17
4. Installation and Wiring Guidelines ............................................................................................................20
Where:
Mxxx denotes M600, M700, M701, M702, M708 or M709
HSxx denotes HS70, HS71 or HS72.
Exxx denotes E200 or E300
The drive rated power e.g. 0.75/ 1.1 denotes Heavy Duty/ Normal Duty.
Products with the same rated voltage and power are identical in construction. The displays, user menus
and firmware are optimised for particular applications.
Notes:
1 Applies to ports where connections may exceed 30 m length. Special provisions may be required in
some cases – see additional information below.
2 Limited by test equipment capability
Unless stated otherwise, immunity is achieved without any additional measures such as filters or
suppressors. To ensure correct operation, the wiring guidelines specified in the Power Installation
Guide must be followed. All inductive components such as relays, contactors, electromagnetic brakes
must be fitted with appropriate suppression.
These circuits meet the requirements of IEC 61000-6-2 (1 kV surge) provided that the 0 V connection
is not earthed. In general the circuits cannot withstand the surge directly between the control lines and
the 0 V connection.
The surge test simulates the effect of a lightning strike, or a severe electrical fault, where high
transient voltages may exist between different points in the grounding system. This is a particular risk
where the circuits are routed outside a building, or if the grounding system in a building is not well
bonded.
In applications where control circuits are exposed to high-energy voltage surges, some special
measures are required to prevent malfunction or damage. In general, circuits that are routed outside
the building where the drive is located, or are longer than 30 m need additional protection. One of the
following techniques should be used:
1. Galvanic isolation, Do not connect the control 0 V terminal to ground. Avoid loops in the control
wiring, i.e. ensure every control wire is routed next to its associated return (0 V) wire.
2. Screened cable. The cable screen may be connected to ground at both ends. In addition the
ground conductors at both ends of the cable must be bonded together by a power ground cable
(equal potential bonding cable) with cross-sectional area of at least 10 mm2. This ensures that in
the event of a fault, the fault current flows through the ground cable and not through signal cable
screen. If the building or plant has a well-designed common bonded network this precaution is not
necessary.
3. Additional over-voltage suppression. This applies to analogue and digital inputs and outputs. A
zener diode network or a commercially available surge suppressor may be connected between
the signal line and 0 V as shown in Figures 1 and 2.
Signal from plant Signal to drive
+
30V zener diode
e.g. 2×BZW50-15
0V 0V
Figure 1 Surge suppression for digital and unipolar analogue inputs and outputs
Signal from plant Signal to drive
0V 0V
Surge suppression devices are available as rail-mounting modules, e.g. from Phoenix Contact GmbH:
Unipolar TT-UKK5-D/24 DC
Bipolar TT-UKK5-D/24 AC
3. Emission
3.1 General
Emission occurs over a wide range of frequencies. The effects are divided into three main categories:
− Low frequency effects, such as supply harmonics and notching.
− High frequency emission below 30 MHz where emission is predominantly by conduction.
− High frequency emission above 30 MHz where emission is predominantly by radiation.
• First Environment - This includes domestic premises, and establishments that share a low-
voltage power supply network with buildings used for domestic purposes. Examples include:
houses, apartment buildings, shops, commercial property and industrial premises that share a
supply with nearby residential property.
• Second Environment - This includes all establishments other than those directly connected to
a low-voltage power supply network which supplies buildings used for domestic purposes.
Examples include Factories, industrial plants and areas of any building supplied by a
dedicated transformer.
• Equipment Category C1 - Equipment that is intended for use in the First Environment
• Equipment Category C2 - Equipment that is neither a plug-in device nor a movable device.
This type of equipment may be used in the First Environment if installed and commissioned
by a professional (i.e. person or organisation having the necessary skills to install and
commission power drive systems, including EMC requirements).
• Equipment Category C3 - Equipment that is intended only for use in the Second Environment.
The equipment is not intended for use in the First Environment
• Equipment Category C4 - Equipment with rated voltage ≥ 1000 V or rated current ≥ 400 A or
intended for use as part of a complex system. This equipment is intended only for use in the
Second Environment.
