SMHB SDN BHD: Jurutera Perunding

The document provides calculations for the design of a fascia section for a TNB substation. It includes input parameters such as material strengths, section dimensions, and loadings. The calculations determine the required reinforcement including main bars of T10-200 and distribution bars of T10-200. Checks are performed for bending reinforcement, shear capacity, and deflection which all meet requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
318 views5 pages

SMHB SDN BHD: Jurutera Perunding

The document provides calculations for the design of a fascia section for a TNB substation. It includes input parameters such as material strengths, section dimensions, and loadings. The calculations determine the required reinforcement including main bars of T10-200 and distribution bars of T10-200. Checks are performed for bending reinforcement, shear capacity, and deflection which all meet requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

SMHB Sdn Bhd Job No.

1023
Jurutera Perunding CALC SHEET NO.:
JOB NAME : KOTA SETAR CSTP CALCULATIONS BY: NSS Date
STRUCTURE : TNB SUB STATION CHECKED BY: Date
SECTION : FASCIA REVIEWED BY: Date
REF CALCULATION OUTPUT
150 450
Area 550
Area 1 = 0.107 710.6
Area 2 = 0.026
175
Total area = 0.133

730
INPUT DATA:
fcu = 30 KN/m2 height of fascia = 550 mm
fy = 460 KN/m2 L, cantilever = 730 mm
fyv = 250 KN/m2 effective depth = 175 mm
Slab thickness = 200 mm b = 1000 mm
Fascia thickness = 150 mm

Loadings
Characteristic load Dead Load = 4.8 KN/m2
For W Finishes = 1.8 KN/m2
Live Load = 0 KN/m2

Characteristic load Dead Load = 3.19 KN/m2


For P

considered 1 m length
Design Load = 9.24 KN/m
Design point load = 4.46 KN

Bending Reinforcement
Moment = 5.72 KNm/m
k = 0.006
z = 166.3 mm
As(required) = 79 mm2/m
As (min) = 300 mm2/m
Main bar Distribution bar
Bar diameter = 10 mm Bar diameter = 10 mm Main bar
spacing = 200 mm spacing = 200 mm T10-200

As provided = 393 mm2 OK As provided = 393 mm2 OK Distr. bar


T10-200 T10-200 T10-200

Shear Check
V = 11.21 KN
v = 0.06 N/mm2
100As/bd = 0.22
Vc = 0.50 N/mm2 SHEAR OK !

Deflection check
Basic ratio = 7
L/d actual = 4
M/bd2 = 0.19
fs = 234
MF = 2.00
L/d allow = 14.00 DEFLECTION OK!
11/9/19

OUTPUT

Main bar
T10-200

Distr. bar
T10-200
SMHB Sdn. Bhd Job No. 1023
Jurutera Perunding CALC SHEET NO.:
JOB NAME : CENTRALISED SEWAGE TREATMENT PLANT CALCULATIONS BY: ASM Date 10/18/2019
STRUCTURE : REFUSE CHAMBER CHECKED BY: Date
SECTION : APRON REVIEWED BY: Date
REF CALCULATION OUTPUT
CANTILEVER SLAB

100

1150
INPUT DATA:
fcu = 30 KN/m2
fy = 500 KN/m2 L, cantilever = 1150 mm
fyv = 500 KN/m2 effective depth = 90 mm
Slab thickness = 100 mm b = 1000 mm

Loadings
Characteristic load Dead Load = 2.4 KN/m2
Live Load = 1.5 KN/m2

considered 1 m length
Design Load = 5.76 KN/m

Bending Reinforcement

Moment = 3.81 KNm/m


k = 0.02
z = 85.5 mm
As(required) = 102 mm2/m
As (min) = 150 mm2/m

Main bar Distribution bar


Bar diameter = 10 mm Bar diameter = 10 mm Main bar
spacing = 200 mm spacing = 200 mm T10-200

As provided = 393 mm2 OK As provided = 393 mm2 OK Dist. bar


T10-200 T10-200 T10-200

Shear Check
V = 6.62 KN
v = 0.07 N/mm2
100As/bd = 0.44
Vc = 0.74 N/mm2 SHEAR OK !

Deflection check
Basic ratio = 7
L/d actual = 12.78
M/bd2 = 0.47
fs = 119
MF = 2.00
L/d allow = 14.00 DEFLECTION OK!