Location: ODIONGAN,ROMBLON AVERAGE TEMPERATURE IN ODIONGAN 2019

SOURCE: CLIMATE-DATA.ORG

Temperatures English SI

Winter Outdoor to 0 ºF 0.00 °C LEGENDS:


Winter Indoor ti 0 ºF 0.00 °C - Input Data
Sum. Outdoor todb 82 ºF 27.50 °C - Constant Data
towb 77 ºF 25.00 °C
Sp. Hum. #VALUE! Lbw/Lba MISCELLANEOUS FILES:
Rel. Hum. #VALUE! %
Sum. Indoor tidb 73 ºF 22.75 °C Psychrometric Chart - ASHRAE.PDF
tiwb 61 ºF 16.00 °C
Sp. Hum. #VALUE! Lbw/Lba where:
Rel. Hum. #VALUE! % U- Heat Transmission Coefficient
Daily Range DR 0 ºF 0.00 °C Qc - Cooling Load
Sens. Heat Ratio SHR 0.7 Qh - Heating Load
CLTD - Cooling Load Temperature Difference
Floor Area Aflr 1614.74 sq. ft. 150.09148 sq. m. SC - Shading Coefficient
Avg. Height CeilHt 19.686 ft. 6.0018293 m GLF - Gain Load Factor LEGEND:
Elevation Elev 31.8 ft 9.70 m Maximum Temperature
Latitude Lat 12.4047 ºN For Summer Indoor: Average Temperature
Building Leakage 2 Tight = 1 Medium=2 Loose =3 twib-16˚C is the average temperature for indoor AC (Thermal Comfort) Minimum Temperature

Zone 1
For heat transmission coefficient (Wall):
Windows U (4) SC (4) GLF (5) Area (sf) qc (Btu/h) qh(Btu/h) Material Thickness Density (lb/cu.ft) Weight (lb/sq.ft) Resistance ® FOR SUMMER OUTDOOR (tdb,twb,relative humidity,specific humidity) FOR SUMMER INDOOR (tdb,twb,relative humidity,specific humidity)
North 0 0.55 14.975 0.00 0.00 Air film 0.25
NE 0.55 0.55 19.678 253.1922 4982.2 0.0 Cement plaster 0.5 116 4.8 0.1
East 0 0.55 14.975 0.00 0.00 CHB 6 64 32 0.91
SE 0.55 0.55 19.678 158.9288 3127.3 0.0 Light Color Paint(White) 0.0495
South 0 0.55 14.975 0.00 0.00 Cement plaster 0.5 116 4.8 0.1
SW 0.55 0.55 19.678 354.3824 6973.4 0.0 Still air 0.68
West 0 0.3 8.168 0.00 0.00 TOTAL 7 296 41.6 2.0895
NW 0.55 0.55 19.678 13.76 270.8 0.0
Horz. 0 0.55 14.975 0.0 0.0 U =1/R
U= 0.478583
Walls U CLTD (6)
North 0 11.55 0.00 0.00
NE 0.4785 17.55 231.231 1941.8 0.0
East 0 21.55 0.00 0.00
SE 0.4785 19.55 164.02 1534.4 0.0
South 0 14.55 0.00 0.00
SW 0.4785 19.55 354.3824 3315.1 0.0
West 0 21.55 0.00 0.00
NW 0.4785 17.55 309.2 2596.6 0.0

Doors U CLTD (6)


North 0 11.55 0.0 0.0
NE 0 17.55 0.0 0.0
East 0 21.55 0 0.00 0.00
SE 0.25 19.55 46.5 227.3 0.0
South 0 14.55 0.0 0.0
SW 0 19.55 0.0 0.0
West 0 21.55 0 0.00 0.00 For Infiltration :
NW 0 5 17.55 0.0 0.0 ACH = (k)(NL)
Where:
Roof/Ceiling U CLTD (6) k = 1.44 s/hr.m)(0.0073 min/hr.ft
Roof 1 0 45.55 0 0.00 0.00 NL = 1000(ELA/Floor area) (No. of story) from ASTM E779 (2003)
Roof 2 0.0 0.0 ELA (Effictive leakage area)
NL (Normalized leakage) ASHRAE (Standard 119, 1998)
Partition U CLTD (6)
(To Unc. Space) 15.13 0.0 0.0 For ACH:
NL 40.0392238
Crawl Space U CLTD (6) ACH 0.42089232
(or floor garage) 15.13 0.0 0.0

