20 Mva Control Panel Problem Encounters-1
20 Mva Control Panel Problem Encounters-1
PARLAN
Regulatory Compliance Officer
: ENGR. GLENN D. TAN
OIC-Substation / Metering Section Head
: ENGR. GABRIEL FERNANDEZ
ESD-Department Head
FROM : BAUANG SUBSTATION
INCIDENT REPORT
Position Indicator malfunction (June 23, 2018)
Date
Bypassed Feeder Relay Protection (as stated)
Place Bauang Substation
Problem/Concern As stated.
Upon giving the clearance to de-energize the PGL Feeder Last
June 23, 2018 (0702H) Scheduled Annual Preventive
Maintenance. We use the position indicator to control / isolate the
circuit breaker from the feeder but it failed to operate, so we
decided to isolate the line from the push button on the breaker
(medium voltage switch gear) to isolate the line.
(A.T.O SF6) Last July 24, 2018 at 0216H & 0412H (1st & 2nd
encounters by passed PGL Feeder Relay Protection). The Operator
on duty conducted per equipment inspection for possible location of
fault inside the substation, but no identified possible equipment
failure. The troubleshooting also conducted site inspection on
distribution lines but reported “undertermined cause of trouble”.
Alarm annunciator indicated "No. 14 - SPARE" instead of
“No. 13 – Lock Out Relay 1 TRIP” for SF6 outage.
But PGL protection relay indicates phase to ground fault.
Alarm 1. (02:16h) ground time overcurrent 51G - G - 12.37 pu.
Alarm 2. (04:13h) phase time overcurrent 51P - B – 23.10 pu
Event/s & Action/s Alarm 3. (04:13h) phase time overcurrent 51P - B – 22.10 pu
Taken:
(A.T.O SF6) Last August 28, 2018 at 0541H (3rd encounters by
passed PGL Feeder Relay Protection) – reported
“ELECTROCUTED BIRD NEAR VILLA STRELLA”
Alarm annunciator indicated "No. 14 - SPARE" instead of
“No. 13 – Lock Out Relay 1 TRIP” for SF6 outage.
But PGL protection relay indicates phase to ground fault.
Alarm 1. (05:41h) Ground Time Overcurrent 51G - G - 18.26 pu.