The drives are capable of meeting the requirements of Equipment Category C3 without external filters
or line reactors. They are capable of meeting the requirements of Equipment Category C2 when
installed with external EMC filters and line reactors.
In a domestic environment this product may cause radio interference in which case
NOTE:
supplementary mitigation measures may be required.
Note that the RMS current in the table may differ from the maximum specified in the installation guide,
since the latter is a worst case value provided for safety reasons which takes account of supply
voltage imbalance. The motor efficiency also affects the current. A standard IE2, 4 pole motor has
been assumed. For balanced sinusoidal supplies, all even and triple harmonics are absent. The
supply voltages used for the calculations are 200 V and 400 V at 50 Hz. The harmonic percentages
do not change substantially for other voltages and frequencies within the drive specification.
Table 5 shows the harmonic currents when the drives are fitted with the line reactors specified in
Table 3 below.
The line reactors cause a slight reduction in the input voltage at the drive terminals, which will
normally still permit the full rated torque to be developed in a standard motor. Higher inductance
values should not be used unless some reduction of available torque at maximum speed is
acceptable. Lower values can be used, and the resulting harmonics currents can be estimated by
linear interpolation between the values for no inductance and the inductance value in the tables
below. The reactor RMS current rating must be at least equal to the value shown in the table, and the
peak current rating should be twice the RMS value in order to avoid magnetic saturation.
IEC 61000-3-12
This standard applies to equipment rated > 16 A and ≤ 75 A per phase. The 200 V drives with power
ratings 1.5 kW, 2.2 kW, 3 kW and 4 kW and the 400 V drives with power ratings 5.5 kW and 7.5 kW
fall within the scope of this standard. Table 6 shows the harmonic currents when the drives are fitted
with the minimum line reactance (inductance) necessary to comply with this standard.
Note: RSCE is the short-circuit ratio. It is the ratio of the short circuit power of the supply to the rated
apparent power of the variable speed drive.
Note: Shaded cells are for Heavy Duty Mode. Unshaded cells are for Normal mode.
Note: Shaded cells are for Heavy Duty Mode. Unshaded cells are for Normal mode.
Table 6 Harmonic currents with minimum line reactance needed to comply with harmonic current limits in EN 61000-3-12, Table 4 for RSCE ≥ 120
AC line
Rated Motor RMS Fund. Harmonic order, magnitude as % of fundamental
THD PWHD choke DPF Power
Voltage Power current current
(%) (%) nom cos Ø factor
(V) (kW) (A) (A) 5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 (µH)
1.1 4.35 4.1 36.58 18.52 33.85 10.74 6.96 3.40 2.82 1.99 1.33 1.24 0.75 0.76 0.54 0.48 0.43 0.35 0.33 0.30 6000 0.9701 0.9114
200