Slab R (ins) U GLF Perimeter For Heat Transfer Coefficient (Slab):


0.5 19.678 1614.7442 15887.4682 0.00 Material Thickness(in) Resistance ®
CP 0.5 0.1
Infiltration ACH Vol cfm Still Air 0.92
Windy 0 0 0 0.00 RC 8 1.11
Summer 0.42 31787.9 223 2059.06 TOTAL 8.5 2.13

People Btu/h-per Number U =1/R


230 20 4600.00 U= 0.469484

Internal (AVG) Btu/h Watts


Kitchen/Laundry 0 0.00
Other (in watts) 1000 3412.00

Sensible
Cool Subtotal 50927.28
Heat Subtotal 0.00
Clg.Fac Htg.Fac
Duct 0 0 0.00 0.00

Sensible
Cool Total 50927.28
Heat Total 0.00

Net Total
Cooling Hp 28.59 Air Conditioning Unit Specification
KJ/s 21.3304854 Split Type Unit
KJ/hr 76789.7473 Brand: Koppel
Model: KSW-0995CA
Number of AC Units Needed Rated Volt: 208-230 V
7.3342643 Cooling Capacity: 9924 BTU/hr.(10470 KJ/hr.)
6-7 AC UNITS

Commercial Office Building Cooling Load Calcualtion (RSU-RESEARCH OFFICE)


Insulation Cooling Gains Heating Losses
Duct Location (hr-ft-F/Btu) Supply Return Supply<120 FSupply>120 F Return
Outdoors, open to well vented None 0.25 0.15 0.25 0.3 0.15
space, uninsulated, R2 0.15 0.08 0.15 0.2 0.08
unconditioned space R4 0.1 0.06 0.1 0.15 0.06
R6 0.05 0.03 0.05 0.1 0.03

Ducts located in enclosed, None 0.2 0.12 0.2 0.25 0.12


insulated, unconditioned, R2 0.1 0.06 0.1 0.15 0.06
unvented spaces R4 0.05 0.03 0.05 0.1 0.03
R6 0.03 0 0.03 0.05 0

None 0.1 0 0.1 0.15 0


Ducts located in return air R2 0.05 0 0.05 0.1 0
ceiling plenum R4 0.03 0 0.03 0.08 0
R6 0 0 0 0.03 0

None 0.1 0.06 0.1 0.15 0.06


Ducts buried in or under R2 0.05 0.03 0.05 0.1 0.03
concrete slab R4 0.03 0 0.03 0.08 0
R6 0 0 0 0.03 0

Ducts in conditioned space or 0 0 0 0 0


stubbed up in space, short run Any 0 0 0 0 0

Cooling Heating Factors


Factor
Table 5 - Shading Coefficients and U-Factors for Residential Windows

Drapes, Venetian Blind,


or Translucent Roller Opaque Roller
None Shade Shade
Glass Type SC U SC U SC U
Single 1.00 1.04 0.50 0.81 0.38 0.81
Double 0.88 0.61 0.45 0.55 0.36 0.55
Heat Absorbing 0.58 0.45 0.37 0.44 0.33 0.44
Triple 0.80 0.44 0.44 0.40 0.36 0.40

Source: ASHRAE Manual - 2001 Fundamentals, The American Society of Heating,


Refrigeration and Air Conditioning Engineers
Notes
1
2
3
4
5
6
7
Weather and climatic information available Table 1A & 1B, Chp. 27, 2001 ASHRAE Fundamental Handbook.
SHR = Sensible Load/Total Load Use: 0.65 for Tropic, 0.70 Humid, 0.75 Avg., 0.80 Dry, 0.85 Arid
Values curve fit fromTables 7 & 8, Chp. 28, 2001 ASHRAE Fundamental Handbook.
See Table 5, Chp. 28, 2001 ASHRAE Fundamental Handbook (reproduced ona another worksheet).
Values curve fit from Table 3, Chp. 28, 2001 ASHRAE Fundamental Handbook.
Values curve fit from Table 1, Chp. 28, 2001 ASHRAE Fundamental Handbook.
See Table 16, Chp. 28, 2001 ASHRAE Fundamental Handbook.