0.75 3.83 3.6 38.79 19.76 35.68 12.13 7.26 3.45 3.07 1.99 1.50 1.30 0.82 0.83 0.56 0.52 0.43 0.36 0.32 0.29 6000 0.9719 0.9064
1.5 5.27 4.9 36.46 18.44 33.76 10.65 6.93 3.40 2.80 2.00 1.32 1.23 0.76 0.75 0.55 0.48 0.43 0.36 0.33 0.30 5000 0.97 0.9116
200
1.1 5.02 4.7 37.25 18.86 34.42 11.13 7.04 3.41 2.90 1.99 1.38 1.26 0.76 0.78 0.54 0.48 0.44 0.35 0.32 0.30 5000 0.9707 0.91
2.2 8.37 7.8 37.38 18.6 34.58 11.15 6.97 3.37 2.87 1.96 1.36 1.24 0.74 0.77 0.54 0.46 0.43 0.34 0.31 0.29 3000 0.9704 0.9094
200
1.5 6.24 5.7 43.24 21.72 39.31 15.17 7.61 3.72 3.36 1.99 1.78 1.34 1.03 0.93 0.65 0.64 0.45 0.45 0.35 0.32 3000 0.9736 0.8941
3 9.59 9 35.17 17.16 32.72 9.84 6.63 3.35 2.58 1.94 1.18 1.14 0.70 0.67 0.53 0.44 0.40 0.34 0.29 0.27 3000 0.9682 0.9137
200
2.2 8.09 7.6 38 19.12 35.09 11.54 7.07 3.39 2.94 1.98 1.42 1.27 0.78 0.80 0.55 0.50 0.44 0.36 0.33 0.30 3000 0.9709 0.908
1.1 2.37 2.2 38.45 19.24 35.46 11.86 7.10 3.41 2.96 1.98 1.44 1.27 0.80 0.81 0.54 0.51 0.43 0.36 0.33 0.29 18000 0.9706 0.9064
400
0.75 1.78 1.6 44.37 21.94 40.20 16.02 7.65 3.80 3.41 1.98 1.80 1.34 1.06 0.92 0.67 0.65 0.44 0.47 0.34 0.32 18000 0.9733 0.8902
1.5 3.12 2.9 37.05 18.34 34.31 10.96 6.86 3.37 2.80 1.96 1.32 1.23 0.74 0.76 0.54 0.47 0.44 0.35 0.33 0.30 15000 0.9692 0.9092
400
1.1 2.21 2 43.93 21.73 39.87 15.68 7.59 3.75 3.37 1.98 1.78 1.33 1.03 0.93 0.65 0.64 0.45 0.46 0.35 0.32 15000 0.9731 0.8914
2.2 4.30 4 37.31 18.17 34.58 11.05 6.80 3.34 2.77 1.94 1.31 1.22 0.73 0.75 0.54 0.46 0.44 0.34 0.32 0.30 11000 0.9687 0.908
400
1.5 3.20 2.9 43.16 21.04 39.32 15.07 7.42 3.62 3.27 1.94 1.69 1.32 0.97 0.89 0.63 0.60 0.42 0.44 0.33 0.30 11000 0.9724 0.8933
3 6.20 5.8 35.97 17.51 33.43 10.28 6.67 3.34 2.65 1.93 1.23 1.17 0.70 0.71 0.53 0.44 0.43 0.33 0.31 0.29 8000 0.9682 0.9114
400
2.2 5.06 4.7 39.53 19.7 36.38 12.53 7.17 3.42 3.05 1.96 1.50 1.30 0.82 0.84 0.57 0.52 0.44 0.38 0.33 0.31 8000 0.9712 0.9036
4 8.82 8.3 35.4 18.44 32.80 10.13 6.79 3.44 2.80 2.02 1.33 1.23 0.74 0.73 0.54 0.47 0.43 0.35 0.32 0.30 5000 0.9715 0.9162
400
3 6.74 6.3 40.02 21.22 36.61 13.14 7.33 3.53 3.27 2.04 1.68 1.38 0.95 0.90 0.61 0.58 0.43 0.42 0.34 0.31 5000 0.9748 0.9054
5.5 10.45 9.8 35.89 18.93 33.21 10.42 6.85 3.44 2.89 2.04 1.39 1.26 0.76 0.77 0.54 0.48 0.44 0.36 0.33 0.31 4000 0.9724 0.9156
400
4 8.61 8 39.19 20.91 35.95 12.56 7.22 3.49 3.22 2.04 1.64 1.37 0.92 0.88 0.60 0.56 0.43 0.40 0.34 0.30 4000 0.9747 0.9079
Note: Shaded cells are for Heavy Duty Mode. Unshaded cells are for Normal mode.
In order to comply with emission standards, a shielded (screened) cable must be used to connect the variable
speed drive to the motor. Most types of cable are acceptable provided that it has an overall screen that is
continuous for its entire length. For example, steel wire armoured cable is acceptable.
The Power Installation Guide gives instructions on how to remove and replace the internal EMC filter.
Suitable filters are available from Control Techniques. The ratings and part numbers are shown in Table 8.
1
Calculation with 3% capacitance tolerance
2 Calculation with two phases open circuit
Ref: 1-000-016-881 05 February 2018 Revision:00.06 Page 14 of 22
Unidrive-M Frame size 3 EMC Data Sheet
In practice, the external filter should always be used in conjunction with the internal filter. The total earth
leakage current with both filters connected may be higher than the figures shown above.
When either the internal filter, the external filter or both filters are connected, the earth
leakage current will exceed 3.5 mA.
A permanent fixed earth connection is necessary to avoid an electric shock hazard.
Further precautions, such as a supplementary earth connection or earth monitoring
system, may also be required.
Unusual hazards can occur on ungrounded supplies with more than one source, for example on ships.
Contact the supplier of the drive for more information.
Quasi-peak limit
Average limit
Quasi-peak
measurement
Average
measurement
Figure 3 Conducted emission, Model: M700-034 00100A, switching frequency = 3 kHz, motor cable length = 100 m
Notes:
1. Where the drive is incorporated into a system with rated input current exceeding 75 A, the higher
emission limits in IEC 61800-3 for the Second environment are applicable, and no filter is required.
2. Operation without a filter is a practical cost-effective option in an industrial environment where existing
levels of electrical noise are likely to be high, and any electrical equipment in operation has been
designed for such an environment. This is in accordance with IEC 61800-3 for the Second
Environment. There is some risk of disturbance to other equipment, and in this case the user and
supplier of the drive system must jointly take responsibility for correcting any problems that occur.
The limits for emission required by the generic emission standards are summarised in Table 13.
Note: The limits apply at a measuring distance of 10 m. The measurements may be made at 3 m with the
limits increased by 10 dB.
A standard enclosure was used having dimensions 1900 mm (high) × 600 mm (wide) × 500 mm (deep). Two
ventilation grilles, both 200 mm square, were provided on the upper and lower faces of the door.
The drive was mounted onto the EMC input filter, which was fitted to the internal back-plate of the enclosure,
the filter casing making electrical contact with the back-plate by the fixing screws. Standard unscreened power
cables were used to connect the complete unit to the supply.
A suitably rated, standard AC induction motor was connected by 2 m of shielded cable (steel braided - type
SY) and mounted externally.
The motor cable screen was clamped to the enclosure back-plate. The motor cable screen was also bonded
to the motor frame.
The motor cable was interrupted by a DIN rail terminal block mounted in the enclosure and the shield pigtails
(50 mm long) were bonded to the back plate through an earthed DIN rail terminal block.
In addition, the motor cable screen was bonded to the back-plate on both sides of the DIN rail using metal
clamps.
A 2 m screened control cable was connected to the drive control terminals with the screen clamped to the
enclosure back-plate
A 2 m unscreened status relay cable was connected to the drive.
A 2 m screened communications cable was connected to the drive. The screen was not electrically connected
to the drive or cubicle back panel.
The drive was operated at 6 Hz, with a switching frequency of 16 kHz. This is the worst case condition for
radiated emission.
No additional EMC preventative measures were taken, e.g. RFI gaskets around the cubicle doors.
The following tables summarise the results for radiated emission, showing the highest measurements over the
frequency range 30 MHz to 1000 MHz:
The results show that the limit for industrial radiated emission (C2) is met with a margin of at least 5 dB.
Depending on construction, the enclosure wall used for cable entry may have separate panels and could make
poor electrical contact at high frequencies with the remaining structure. If the motor cable is only bonded to
these surfaces and not to a back-plate, then the enclosure may provide insufficient attenuation of RF emission.
It is the bonding to a common metal plate which minimises radiated emission. In the tests described, opening
the cubicle door had little effect on the emission level, showing that the enclosure design is not critical.
3.4.6 Radiated emissions test limits for lifts, elevators and moving walkways.
The limits for Radiated Emissions in the standard for Electromagnetic compatibility, Product family standard
for lifts, escalators and moving walks, Emission, EN 12015 are the same as those in IEC 61800-3 for
equipment category C2.
Back-plate
Enclosure
To the motor
Isolator
(If required)